Plan Review Notes For Permit 07120174 |
Permit Number |
07120174 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-02-06 19:13:17 | *****UNSAT***** | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 08.YOUR RESPONSE INDICATED THAT THIS BUILDING DOES | | HAVE A FIRE ALARM SYSTEM.PLEASE SHOW A LAYOUT OF THE | | FIRE ALARM DEVICES FOR THIS SITE. | | | | 09.ON SHEET FS-1 UNDER THE SYMBOL LEGEND, THE SYMBOL | | FOR THE NEW SPRINKLER PIPE AND THE EXISTING SPRINKLER | | PIPE APPEAR TO BE THE SAME. | | | | 10.IT IS NOTED ON SHEET FS-1, THAT ALL SPRINKLER | | EQUIPMENT AT THE SITE IS EXISTING - NO MODIFICATIONS | | REQUIRED.HOWEVER, IN THE FIRE SPRINKLER SCHEDULE ON | | SHEET FS-1, THERE ARE 89 NEW SEMI RECESSED PENDENT | | SPRINKLERS WHICH ARE SHOWN IN THE OFFICE AREA ON SHEET | | FS-2 AND ALSO THE REMOVAL OF EXISTING HEADS THAT | | CURRENTLY PROTECT UNDER OVERHEAD DOORS SHOWN IN THE | | GARAGE AREA (SHEET FS-2).PLEASE EXPLAIN OR AMEND. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|