2007-12-22 13:10:59 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2007 REVISIONS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. EXISTING BUILDING: THE LEVEL OF ALTERATION IS NOT |
| DECLARED ON PLANS. THE DESIGN PROFESSIONAL OR OWNER |
| MUST ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION |
| PURSUANT TO SECTIONS 303, 304 AND 305 OF THIS CODE IN |
| ACCORDANCE WITH FBC, EB 301.5. FOR THE PURPOSE OF |
| MECHANICAL REVIEW THE PROPOSED SCOPE OF WORK WILL BE |
| CONSIDERED A LEVEL 3 ALTERATION AS DEFINED IN FBC, EB |
| 305.1. LEVEL 3 ALTERATIONS SHALL COMPLY WITH THE |
| PROVISIONS OF CHAPTERS 5 AND 6 FOR LEVEL 1 AND 2 |
| ALTERATIONS, RESPECTIVELY, AS WELL AS THE PROVISIONS OF |
| CHAPTER 7 IN ACCORDANCE WITH FBC, EB 305.2. |
| |
| 2. OUTSIDE AIR CALCULATIONS HAVE NOT BEEN PROVIDED. ALL |
| RECONFIGURED SPACES INTENDED FOR OCCUPANCY SHALL BE |
| PROVIDED WITH NATURAL OR MECHANICAL VENTILATION OR |
| EXHAUST IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| MECHANICAL. SHOW COMPLIANCE WITH FBC, M 403.3 OR ASHRAE |
| 62.1-2004 FOR ALL HABITABLE SPACES IN ACCORDANCE WITH |
| FBC, EB 609.1. |
| |
| 3. HVAC GENERAL NOTE #27 ON M-2: FAN SHUT-DOWN BY SMOKE |
| DETECTOR IS REQUIRED FOR ALL AIR HANDLERS IN THIS SPACE |
| SINCE ALL UNITS SHARE A COMMON RETURN PLENUM IN |
| ACCORDANCE WITH FBC, M 606.2.2. SMOKE DETECTORS SHALL |
| BE CONNECTED TO THE BUILDING FIRE ALARM SYSTEM IN |
| ACCORDANCE WITH FBC, M 606.4.1. |
| |
| 4. FIRE DAMPER DETAIL ON M-2: FIRE DAMPERS LOCATED |
| WITHIN AIR DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN |
| ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER?S |
| INSTALLATION INSTRUCTIONS AND LISTING PER FBC, M |
| 607.2. |
| NOTE: IT IS LIKELY THAT MANUFACTURER?S INSTRUCTIONS |
| WILL NOT CORRESPOND WITH THE DETAIL ON PLANS. |
| |
| 5. PG A-3.2: ROOF DECK NOTE AT WALL SECTIONS CALLS FOR |
| ICYNENE INSULATION TO BE APPLIED TO THE UNDERSIDE OF |
| THE ROOF DECK. THIS SPACE IS BEING USED AS A RETURN AIR |
| PLENUM. FOAM PLASTIC INSULATION (SUCH AS ICYNENE) USED |
| IN A PLENUM SHALL BE IN COMPLIANCE WITH FBC, M |
| 602.2.1.5. SEE ALSO FBC 2603.4. |
| |
| 6. PG M-2 GARAGE VENTILATION: THE FAN IS SHOWN TO BE |
| OPERATED BY A CO2 SENSOR SET AT 900 PARTS PER MILLION |
| (PPM). MECHANICAL VENTILATION SYSTEMS FOR ENCLOSED |
| PARKING GARAGES ARE NOT REQUIRED TO OPERATE |
| CONTINUOUSLY WHERE THE SYSTEM IS ARRANGED TO OPERATE |
| AUTOMATICALLY UPON DETECTION OF A CONCENTRATION OF |
| CARBON MONOXIDE OF 25 PARTS PER MILLION (PPM) BY |
| APPROVED AUTOMATIC DETECTION DEVICES IN ACCORDANCE WITH |
| FBC, M 404.1. ALSO, AUTOMATIC OPERATION OF THE SYSTEM |
| SHALL NOT REDUCE THE VENTILATION RATE BELOW0.05 CFM |
| PER SQUARE FOOT OF THE FLOOR AREA AND THE SYSTEM SHALL |
| BE CAPABLE OF PRODUCING A VENTILATION RATE OF 1.5 CFM |
| PER SQUARE FOOT OF FLOOR AREA IN ACCORDANCE WITH FBC, M |
| 404.2. |
| |