Plan Review Notes
Plan Review Notes For Permit 07120174
Permit Number 07120174
Review Stop M
Sequence Number 1
Notes
Date Text
2007-12-22 13:10:59REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. EXISTING BUILDING: THE LEVEL OF ALTERATION IS NOT
 DECLARED ON PLANS. THE DESIGN PROFESSIONAL OR OWNER
 MUST ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTIONS 303, 304 AND 305 OF THIS CODE IN
 ACCORDANCE WITH FBC, EB 301.5. FOR THE PURPOSE OF
 MECHANICAL REVIEW THE PROPOSED SCOPE OF WORK WILL BE
 CONSIDERED A LEVEL 3 ALTERATION AS DEFINED IN FBC, EB
 305.1. LEVEL 3 ALTERATIONS SHALL COMPLY WITH THE
 PROVISIONS OF CHAPTERS 5 AND 6 FOR LEVEL 1 AND 2
 ALTERATIONS, RESPECTIVELY, AS WELL AS THE PROVISIONS OF
 CHAPTER 7 IN ACCORDANCE WITH FBC, EB 305.2.
  
 2. OUTSIDE AIR CALCULATIONS HAVE NOT BEEN PROVIDED. ALL
 RECONFIGURED SPACES INTENDED FOR OCCUPANCY SHALL BE
 PROVIDED WITH NATURAL OR MECHANICAL VENTILATION OR
 EXHAUST IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL. SHOW COMPLIANCE WITH FBC, M 403.3 OR ASHRAE
 62.1-2004 FOR ALL HABITABLE SPACES IN ACCORDANCE WITH
 FBC, EB 609.1.
  
 3. HVAC GENERAL NOTE #27 ON M-2: FAN SHUT-DOWN BY SMOKE
 DETECTOR IS REQUIRED FOR ALL AIR HANDLERS IN THIS SPACE
 SINCE ALL UNITS SHARE A COMMON RETURN PLENUM IN
 ACCORDANCE WITH FBC, M 606.2.2. SMOKE DETECTORS SHALL
 BE CONNECTED TO THE BUILDING FIRE ALARM SYSTEM IN
 ACCORDANCE WITH FBC, M 606.4.1.
  
 4. FIRE DAMPER DETAIL ON M-2: FIRE DAMPERS LOCATED
 WITHIN AIR DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS AND LISTING PER FBC, M
 607.2.
 NOTE: IT IS LIKELY THAT MANUFACTURER?S INSTRUCTIONS
 WILL NOT CORRESPOND WITH THE DETAIL ON PLANS.
  
 5. PG A-3.2: ROOF DECK NOTE AT WALL SECTIONS CALLS FOR
 ICYNENE INSULATION TO BE APPLIED TO THE UNDERSIDE OF
 THE ROOF DECK. THIS SPACE IS BEING USED AS A RETURN AIR
 PLENUM. FOAM PLASTIC INSULATION (SUCH AS ICYNENE) USED
 IN A PLENUM SHALL BE IN COMPLIANCE WITH FBC, M
 602.2.1.5. SEE ALSO FBC 2603.4.
  
 6. PG M-2 GARAGE VENTILATION: THE FAN IS SHOWN TO BE
 OPERATED BY A CO2 SENSOR SET AT 900 PARTS PER MILLION
 (PPM). MECHANICAL VENTILATION SYSTEMS FOR ENCLOSED
 PARKING GARAGES ARE NOT REQUIRED TO OPERATE
 CONTINUOUSLY WHERE THE SYSTEM IS ARRANGED TO OPERATE
 AUTOMATICALLY UPON DETECTION OF A CONCENTRATION OF
 CARBON MONOXIDE OF 25 PARTS PER MILLION (PPM) BY
 APPROVED AUTOMATIC DETECTION DEVICES IN ACCORDANCE WITH
 FBC, M 404.1. ALSO, AUTOMATIC OPERATION OF THE SYSTEM
 SHALL NOT REDUCE THE VENTILATION RATE BELOW0.05 CFM
 PER SQUARE FOOT OF THE FLOOR AREA AND THE SYSTEM SHALL
 BE CAPABLE OF PRODUCING A VENTILATION RATE OF 1.5 CFM
 PER SQUARE FOOT OF FLOOR AREA IN ACCORDANCE WITH FBC, M
 404.2.
  