Date |
Text |
2008-01-02 13:54:52 | *****DENIED***** |
| |
| |
| 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 02.THE SCOPE OF WORK SHALL NO NOT HINDER OR INTERFERE |
| WITH EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR |
| VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE |
| LANES). |
| |
| 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| SHALL BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY |
| AS NECESSARY FOR SAFE OPERATION. |
| |
| 04.WILL THE BUILDING OR PORTION OF THE BUILDING BE |
| OCCUPIED DURING THE SCOPE OF WORK?IF THE BUILDING OR |
| PORTION OF THE BUIDLING IS TO BE OCCUPIED DURING THIS |
| SCOPE OF WORK, THIS WILL DONE ONLY WHERE REQUIRED MEANS |
| OF EGRESS AND REQUIRED FIRE PROTECTION FEATURES ARE IN |
| PLACE AND MAINTAINED. |
| |
| 05.FIRE EXTINGUISHERS TO BE 2A:10BC RATED.AMEND |
| SHEET A-4.0 TO REFLECT AS SUCH. |
| |
| 06.ON THE APPROPIATE EXTERIOR ELEVATION (SHEET A |
| 5.0), DISPLAY/SHOW THE NUMERICAL ADDRESS FOR THIS |
| BUILDING.AS PER WEST PALM BEACH CODE, THE ADDRESS |
| SHALL BE POSTED ON THAT PORTION OF THE STRUCTURE |
| FRONTING OR FACING UPON THE STREET OR PRINCIPAL |
| VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE READILY |
| VISIBLE TO APPROACHING VEHICLES.ALSO, THE NUMBERS |
| SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" |
| IN WIDTH. |
| |
| 07.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| REFERENCED. |
| |
| 08.IT IS NOT INDICATED IF THIS BUILDING HAS A FIRE |
| ALARM SYSTEM OR NOT.HOW IS THE FIRE DEPARTMENT |
| NOTIFIED IF THE ACTIVATION OF OF A FIRE SPRINKLER |
| OCCURS DURING NON-BUSINESS HOURS? |
| |
| 09.ON SHEET FS-1 UNDER THE SYMBOL LEGEND, THE SYMBOL |
| FOR THE NEW SPRINKLER PIPE AND THE EXISTING SPRINKLER |
| APPEAR TO BE THE SAME. |
| |
| 10.IT IS NOTED ON SHEET FS-1, THAT ALL SPRINKLER |
| EQUIPMENT AT THE SITE IS EXISTING - NO MODIFICATIONS |
| REQUIRED.HOWEVER, IN THE FIRE SPRINKLER SCHEDULE ON |
| SHEET FS-1, THERE ARE 89 NEW SEMI RECESSED PENDENT |
| SPRINKLERS WHICH ARE SHOWN IN THE OFFICE AREA ON SHEET |
| FS-2 AND ALSO THE REMOVAL OF EXISTING HEADS THAT |
| CURRENTLY PROTECT UNDER OVERHEAD DOORS SHOWN IN THE |
| GARAGE AREA (SHEET FS-2).PLEASE EXPLAIN OR AMEND. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |