Plan Review Notes
Plan Review Notes For Permit 07120174
Permit Number 07120174
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-01-02 13:54:52*****DENIED*****
  
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.THE SCOPE OF WORK SHALL NO NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES).
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY
 AS NECESSARY FOR SAFE OPERATION.
  
 04.WILL THE BUILDING OR PORTION OF THE BUILDING BE
 OCCUPIED DURING THE SCOPE OF WORK?IF THE BUILDING OR
 PORTION OF THE BUIDLING IS TO BE OCCUPIED DURING THIS
 SCOPE OF WORK, THIS WILL DONE ONLY WHERE REQUIRED MEANS
 OF EGRESS AND REQUIRED FIRE PROTECTION FEATURES ARE IN
 PLACE AND MAINTAINED.
  
 05.FIRE EXTINGUISHERS TO BE 2A:10BC RATED.AMEND
 SHEET A-4.0 TO REFLECT AS SUCH.
  
 06.ON THE APPROPIATE EXTERIOR ELEVATION (SHEET A
 5.0), DISPLAY/SHOW THE NUMERICAL ADDRESS FOR THIS
 BUILDING.AS PER WEST PALM BEACH CODE, THE ADDRESS
 SHALL BE POSTED ON THAT PORTION OF THE STRUCTURE
 FRONTING OR FACING UPON THE STREET OR PRINCIPAL
 VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE READILY
 VISIBLE TO APPROACHING VEHICLES.ALSO, THE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1"
 IN WIDTH.
  
 07.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 08.IT IS NOT INDICATED IF THIS BUILDING HAS A FIRE
 ALARM SYSTEM OR NOT.HOW IS THE FIRE DEPARTMENT
 NOTIFIED IF THE ACTIVATION OF OF A FIRE SPRINKLER
 OCCURS DURING NON-BUSINESS HOURS?
  
 09.ON SHEET FS-1 UNDER THE SYMBOL LEGEND, THE SYMBOL
 FOR THE NEW SPRINKLER PIPE AND THE EXISTING SPRINKLER
 APPEAR TO BE THE SAME.
  
 10.IT IS NOTED ON SHEET FS-1, THAT ALL SPRINKLER
 EQUIPMENT AT THE SITE IS EXISTING - NO MODIFICATIONS
 REQUIRED.HOWEVER, IN THE FIRE SPRINKLER SCHEDULE ON
 SHEET FS-1, THERE ARE 89 NEW SEMI RECESSED PENDENT
 SPRINKLERS WHICH ARE SHOWN IN THE OFFICE AREA ON SHEET
 FS-2 AND ALSO THE REMOVAL OF EXISTING HEADS THAT
 CURRENTLY PROTECT UNDER OVERHEAD DOORS SHOWN IN THE
 GARAGE AREA (SHEET FS-2).PLEASE EXPLAIN OR AMEND.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW