Plan Review Notes For Permit 07120146 |
Permit Number |
07120146 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-06-10 14:09:15 | SPECS AND PHOTOS SUBMITTED SHOW A SERVICE ENTRANCE | | RATED ATS WITH MANUAL MEANS OF DISCONNECT RATED FOR THE | | LOAD SERVED. | | NO LIVE PARTS APPEAR AS PLEXIGLASS DEADFRONT IS SHOWN | | ON PICS. | | SHOWS MANUAL HANDLE. INSPECTOR TO VERIFY CENTER OFF | | POSITION WHICH WILL KEEP POWER FROM SERVICE UNDER | | NORMAL OR EMERGENCY OPERATIONS. | | | | ** THIS BACK UP GENERATOR IS FOR "OPTIONAL STAND-BY | | POWER" ONLY. | | ALL EM LTS AND EXIT LIGHTS ARE BATTERY BACK AND | | EXISTING PER CONTRACRTOR. |
|