2008-06-10 14:09:15SPECS AND PHOTOS SUBMITTED SHOW A SERVICE ENTRANCE
 RATED ATS WITH MANUAL MEANS OF DISCONNECT RATED FOR THE
 LOAD SERVED.
 NO LIVE PARTS APPEAR AS PLEXIGLASS DEADFRONT IS SHOWN
 ON PICS.
 SHOWS MANUAL HANDLE. INSPECTOR TO VERIFY CENTER OFF
 POSITION WHICH WILL KEEP POWER FROM SERVICE UNDER
 NORMAL OR EMERGENCY OPERATIONS.
  
 ** THIS BACK UP GENERATOR IS FOR "OPTIONAL STAND-BY
 POWER" ONLY.
 ALL EM LTS AND EXIT LIGHTS ARE BATTERY BACK AND
 EXISTING PER CONTRACRTOR.