Date Text
2008-05-27 10:42:44***DENIED***
  
 NO RESPONSE TO FIRST FIRE REVIEW COMMENTS:
  
 1) OK
  
 2) OK
  
 3) PLEASE INDICATE IF THE NEWLY INSTALLED GENERATOR IS
 FOR EMERGENCY USE OR FOR STANDBY POWER FOR FIRE
 PROTECTION SYSTEMS OR BOTH.
  
 4) IT IS INDICATED THAT THE PROPSED EQUIPMENT WILL BE A
 500 GALLON DIESEL FUEL ENGINE GENERATOR. STORAGE AND
 HANDLING OF FLAMMABLE LIQUIDS OR GASES SHALL BE IN
 ACCORDANCE WITH NFPA 30 AND NFPA 54.
  
  
 NEW COMMENT:
  
 1) WORK TO COMPLY WITH NFPA 110, STANDARD FOR EMERGENCY
 AND STANDBY POWER SYSTEMS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW