2008-05-04 14:04:41 | ** DENIED REVIEW ** |
| |
| 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH |
| RESPECT TO THE SERVICE ENTRANCE RATED ATS AND |
| DISCONNECTING MEANS REQUIRED FOR FEEDERS FROM ATS. |
| PLEASE SEE 230.76,230.79 AND 225.31-225.39 AS THE |
| DISCONNECTING MEANS FOR THE SERVICE SHALL MEET230.76, |
| 230.79. |
| THE DISCONNECTING MEANS FOR THE FEEDERS NEEDS TO MEET |
| 225.31-225.39 UNLESS MEETING THE EXCEPTION IN THE CODE |
| IN 702.11. |
| PLEASE KNOW ANY GENERATOR BREAKER WHEN USED AS THE |
| DISCONNECTING MEANS SHALL NOT BE IN A LOCKED ENCLOSURE |
| AND BASED ON THE ATS SPECS SHOWN THERE IS NO DISCONNECT |
| READILY ACCESSIBLE FOR FIRE DEPARTMENT OR OTHER |
| PERSONNEL. |
| PLEASE KNOW ANY INDIVIDUAL MAY NOT BE EXPOSED TO LIVE |
| PARTS WHEN OPERATING THE ATS PER 110.27 |
| PLEASE KNOW THESE TWO ITEMS STILL NEED TO MEET CODE AND |
| INSTALLATION FOR SAFE OPERATION FOR ALL OCCUPANTS AS |
| WELL AS OTHER PERSONNEL. |
| PAGE TWO OF THE SUBMITTAL STATES THE SERVICE DISCONNECT |
| TO MECHANICALLY AND ELECTRICAL OPEN BOTH BREAKERS |
| HOWEVER NEED TO VERIFY DEAD FRONT AND HOW THIS WILL |
| TAKE PLACE. |
| PLEASE CONTACT THIS OFFICE. CONTACT COULD NOT BE MADE |
| TO CONTRACTOR AS THEIR OFFICE WAS CLOSED AT THE TIME OF |
| THIS REVIEW. |
| |
| 2) NOTE: PLEASE KNOW THIS OFFICE STILL NEEDS TO VERIFY |
| WHETHER OR NOT BUILDING CONTAINS BATTERY BACK UP LIGHT |
| FIXTURES FOR EMERGENCY LIGHTS AND EXIT LIGHTS. THIS |
| NEEDS TO BE STATED ON PLANS. IF BUILDING IS GOING TO BE |
| OCCUPIED AND IN USE UNDER EMERGENCYPOWER WHICH SEEMS |
| TO BE THE INTENT OF THIS UNIT,BATTERY BACK UP |
| FIXTURES AS NOTED ABOVE SHALL BE INSTALLED IF NOT |
| EXISTING FOR MINIMUM LIFE SAFETY. |
| NFPA-10 17.8, 7.9. |
| |
| PLEASE CONTACT THIS REVIEWER FOR ANY QUESTIONS AND TO |
| PROVIDE INFORMATION. |
| |