2007-12-12 12:33:25 | ** DENIED ** |
| |
| RED CROSS |
| NEW GENERATOR INSTALL. |
| |
| 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| ON PLANS.(ELECTRICAL PLANS) |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-110 |
| |
| 2) NOTE: PLEASE SEE THE ELECTRICAL PLANS SUBMITTED ARE |
| REQUIRED TO CONTAIN AND PRINTED NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE PER FS 471.003, 489. |
| |
| 3) NOTE: PLEASE SPECIFY IF THE GENERATOR WILL BE A |
| SEPARATELY DERIVED SYSTEM. |
| PLEASE SEE NEC 250.30, 250.20 ETC AS A FOUR POLE ATS |
| WOULD BE REQUIRED. |
| |
| 4) NOTE: PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS FOR |
| THE PROPOSED ATS. |
| PLEASE ALSO SEE NOTES FROM FIRE AND MECHANICAL REVIEW |
| FOR SPECS/CUT SHEETS FOR FUEL TANK ALSO. |
| 90.7, 110.3 |
| FBC 106.1.2 |
| |
| 5) NOTE: PLEASE SUBMIT AN OVER VIEW OF ALL ELECTRICAL |
| EQUIPMENT AND LOCATIONS. |
| PLEASE KNOW SOME ITEMS FOR REVIEW OF CODE COMPLIANCE |
| CAN NOT BE DONE AT THIS TIME. |
| 110.26,ETC |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 6) NOTE: PLEASE SEE 225.31-225.39 FOR REQUIRED |
| DISCONNECTING MEANS FOR FEEDERS AT THE BUILDING. PLEASE |
| SEE THERE IS AN EXCEPTION WHICH IS PROVIDED IN 700,701 |
| AND 702 HOWEVER THE DISCONNECTING MEANS MUST BE *WITHIN |
| SIGHT* AND *READILY ACCESSIBLE*. |
| |
| 7) NOTE: PLEASE PROVIDE INFORMATION ON PLANS WHETHER OR |
| NOT THIS PROPOSED SYSTEM FEEDS ANY LEGALLY REQUIRED OR |
| LIFE SAFETY SYSTEMS PER 700 OR 701. |
| |
| 8) NOTE: PLEASE PROVIDE A PANEL SCHEDULE SHOWING OVER |
| CURRENT PROTECTION DEVICES, CONDUCTOR SIZES ETC FOR ALL |
| BRANCH CIRCUITS TO GENERATOR CONTROL PANEL OR ANY OTHER |
| SYSTEMS/DEVICES WHICH ARE BEING INSTALLED. |
| FOR EXAMPLE: SHEET ATTACHED TO GENERATOR SPECS |
| INDICATES HEATER ETC. |
| FBC 106.3.5.1.2, 106.1.2 |
| NEC 310.16, 240.4, 408.4 |
| |
| 9) NOTE: PLEASE PROVIDE FURTHER INFORMATION AND |
| CLARIFICATION OF THE *PROTOTYPE CERTIFICATION* SHEET |
| SUBMITTED. |
| PLEASE VERIFY UNIT IS LISTED AND CERTIFIED BY |
| MANUFACTURE BEFORE AND AFTER INSTALL. |
| 110.3, 90.7 |
| FBC 106.1.2 |
| |
| 10) NOTE: PLEASE KNOW A GENERAL CONTRACTOR WILL BE |
| REQUIRED FOR THE BUILDING SCOPE OF WORK AS SHOWN ON |
| PLANS. |
| THIS COMMENT MAY BE PRESENT IN OTHER REVIEWS. |
| |
| 11) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS SUBMITTED |
| ARE NOT SIGNED, OR SEALED BY THE ARCHITECT. |
| FS 481.221 |
| |
| 12) NOTE: PLEASE LIST OCP AT THE GENERATOR. |
| 310.16, 240.4, 445.13 |
| SIZING OF CONDUCTORS CAN NOT BE VERIFIED AT THIS TIME |
| PER 445.13 |
| |
| ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET |
| SUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS ON THE |
| FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |