Plan Review Notes
Plan Review Notes For Permit 07120146
Permit Number 07120146
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-12 12:33:25** DENIED **
  
 RED CROSS
 NEW GENERATOR INSTALL.
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS.(ELECTRICAL PLANS)
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-110
  
 2) NOTE: PLEASE SEE THE ELECTRICAL PLANS SUBMITTED ARE
 REQUIRED TO CONTAIN AND PRINTED NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE PER FS 471.003, 489.
  
 3) NOTE: PLEASE SPECIFY IF THE GENERATOR WILL BE A
 SEPARATELY DERIVED SYSTEM.
 PLEASE SEE NEC 250.30, 250.20 ETC AS A FOUR POLE ATS
 WOULD BE REQUIRED.
  
 4) NOTE: PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS FOR
 THE PROPOSED ATS.
 PLEASE ALSO SEE NOTES FROM FIRE AND MECHANICAL REVIEW
 FOR SPECS/CUT SHEETS FOR FUEL TANK ALSO.
 90.7, 110.3
 FBC 106.1.2
  
 5) NOTE: PLEASE SUBMIT AN OVER VIEW OF ALL ELECTRICAL
 EQUIPMENT AND LOCATIONS.
 PLEASE KNOW SOME ITEMS FOR REVIEW OF CODE COMPLIANCE
 CAN NOT BE DONE AT THIS TIME.
 110.26,ETC
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE SEE 225.31-225.39 FOR REQUIRED
 DISCONNECTING MEANS FOR FEEDERS AT THE BUILDING. PLEASE
 SEE THERE IS AN EXCEPTION WHICH IS PROVIDED IN 700,701
 AND 702 HOWEVER THE DISCONNECTING MEANS MUST BE *WITHIN
 SIGHT* AND *READILY ACCESSIBLE*.
  
 7) NOTE: PLEASE PROVIDE INFORMATION ON PLANS WHETHER OR
 NOT THIS PROPOSED SYSTEM FEEDS ANY LEGALLY REQUIRED OR
 LIFE SAFETY SYSTEMS PER 700 OR 701.
  
 8) NOTE: PLEASE PROVIDE A PANEL SCHEDULE SHOWING OVER
 CURRENT PROTECTION DEVICES, CONDUCTOR SIZES ETC FOR ALL
 BRANCH CIRCUITS TO GENERATOR CONTROL PANEL OR ANY OTHER
 SYSTEMS/DEVICES WHICH ARE BEING INSTALLED.
 FOR EXAMPLE: SHEET ATTACHED TO GENERATOR SPECS
 INDICATES HEATER ETC.
 FBC 106.3.5.1.2, 106.1.2
 NEC 310.16, 240.4, 408.4
  
 9) NOTE: PLEASE PROVIDE FURTHER INFORMATION AND
 CLARIFICATION OF THE *PROTOTYPE CERTIFICATION* SHEET
 SUBMITTED.
 PLEASE VERIFY UNIT IS LISTED AND CERTIFIED BY
 MANUFACTURE BEFORE AND AFTER INSTALL.
 110.3, 90.7
 FBC 106.1.2
  
 10) NOTE: PLEASE KNOW A GENERAL CONTRACTOR WILL BE
 REQUIRED FOR THE BUILDING SCOPE OF WORK AS SHOWN ON
 PLANS.
 THIS COMMENT MAY BE PRESENT IN OTHER REVIEWS.
  
 11) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS SUBMITTED
 ARE NOT SIGNED, OR SEALED BY THE ARCHITECT.
 FS 481.221
  
 12) NOTE: PLEASE LIST OCP AT THE GENERATOR.
 310.16, 240.4, 445.13
 SIZING OF CONDUCTORS CAN NOT BE VERIFIED AT THIS TIME
 PER 445.13
  
 ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET
 SUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  