1 |
|
Notes |
Date |
Text |
2007-12-28 15:09:37 | | | BUILDING PLAN REVIEW | | PERMIT: 07120146 | | ADD: 825 FERN STREET | | CONT: MALONE ELECTRICAL SOLUTIONS | | TEL: (561)644-9495 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW: 1ST | | ACTION: DENIED | | 12/28/07 | | | | 1) 2004 FBC 1609.1.3 PLEASE PROVIDE INFORMATION ON THE | | ANCHORAGE THE GENERATOR TO RESIST THE MOMENT OF | | OVERTURNING, UPLIFT AND SLIDING. | | GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE | | SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE | | INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF | | FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE | | REQUIRES WITHOUT LOAD REDUCTION. | | | | 2) FBC 106.1 PLANS, SPECIFICATIONS, REPORTS OR OTHER | | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING | | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE | | DOCUMENT. | | FL ADMIN CODE 61G15-23.002 ENGINEERS | | FL ADMIN CODE 61G16.003 ARCHITECTS | | | | 3)A GENERAL CONTRACTOR IS REQUIRED TO BUILD THE WALL | | AND FOUNDATION PAD FOR THE GENERATOR. THE ELECTRICAL | | CONTRACTOR IS NOT QUALIFIED TO DO THIS TYPE OF WORK. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] |
|