Plan Review Notes
Plan Review Notes For Permit 07120146
Permit Number 07120146
Review Stop B
Sequence Number 1
Notes
Date Text
2007-12-28 15:09:37 
 BUILDING PLAN REVIEW
 PERMIT: 07120146
 ADD: 825 FERN STREET
 CONT: MALONE ELECTRICAL SOLUTIONS
 TEL: (561)644-9495
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 12/28/07
  
 1) 2004 FBC 1609.1.3 PLEASE PROVIDE INFORMATION ON THE
 ANCHORAGE THE GENERATOR TO RESIST THE MOMENT OF
 OVERTURNING, UPLIFT AND SLIDING.
 GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE
 SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE
 INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION.
  
 2) FBC 106.1 PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3)A GENERAL CONTRACTOR IS REQUIRED TO BUILD THE WALL
 AND FOUNDATION PAD FOR THE GENERATOR. THE ELECTRICAL
 CONTRACTOR IS NOT QUALIFIED TO DO THIS TYPE OF WORK.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]