Plan Review Notes
Plan Review Notes For Permit 07120104
Permit Number 07120104
Review Stop Z
Sequence Number 1
Notes
Date Text
2007-12-10 10:29:28***FAILED***
  
  
 1)PLEASE PROVIDE TWO FULL SURVEYS (NOT PARTIAL
 COPIES), SHOWING THE LOCATION OF THE PROPOSED GENERATOR
 WITH SETBACK DIMENSIONS TO ALL PROPERTY LINES.
  
 2)PROPOSED LOCATION DOES NOT MEET MINIMUM SETBACK
 REQUIREMENTS.AS PER SECTION 94-305(B)(4) OF THE
 ZLDRS: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN
 4' INTO A REQUIRED SETBACK.THE REQUIRED FRONT SETBACK
 IS 25', YIELDING A MINIMUM REQUIRED FRONT SETBACK OF
 21' TO THE PROPOSED GENERATOR.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - GEN. BOX