2007-12-13 10:04:00 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| GAS PLAN REVIEW: |
| DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. PLEASE |
| INDICATE THE FOLLOWING ON THE REQUIRED GAS ISOMETRIC. |
| PLEASE REFERENCE THE CITY OF WEST PALM BEACH GAS PERMIT |
| APPLICATION REQUIREMENTS FOR PERMIT APPLICATIONS |
| ATTACHED TO THESE COMMENTS. |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| **THE SUBMITTED GAS ISOMETRIC IS INCOMPLETE, AND DOES |
| NOT INDICATE THE CORRESPONDING LENGTHS FOR THE CUT |
| SECTIONS OF PIPE. PLEASE RESUBMIT WITH A COMPLETE RISER |
| DIAGRAM OF THE PROPOSED GAS FOR THE GENERATOR FROM |
| METER TO GENERATOR WITH THE REQUIRED INFORMATION. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| **THE INCOMPLETE GAS ISOMETRIC RISER DIAGRAM DOES NOT |
| INDICATE PIPE SIZES. |
| |
| 3. TYPE OF GAS, (LP OR NATURAL) |
| **THE SUBMITTED GAS RISER DOES NOT INDICATE THE GAS |
| TYPE. |
| |
| 4. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| **THE SUBMITTED GAS RISER DOES NOT INDICATE THE BTU |
| LOADS. |
| |
| 5. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| **PLEASE REFERENCE COMMENT ONE AND COMPLY. |
| |
| 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| **THE SUBMITTED GAS RISER DOES NOT INDICATE THIS. |
| |
| **IMPROTANT** |
| THE ABOVE INFORMATION NEEDS TO BE ON THE GAS ISOMETRIC |
| RISER DIAGRAM, PLEASE COMPLY ON THE RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |