Plan Review Notes
Plan Review Notes For Permit 07120104
Permit Number 07120104
Review Stop G
Sequence Number 1
Notes
Date Text
2007-12-13 10:04:00PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE. PLEASE
 INDICATE THE FOLLOWING ON THE REQUIRED GAS ISOMETRIC.
 PLEASE REFERENCE THE CITY OF WEST PALM BEACH GAS PERMIT
 APPLICATION REQUIREMENTS FOR PERMIT APPLICATIONS
 ATTACHED TO THESE COMMENTS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **THE SUBMITTED GAS ISOMETRIC IS INCOMPLETE, AND DOES
 NOT INDICATE THE CORRESPONDING LENGTHS FOR THE CUT
 SECTIONS OF PIPE. PLEASE RESUBMIT WITH A COMPLETE RISER
 DIAGRAM OF THE PROPOSED GAS FOR THE GENERATOR FROM
 METER TO GENERATOR WITH THE REQUIRED INFORMATION.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 **THE INCOMPLETE GAS ISOMETRIC RISER DIAGRAM DOES NOT
 INDICATE PIPE SIZES.
  
 3. TYPE OF GAS, (LP OR NATURAL)
 **THE SUBMITTED GAS RISER DOES NOT INDICATE THE GAS
 TYPE.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 **THE SUBMITTED GAS RISER DOES NOT INDICATE THE BTU
 LOADS.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **PLEASE REFERENCE COMMENT ONE AND COMPLY.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 **THE SUBMITTED GAS RISER DOES NOT INDICATE THIS.
  
 **IMPROTANT**
 THE ABOVE INFORMATION NEEDS TO BE ON THE GAS ISOMETRIC
 RISER DIAGRAM, PLEASE COMPLY ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  