2007-12-21 14:11:09RESIDENTIAL RENOVATION, BUILDING REVIEW APPROVED WITH
 PROVISO:
  
 PROVIDE THE FOLLOWING INFORMATION FOR REVIEW PRIOR TO
 FIRST INSPECTION:
  
 1- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDECLEAR AND LEGIBLE COPIES.
  
 B) REVISE INFORMATION ON TABLE 6C-1. INSULATION ON
 WALLS AND CEILING NEED TO MATCH INFORMATION ON PLANS.
 ALSO, MAKE SURE MIN. R-INSULATIONAS REQUIRED BY THIS
 TABLE IS PROVIDED.
  
 C) SPECIFY WALL AREA TO BE INSULATED ON ITEM9A-2.
  
 D) SPECIFYCEILING AREA TO BE INSULATED ON ITEM
 10A.
 NOTE: COORDINATE WITH TABLE 6C-1 FOR MIN. REQUIRED
 INSULATION.
  
 D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.