2007-12-11 14:13:11 | |
| |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING:ALL COMMENTS RELATE TO |
| SHEET E-1, UNLESS OTHERWISE NOTED. ALL CODE ARTICLES |
| REFERENCED ARE 2005 NEC UNLESS OTHERWISE NOTED. |
| |
| 1} THE RISER DIAGRAM INDICATES A 150 AMP MAIN, THE |
| DISCONNECT (NOT SHOWN) INDICATED ON THE FLOOR PLAN IS |
| 200 AMP. IF THIS IS A METER/ MAIN CHANGE THE RISER TO |
| REFLECT A METER/ MAIN. |
| |
| 2} VERIFY THE 4/0 SERVICE CONDUCTORS SHOWN ON THE RISER |
| ARE WHAT THE DESIGNER INTENDED WHEN A MINIMUM OF #1 CU |
| IS ALL THATS REQUIRED FOR A 150 AMP SERVICE PER |
| 310.15./0 CAN BE USED BUT WILL REQUIRE A REVISION TO |
| CHANGE AFTER PERMITTING. |
| |
| 3} 210.52(B) (3) KITCHEN RECEPTACLE REQUIREMENTS: |
| RECEPTACLES INSTALLED IN A KITCHEN TO SERVE COUNTERTOP |
| SURFACES SHALL BE SUPPLIED BY NOT FEWER THAN TWO |
| SMALL-APPLIANCE BRANCH CIRCUITS, EITHER OR BOTH OF |
| WHICH SHALL ALSO BE PERMITTED TO SUPPLY RECEPTACLE |
| OUTLETS IN THE SAME KITCHEN AND IN OTHER ROOMS |
| SPECIFIED IN 210.52(B) (1). ADDITIONAL SMALL-APPLIANCE |
| BRANCH CIRCUITS SHALL BE PERMITTED TO SUPPLY RECEPTACLE |
| OUTLETS IN THE KITCHEN AND OTHER ROOMS SPECIFIED IN |
| 210.52(B)(1). NO SMALL-APPLIANCE BRANCH CIRCUIT SHALL |
| SERVE MORE THAN ONE KITCHEN.BECAUSE THE COUNTERTOP |
| RECEPTACLE OUTLETS GENERALLY SUPPLY MORE OF THE |
| PORTABLE COOKING APPLIANCES THAN THE WALL RECEPTACLES |
| IN THE KITCHEN AND DINING AREAS, THE COUNTER AREAS MUST |
| BE SUPPLIED BY NO FEWER THAN TWO SMALL-APPLIANCE BRANCH |
| CIRCUITS. *THE INTENT OF THIS ARTICLE IS NOT MET WITH |
| CIRCUIT #22 AS THE ONLY CIRCUIT SERVING THE |
| COUNTERTOP. |
| |
| 4} 210.11(C) (2) LAUNDRY BRANCH CIRCUITS IN ADDITION TO |
| THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS |
| OF THIS SECTION, AT LEAST ONE ADDITIONAL 20-AMPERE |
| BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY THE LAUNDRY |
| RECEPTACLE OUTLET(S) REQUIRED BY 210.52(F). THIS |
| CIRCUIT SHALL HAVE NO OTHER OUTLETS.* CIRCUIT #13 DOES |
| NOT COMPLY, ALSO THE DINING ROOM IS REQUIRED TO BE ON A |
| SMALL APPLIANCE CIRCUIT PER 210.11(C)(1). THE LIVING |
| ROOM IS NOT. |
| |
| 5} A RECEPTACLE IS REQUIRED IN THE GARAGE PER |
| 210.52(G), GFCI PROTECTED PER 210.8(A)(2). |
| |
| 6} 210.52(E) REQUIRES A RECEPTACLE IN THE FRONT OUTSIDE |
| OF THE RESIDENCE. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| |
| |