2007-12-19 16:58:12 | RESIDENTIAL RENOVATIONS, BUILDING REVIEW FIRST |
| CHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1- NEED NOTICE OF COMMENCEMENT. SEC. 713.13 FLORIDA |
| STATUTE. |
| |
| 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| 9B-72 FORGARAGE DOOR AS SHOWN ON PLANS. |
| |
| 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 4- ENGINEER TO SPECIFY TYPE OF DOOR TO BE USED FOR |
| GARAGE DOOR LEADING TO THE INTERIOR OF THE HOUSE AS |
| REQUIRED BY SEC. R309.1 OF 2004 FLORIDA RESIDENTIAL |
| CODE. |
| |
| 5- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS. |
| PROVIDEINSTALLATION KEY PLAN AND COMPLETE |
| INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE.ALSO, |
| CLEARLY MARK ON DRAWINGS SPECIFIC MOUNTING CONDITIONS, |
| EG: WALL MOUNTED, BUILT OUT, ETC,AND SPECIFIC ANCHOR |
| TYPE AND SPACING TO BE USED. THIS WILL EXPEDITE REVIEW |
| PROCESS AND WILL SHOW COMPLIANCE WITH PROPOSED |
| INSTALLATION.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 |
| TO VERIFY COMPLIANCE WITH SEC. R301 OF 2004 FLORIDA |
| RESIDENTIAL CODE. |
| |
| 6- CLARIFY HOW R-19 INSULATION IS GOING TO BE ACHIEVED |
| ON THE EXTERIOR CONCRETE BLOCK WALL AND ON THE 2X4 |
| ADJACENT FRAME WALL?. SEE ENERGY CALCULATIONS. |
| NOTE: R-19 BATT INSULATION DOESN'T FIT IN A 2X4 WALL. |
| |
| 7- PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| ENERGY CALCULATIONS FORM. INCLUDING CORRECT NAME OF |
| BUILDER. |
| |
| 8- INFORMATION ON PLANS AND ENERGY CALCULATIONS NEED TO |
| MATCH.COORDINATEINSULATION VALUE FOR EXTERIOR AND |
| ADJACENT WALLS TO MATCH. |
| |
| 9- ENERGY CALCULATIONS ARE TAKING THE CEILING FANS |
| CREDIT. THEREFORE, CEILING FANS SHALL BE INSTALLED. |
| SPECIFY CEILINGFAN SIZES IN ALL ROOMS AS REQUIRED BY |
| TABLE 13-607.1.A.1 OF FBC 2004. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |