Plan Review Notes
Plan Review Notes For Permit 07120070
Permit Number 07120070
Review Stop E
Sequence Number 2
Notes
Date Text
2008-01-03 08:25:41 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} LOCATE THE ELECTROCAL PANEL ON THE PLAN, IT HAS BEEN
 REMOVED.
  
 2} THE NOTE FOR THE FEEDER (RISER DIAGRAM) INDICATES
 "MAIN LUG", THE PANEL ON THE RISER INDICATES "MAIN
 BREAKER". CORRELATE SO THE DESIGNERS INTENTION IS
 CLEAR,106.1.1 FBC AS AMENDED.
  
 3} THERE ARE DISPOSAL AND DISHWASHER BREAKERS IN THE
 PANEL WITH NO LOADS SHOWN FOR CALCULATIONS. ALL LOADS
 MUST BE LISTED AT NAMEPLATE RATING . 220.83 NEC.ALSO
 NOTE: THE BATH GFI CIRCUIT IS PART OT THE GENERAL
 LIGHTING LOAD AND DOES NOT NEED TO BE RECALAULATED,
 (SEE 1500 VA).
  
 4} THE A/C LOAD ON THE PANEL SCHEDULE NOW LISTED AT
 10000VA, AND THE MECHANICAL PLAN AT 7500VA, CORRELATE
 SAME.
  
 5} INDICATE A DISCONNECTING MEANS FOR THE WATER HEATER.
 SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, AND
 422.31(B) FOR HARDWIRE REQUIREMENTS.
  
 6} SHOW THE LOCATION OF THE A/C EQUIPMENT (CONDENER) ON
 THE PLAN. ALSO SHOW COMPLIANCE WITH THE REQUIRED
 DISCONNECT PER 440.14,RECEPTACLE PER 210.63.
  
 7} THE "A/C" PLAN AND THE FLOOR PLAN INDICATE DIFFERENT
 OPENING LOCATIONS FOR THE AIR HANDLER, CORRELATE SAME.
  
 8} A RECEPTACLE IS REQUIRED FOR SPACING REQUIREMENT
 210.52(A)(2), IN THE KITCHEN ON THE A/C WALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718