2007-12-19 11:40:56PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PERMIT APPLICATION STATES RENOVATION AND REPAIR
 PLUMBING, HOWEVER THE SUBMITTED PLANS ON SHEET 1 (BOTH
 SETS 1017, 1017 1/2 AND 1019, 1019 1/2) ARE INDICATING
 THE FOLLOWING "NOTE, PLUMBING EXISTING" WITH A
 ISOMETRIC SANITARY RISER DIAGRAM THAT DOES NOT REFLECT
 THE FLOOR PLAN OR IS CODE COMPLIANT. PLEASE REFERENCE
 THE CORRECTED SANITARY ISOMETRIC RISER DIAGRAM THAT
 REFLECTS THE FLOOR PLAN AND IS CODE COMPLIANT. CLEARLY
 INDICATE ON THE RESUBMITTED PLANS WHAT PLUMBING WORK IS
 GOING TO BE DONE. PER *106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS AND *106.1.2 ADDITIONAL DATA.
  
 2. SHEET 1, ISOMETRIC SANITARY RISER DIAGRAM:PER
 FBC-2004 CHAPTER 1, SECTION 106.3.5.4 RESIDENTIAL (ONE
 AND TWO-FAMILY)(9) PLUMBING: PLEASE SUBMIT A PLUMBING
 SANITARY ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE,
 VENTS, TRAPS AND SIZES WITH CLEANOUT LOCATIONS.**THE
 SUBMITEED RISER DIAGRAM ALSO DOES NOT COMPLY WITH THE
 FOLLOWING AS WELL AS WHAT WAS STATED IN COMMENT 1.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE 3".
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED 4'
 A.F.F.
  
 3. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING.
 PLEASE DO THIS PRIOR TO RESUBMITTING.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER