Plan Review Notes
Plan Review Notes For Permit 07120070
Permit Number 07120070
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-14 14:29:33 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THIS REVIEW IS FOR 1017 21 STREET, SEPERATE PLANS
 AND APPLICATIONS ARE REQUIRED FOR EACH OF THE SEPERATE
 ADDRESSES INDICATING THE SCOPE OF WORK PROPOSED FOR
 EACH BUILDING.106.1.3 FBC AS AMENDED.
  
 2} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70, 225.32. LOCATE ON THE FLOOR PLAN AND ON THE
 RISER. SHOW ALL CONDUCTORS ON THE RISER.
  
 3} } PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR
 THE FEEDER TO THE PANEL.
  
 4} THE 6" GROUND ROD ON THE RISER DIAGRAM DOES NOT
 COMPLY WITH 250.53(G) "ROD AND PIPE ELECTRODES THE
 ELECTRODE SHALL BE INSTALLED SUCH THAT AT LEAST 2.44 M
 (8 FT) OF LENGTH IS IN CONTACT WITH THE SOIL.---"
  
 5}INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE
 PLAN IS NEW OR EXISTING SINCE THE SCOPE IS NOT CLEAR ON
 THE APPLICATION.
  
 6} THE CIRCUIT MARKED A/C LISTED AT 8000W " AND 10000W
 DEMAND. CLARIFYPROVIDE A PANEL SCHEDULE PER 408.4.
 INCLUDE OCP AND CONDUCTOR SIZES. PLEASE SEE NEW VERBAGE
 FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 7} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED.
  
 8} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), NONE SHOWN ON THE PANEL SCHEDULE.
  
 9} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63.
  
 10} EGRESS LIGHTING IS REQUIRED PER 210.70(A)(2)(B).SEE
 REAR EXIT.
  
 11} 210.52 (E) OUTDOOR OUTLETS FOR A ONE-FAMILY
 DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS
 AT GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE AT GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/
 2 FT) ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND
 BACK OF THE DWELLING.
  
 12} PROVIDE AN ELECTRICAL LEGEND. 106.1.3.FBC AS
 AMENDED.
  
 13} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE ON PLANS
 AS REQUIRED.NOTE: NFPA-72 REQUIRES ALARMS OR DETECTORS
 WITHIN 20 FEET OF COOKING APPLIANCES BE SILENCING OR
 PHOTOELECTRIC. SEE 11.8.3.5(4)..
  
 14} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 15} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 16} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN
 MUST PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3.
 FBC. IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND
 471 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
2007-12-12 10:46:19 
  
 TO ZONING ./WRT