| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} THIS REVIEW IS FOR 1017 21 STREET, SEPERATE PLANS |
| AND APPLICATIONS ARE REQUIRED FOR EACH OF THE SEPERATE |
| ADDRESSES INDICATING THE SCOPE OF WORK PROPOSED FOR |
| EACH BUILDING.106.1.3 FBC AS AMENDED. |
| |
| 2} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED |
| PER 230.70, 225.32. LOCATE ON THE FLOOR PLAN AND ON THE |
| RISER. SHOW ALL CONDUCTORS ON THE RISER. |
| |
| 3} } PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR |
| THE FEEDER TO THE PANEL. |
| |
| 4} THE 6" GROUND ROD ON THE RISER DIAGRAM DOES NOT |
| COMPLY WITH 250.53(G) "ROD AND PIPE ELECTRODES THE |
| ELECTRODE SHALL BE INSTALLED SUCH THAT AT LEAST 2.44 M |
| (8 FT) OF LENGTH IS IN CONTACT WITH THE SOIL.---" |
| |
| 5}INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE |
| PLAN IS NEW OR EXISTING SINCE THE SCOPE IS NOT CLEAR ON |
| THE APPLICATION. |
| |
| 6} THE CIRCUIT MARKED A/C LISTED AT 8000W " AND 10000W |
| DEMAND. CLARIFYPROVIDE A PANEL SCHEDULE PER 408.4. |
| INCLUDE OCP AND CONDUCTOR SIZES. PLEASE SEE NEW VERBAGE |
| FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE |
| SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| DISTINGUISHED FROM ALL OTHERS." |
| |
| 7} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, |
| STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. |
| |
| 8} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| PER 210.11(C) (3), NONE SHOWN ON THE PANEL SCHEDULE. |
| |
| 9} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. |
| ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| 440.14,RECEPTACLE PER 210.63. |
| |
| 10} EGRESS LIGHTING IS REQUIRED PER 210.70(A)(2)(B).SEE |
| REAR EXIT. |
| |
| 11} 210.52 (E) OUTDOOR OUTLETS FOR A ONE-FAMILY |
| DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS |
| AT GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET |
| ACCESSIBLE AT GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ |
| 2 FT) ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND |
| BACK OF THE DWELLING. |
| |
| 12} PROVIDE AN ELECTRICAL LEGEND. 106.1.3.FBC AS |
| AMENDED. |
| |
| 13} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN |
| INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS |
| SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE ON PLANS |
| AS REQUIRED.NOTE: NFPA-72 REQUIRES ALARMS OR DETECTORS |
| WITHIN 20 FEET OF COOKING APPLIANCES BE SILENCING OR |
| PHOTOELECTRIC. SEE 11.8.3.5(4).. |
| |
| 14} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. |
| |
| 15} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| DESIGNED. |
| |
| 16} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN |
| MUST PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. |
| FBC. IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND |
| 471 FS, RESPECTIVELY. |
| THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL |
| IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, |
| APPLY. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |