2007-12-20 14:37:09RESIDENTIAL RENOVATION, BUILDING REVIEW FIRST
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-A) THERE ARE FOUR INDEPENDENT BUILDINGS ON THIS
 PROPERTY. NEED TO PROVIDE A PERMIT APPLICATION FOR EACH
 DWELLING UNIT. SAME SET OF PLANS MAY BE USED FOR ALL
 FOUR UNITS, BUT SEPARATE PERMIT APPLICATION IS REQUIRED
 FOR EACH BUILDING. (2 SETS OF PLANS REQUIRED FOR EACH
 BUILDING)
  
 B) VALUATION DECLARED ON THE PERMIT APPLICATION IS
 TOO LOW. SECTION 108.3 CITY AMENDMENTS TO FBC 2004.
 VALUATION TO BE UPDATED TO INCLUDEALL SCOPE OF WORK
 TO BE PERFORMEDON EACH BUILDING SEPARATELY AND
 SPECIFIED ON EACH PERMIT APPLICATION.
  
 2- A) INFORMATION ON CONSTRUCTION DOCUMENTS IS NOT
 CLEAR.SEC. 106.1.1 CITY AMENDMENTS TO FBC 2004.IT'S
 NOT CLEAR WHAT IS GOING TO BE REPLACED OR NOT.WHAT'S
 EXISTING AND WHAT'S NOT. PLANS NEED TO BE CLEAR TO
 DETERMINE COMPLETE SCOPE OF WORK AND TO VERIFY
 COMPLIANCE WITH AREAS TO BE RENOVATED. INDICATE ON
 PLANS SPECIFIC AREAS OF WORK AND SPECIFIC WORK TO BE
 PERFORMED. THIS WILL ALSO HELP TO DETERMINE TOTAL COST
 AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 B)IS 4"X4" POST AT ENTRY PORCH GOING TO BE
 REPLACED?PROVIDE COMPLETE INFORMATION, INCLUDING
 FASTENER ON TOP AND BOTTOM AND PROVIDE THE CALCULATED
 UPLIFT LOADS TO VERIFY COMPLIANCE WITH SEC. R301 OF
 2004.
  
 C) SHEET 3 OF 3: AREWINDOW OPENINGS AND EXTERIOR
 WALLS GOING TO BE RE-FRAMED OR THESE ARE EXISTING. IS
 NOT CLEAR WHAT'S NEW AND WHAT'S NOT.IF REFRAMING
 WINDOW OPENINGS , THEN SPECIFY NUMBER OF STUDS REQUIRED
 AT THE ENDS OF EACH OPENING. SPECIFY ALL FASTENERS TO
 VERIFY COMPLIANCE WITH SEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE.THIS APPLIES TO TYPICAL WALL SECTION
 ALSO. SPECIFY ALL FASTENERS SHOWING HOW LOADS GET
 TRANSFERRED FROM ROOF TO FOOTING.
  
 D) PROVIDE NAME AND SIGNATURE OF DESIGNER OF RECORD
 AS REQUIRED BY SEC. 106.1.3 CITY AMENDMENTS TO FBC
 2004.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 NOTE: MAKE SURE ALL UNITS ARE INCLUDED.
  
 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE WHERE CONNECTOR IS TO
 EXPEDITE REVIEW PROCESS AND SAVE PAPER.
 NOTE: ONLY 2 SETS OF PRODUCT APPROVALS ARE REQUIRED,
 NOT 4.
  
 5- PERSON RESPONSIBLE FOR THE DESIGN TO REVIEW AND
 APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL
 PRODUCT APPROVAL AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 6- ENERGY CALCULATIONS:
 A) PROVIDE ENERGY CALCULATIONS FOR EACH UNIT AS
 REQUIRED BY SEC. 13-101.2.5.1 FBC 2004.
  
 B) REVISE ITEM #2. THIS ARE SINGLE FAMILY UNITS
 DETACHED, NOT MULTIPLE FAMILY.
  
 C) SPECIFY FLOOR AREA ON ITEM # 8(B). IT WAS LEFT
 BLANK.
  
 D) PREPARER TO SIGN AND DATE BOTTOM OF FORM.
  
 E) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 F) REVISE INFORMATION ON TABLE 6C-1.NEED TO
 PROVIDE R-30 INSULATION UNDER ATTIC AREA, NOT R-19
 UNDER SINGLE ASSEMBLY BECAUSE THIS IS NOT SINGLE
 ASSEMBLY. REVISE AS REQUIRED.
  
 G) COMPLETE INFORMATION ON TABLE 6C-2.
  
 7- STORM SHUTTERS:
 A) REVISE INSTALLATION SCHEDULE. REVISE COLUMN FOUR.
 INFORMATION REQUESTED IS SHUTTER MOUNTING CONDITION,
 EG; WALL MOUNTED, BUILT OUT, ETC. SEE PAGES2AND 3
 ON STORM SHUTTER DRAWINGS SUBMITTED.
  
 B) REVISE SHUTTER SPAN. SEE SHEET 1 OF 3 OF STORM
 SHUTTERS TO SEE HOW TO MEASURE THE PANEL SPAN.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER.
 (561)805-6712
  