2008-02-21 17:01:29 | BUILDING REVIEW PROVISO: | | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | 9B-72 FOR ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED | | ON PLANS AND DETAILS. | | 2- ROOF PITCH OF 3:12REQUIRES 2 LAYERS OF | | UNDERLAYMENT AS REQUIRED BY SEC. R905.3.3.1 2004 | | FLORIDA RESIDENTIAL CODE.REVISE SPECIFICATIONS ON | | DRAWINGS AS REQUIRED. | | 3- ROOF PLAN SHOWS ONLY ONE ROOF DRAIN AND SCUPPER FOR | | ENTIRE ROOF. CLARIFY IF THEY ARETHE ONLY DRAINS FOR | | THIS ROOF. AND PROVIDE DRAINAGE CALCULATIONS FOR | | PLUMBING PLAN REVIEWER PRIOR TO ROOF DRAINS | | INSTALLATION TO AVOID DELAYS OR CONFLICTS. | | 4- REVISE WALL SECTIONS IN SHEET A-4PROVIDING | | COMPLETE SPECIFICATIONS FOR ANCHORS/FASTENERSSHOWING | | TRANSITION OF LOADS FROM ROOF TO FOOTINGAS REQUIRED | | BY SEC. R601.2 OF 2004 FLORIDA RESIDENTIAL CODE. | | 5- REVISE ROOF SHEATHING NAIL SPACING FOR ROOF ZONE 3. | | SEE SEC. R803.2.3.1 2004 FLORIDA RESIDENTIAL CODE. |
|