Plan Review Notes
Plan Review Notes For Permit 07120067
Permit Number 07120067
Review Stop B
Sequence Number 2
Notes
Date Text
2008-02-21 17:01:29BUILDING REVIEW PROVISO:
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND DETAILS.
 2- ROOF PITCH OF 3:12REQUIRES 2 LAYERS OF
 UNDERLAYMENT AS REQUIRED BY SEC. R905.3.3.1 2004
 FLORIDA RESIDENTIAL CODE.REVISE SPECIFICATIONS ON
 DRAWINGS AS REQUIRED.
 3- ROOF PLAN SHOWS ONLY ONE ROOF DRAIN AND SCUPPER FOR
 ENTIRE ROOF. CLARIFY IF THEY ARETHE ONLY DRAINS FOR
 THIS ROOF. AND PROVIDE DRAINAGE CALCULATIONS FOR
 PLUMBING PLAN REVIEWER PRIOR TO ROOF DRAINS
 INSTALLATION TO AVOID DELAYS OR CONFLICTS.
 4- REVISE WALL SECTIONS IN SHEET A-4PROVIDING
 COMPLETE SPECIFICATIONS FOR ANCHORS/FASTENERSSHOWING
 TRANSITION OF LOADS FROM ROOF TO FOOTINGAS REQUIRED
 BY SEC. R601.2 OF 2004 FLORIDA RESIDENTIAL CODE.
 5- REVISE ROOF SHEATHING NAIL SPACING FOR ROOF ZONE 3.
 SEE SEC. R803.2.3.1 2004 FLORIDA RESIDENTIAL CODE.