Plan Review Notes
Plan Review Notes For Permit 07120067
Permit Number 07120067
Review Stop P
Sequence Number 1
Notes
Date Text
2007-12-13 09:13:15PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-1 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN (KITCHEN SINK IS A DOUBLE BOWL
 NOT A SINGLE BOWL) AND SUBMIT MANUFACTURER'S
 SPECIFICATION SHEET OF THE INDICATED FITIING FOR THE
 WATER CLOSET, TUB, AND VENT (REFERENCE RED LINE
 CORRECTIONS OF THIS AREA). PER *106.1.1, INFORMATION ON
 CONSTRUCTION DOCUMENTS AND *106.1.2, ADDITIONAL DATA.
  
 2. SHEET A-1 SANITARY ISOMETRIC RISER DIAGRAM: PER
 FBC-2004 CHAPTER 1, SECTION *106.3.5.4 RESIDENTIAL (ONE
 AND TWO-FAMILY) (9) PLUMBING, PLEASE SUBMIT A PLUMBING
 SANITARY ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE,
 VENTS, TRAPS AND SIZES WITH CLEANOUT LOCATIONS. **THE
 SUBMITTED DRAWING DOES NOT HAVE ALL WASTE AND TRAPS
 SIZED.
  
 3. SHEET A-1 SANITARY ISOMETRIC RISER DIAGRAM: THE NEW
 WASHER AND DOUBLE KITCHEN SINK MUST DRAIN DOWNSTREAM OF
 THE WET VENTED BATHROOM. PER *909.1 WET VENT
 PERMITTED.
  
 4. SHEET A-1 SANITARYISOMETRIC RISER DIAGRAM: THE
 WASHER IS SIZED WRONG, PLEASE CORRECT PER THE
 FOLLOWING.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM).
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE 3".
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED 4'
 A.F.F.
  
 5. SHEET A-1 SANITARY ISOMETRIC RISER DIAGRAM:PER
 *708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 TWO-WAY CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
  
 6. SHEET A-1 PLUMBING NOTE #1, SLOPE OF THE HORIZONTAL
 DRAINAGE PIPE SHALL BE PER THE FOLLOWING.
 704.1 SLOPE OF HORIZONTAL DRAINAGE PIPING. HORIZONTAL
 DRAINAGE PIPING SHALL BE INSTALLED IN UNIFORM ALIGNMENT
 AT UNIFORM SLOPES. THE MINIMUM SLOPE OF A HORIZONTAL
 DRAINAGE PIPE SHALL BE IN ACCORDANCE WITH TABLE 704.1
 .
 TABLE 704.1
 SLOPE OF HORIZONTAL DRAINAGE PIPE
  
 SIZE--MINIMUM SLOPE
 (INCHES)--(INCH PER FOOT)
 2-1/2 OR LESS--1/4
 3 TO 6--1/8
 8 OR LARGER--1/16
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  