2007-12-13 09:13:15 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SHEET A-1 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN (KITCHEN SINK IS A DOUBLE BOWL |
| NOT A SINGLE BOWL) AND SUBMIT MANUFACTURER'S |
| SPECIFICATION SHEET OF THE INDICATED FITIING FOR THE |
| WATER CLOSET, TUB, AND VENT (REFERENCE RED LINE |
| CORRECTIONS OF THIS AREA). PER *106.1.1, INFORMATION ON |
| CONSTRUCTION DOCUMENTS AND *106.1.2, ADDITIONAL DATA. |
| |
| 2. SHEET A-1 SANITARY ISOMETRIC RISER DIAGRAM: PER |
| FBC-2004 CHAPTER 1, SECTION *106.3.5.4 RESIDENTIAL (ONE |
| AND TWO-FAMILY) (9) PLUMBING, PLEASE SUBMIT A PLUMBING |
| SANITARY ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE, |
| VENTS, TRAPS AND SIZES WITH CLEANOUT LOCATIONS. **THE |
| SUBMITTED DRAWING DOES NOT HAVE ALL WASTE AND TRAPS |
| SIZED. |
| |
| 3. SHEET A-1 SANITARY ISOMETRIC RISER DIAGRAM: THE NEW |
| WASHER AND DOUBLE KITCHEN SINK MUST DRAIN DOWNSTREAM OF |
| THE WET VENTED BATHROOM. PER *909.1 WET VENT |
| PERMITTED. |
| |
| 4. SHEET A-1 SANITARYISOMETRIC RISER DIAGRAM: THE |
| WASHER IS SIZED WRONG, PLEASE CORRECT PER THE |
| FOLLOWING. |
| (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| WASHER SHALL BE A MINIMUM OF 2 INCHES |
| (51MM) IN DIAMETER. THE AUTOMATIC |
| CLOTHES WASHER FIXTURE DRAIN SHALL |
| CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| STACK A MINIMUM OF 3 INCHES (76MM) IN |
| DIAMETER. |
| |
| (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| TRAPPED. STANDPIPES SHALL |
| EXTEND A MINIMUM OF 18 INCHES (457MM) |
| AND A MAXIMUM OF 42 INCHES (1066MM) |
| ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| PROVIDED TO ALL STANDPIPES AND DRAINS |
| FOR RODDING. |
| |
| (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| BE THE SAME NOMINAL SIZE AS THE PIPE |
| THEY SERVE UP TO 4 INCHES (102MM). |
| **CLEANOUT FOR THE WASHING MACHINE SHALL BE 3". |
| |
| (D) 708.9 ACCESS. ACCESS SHALL BE |
| PROVIDED TO ALL CLEANOUTS. |
| **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED 4' |
| A.F.F. |
| |
| 5. SHEET A-1 SANITARY ISOMETRIC RISER DIAGRAM:PER |
| *708.3.5 BUILDING DRAIN AND BUILDING |
| SEWER JUNCTION. THERE SHALL BE A |
| TWO-WAY CLEANOUT NEAR THE JUNCTION OF THE |
| BUILDING DRAIN AND THE BUILDING SEWER. |
| |
| 6. SHEET A-1 PLUMBING NOTE #1, SLOPE OF THE HORIZONTAL |
| DRAINAGE PIPE SHALL BE PER THE FOLLOWING. |
| 704.1 SLOPE OF HORIZONTAL DRAINAGE PIPING. HORIZONTAL |
| DRAINAGE PIPING SHALL BE INSTALLED IN UNIFORM ALIGNMENT |
| AT UNIFORM SLOPES. THE MINIMUM SLOPE OF A HORIZONTAL |
| DRAINAGE PIPE SHALL BE IN ACCORDANCE WITH TABLE 704.1 |
| . |
| TABLE 704.1 |
| SLOPE OF HORIZONTAL DRAINAGE PIPE |
| |
| SIZE--MINIMUM SLOPE |
| (INCHES)--(INCH PER FOOT) |
| 2-1/2 OR LESS--1/4 |
| 3 TO 6--1/8 |
| 8 OR LARGER--1/16 |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| EXAMINER FOR REFERENCE FOR THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |