Date |
Text |
2007-12-19 10:48:39 | RESIDENTIAL ADDITION, BUILDING REVIEW CHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT DESCRIBING |
| SCOPE OF WORK TO BE PERFORMED AS REQUIRED BY SEC. |
| 713.13 FLORIDA STATUTE.THERE IS AN EXISTING NOTICE OF |
| COMMENCEMENT BUT IT WAS FOR INTERIOR DEMOLITION ONLY. |
| |
| 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| 13-101.2.2 AND 13-101.2.3 OF FBC 2004. |
| PLEASE, MAKE SUREREVISED FORM IS USED,CALCULATIONS |
| ARE FILLED COMPLETELY AND OWNER/AGENT SIGNS AND DATE |
| FORMS AS REQUIRED TOAVOID UNNECESSARY DELAYS. |
| |
| 3- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD |
| (561)233-5115) TO VERIFY IF IMPACT FEES ARE DUE. BRING |
| BACK STAMPED PLANS AND COPY OF PAID RECEIPTIF FEES |
| ARE DUE. |
| |
| 4- PROPOSED ADDITIONEAST SIDE WALL NEEDSTO COMPLY |
| WITH SEC. R302.1 AND SEC. R302.2 OF 2004 FLORIDA |
| RESIDENTIAL CODE.WALL NEEDS TO BE FIRE RATED AND |
| OPENINGS ARE NOT ALLOWED.CLEARLY SHOW ON SITE PLAN |
| DISTANCE OF EXISTING ADJACENT STRUCTURES TO VERIFY |
| COMPLIANCE WITH THISCODE SECTION. |
| |
| 5- IF PLANS/ELEVATIONS ARE CHANGED, THEN PLEASE BRING |
| THEM TO THE HISTORIC DEPARTMENT ON THE FIFTH FLOOR FOR |
| APPROVAL RE-STAMP PRIOR TO SUBMITTAL TO THIS OFFICE TO |
| EXPEDITE REVIEW PROCESS. |
| |
| 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| 9B-72 FOR: |
| A) EXTERIOR SWING DOORS. FLORIDA PRODUCT APPROVAL |
| FL1893 SUBMITTED ISFOR CODE VERSION 2001.NEED TO |
| PROVIDECURRENT PRODUCT APPROVAL FOR CODE VERSION 2004 |
| AND MAKE SURE NOA IS NOT EXPIRED. |
| |
| B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| PLANS AND DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL |
| COVER PAGE AND PAGE SHOWING CONNECTOR ONLY TO SAVE |
| PAPER AND EXPEDITE REVIEW PROCESS. NO NEED TO SUBMIT |
| COMPLETE REPORT SHOWING ALL STRAPS. |
| |
| 7- PROFESSIONAL DESIGNEROF RECORD NEEDS TO PROVIDE |
| ORIGINAL SIGNATURE (AND PROVIDE DATE)ON THE PRODUCT |
| APPROVALSREVIEW STAMP.RUBBER SIGNATURE IS NOT |
| ALLOWED BY CHAPTER 481 OF FLORIDA STATUTE. |
| |
| 8- FLAT ROOF PRODUCT APPROVAL:SELECTED ASSEMBLY ON |
| PAGE 18 OF 21 OF NOA 03-0501.05 SUBMITTED IS MISSING |
| THE ENHANCED NAILING CALCULATIONS FOR PERIMETER AND |
| CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7. |
| THERE IS A NOTE SAYING "SEE ENHANCED NAILING", BUT THIS |
| INFORMATION WAS NOT PROVIDED. PLEASE, PROVIDE THIS |
| INFORMATION TO VERIFY COMPLIANCE WITH UPLIFT PRESSURES |
| AS REQUIRED BY SEC. R301 OF 2004 FLORIDA RESIDENTIAL |
| CODE. |
| |
| 9- OWES $0.74 FOR NEW ADDITIONS RADON FEES. |
| |
| 10- UPDATE GENERAL SPECIFICATIONS NOTE #1 ON SHEET A-1. |
| NEED TO REFERENCE2007 REVISIONS, NOT 2006. REVISE AS |
| REQUIRED. |
| |
| 11-SPECIFY ROOF PITCH TO VERIFY COMPLIANCE WITH SEC. |
| R905.3.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| 12-ROOF DRAINAGE ON FLAT ROOF NEEDS TO COMPLY WITH |
| SEC. R903.4.1 OF 2004 FLORIDA RESIDENTIALCODE. |
| PROVIDE COMPLETE SPECIFICATIONS AND DETAILS SHOWING |
| COMPLIANCE. |
| |
| 13- SHEET A-4: |
| A) SECTION AT UTILITY ROOM. CLARIFY WHY USING (2)2X4 |
| HEADERS LAID FLAT ABOVE THE DOORINSTEAD OF BEING |
| VERTICAL .THIS IS NOT AN STANDARD CONSTRUCTION |
| TECHNIQUE.SPECIFY WHICH TABLE WAS USED TO USE HEADER |
| IN THIS WAY. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| B) PROVIDE COMPLETE SPECIFICATIONS SHOWINGHOW ARE |
| THE WALLS CONNECTED TO THE FOOTING TO TRANSMIT ALL THE |
| LOADS TO THE FOOTING.SECTIONS SHOWN ON THIS DRAWINGS |
| ARE MISSING THIS INFORMATION.ALSO, MISSINGCOMPLETE |
| SPECIFICATION FOR NEW PARAPET WALL CONNECTIONS SEC. |
| R601.2 OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| C) REVISE TYPE OF NAIL TO BE USED ON ROOF SHEATHING. |
| NEED TO SPECIFY MIN.8D RING SHANK NAILS AS REQUIRED |
| BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |