Plan Review Notes
Plan Review Notes For Permit 07120067
Permit Number 07120067
Review Stop B
Sequence Number 1
Notes
Date Text
2007-12-19 10:48:39RESIDENTIAL ADDITION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT DESCRIBING
 SCOPE OF WORK TO BE PERFORMED AS REQUIRED BY SEC.
 713.13 FLORIDA STATUTE.THERE IS AN EXISTING NOTICE OF
 COMMENCEMENT BUT IT WAS FOR INTERIOR DEMOLITION ONLY.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-101.2.2 AND 13-101.2.3 OF FBC 2004.
 PLEASE, MAKE SUREREVISED FORM IS USED,CALCULATIONS
 ARE FILLED COMPLETELY AND OWNER/AGENT SIGNS AND DATE
 FORMS AS REQUIRED TOAVOID UNNECESSARY DELAYS.
  
 3- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5115) TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPTIF FEES
 ARE DUE.
  
 4- PROPOSED ADDITIONEAST SIDE WALL NEEDSTO COMPLY
 WITH SEC. R302.1 AND SEC. R302.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.WALL NEEDS TO BE FIRE RATED AND
 OPENINGS ARE NOT ALLOWED.CLEARLY SHOW ON SITE PLAN
 DISTANCE OF EXISTING ADJACENT STRUCTURES TO VERIFY
 COMPLIANCE WITH THISCODE SECTION.
  
 5- IF PLANS/ELEVATIONS ARE CHANGED, THEN PLEASE BRING
 THEM TO THE HISTORIC DEPARTMENT ON THE FIFTH FLOOR FOR
 APPROVAL RE-STAMP PRIOR TO SUBMITTAL TO THIS OFFICE TO
 EXPEDITE REVIEW PROCESS.
  
 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) EXTERIOR SWING DOORS. FLORIDA PRODUCT APPROVAL
 FL1893 SUBMITTED ISFOR CODE VERSION 2001.NEED TO
 PROVIDECURRENT PRODUCT APPROVAL FOR CODE VERSION 2004
 AND MAKE SURE NOA IS NOT EXPIRED.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING CONNECTOR ONLY TO SAVE
 PAPER AND EXPEDITE REVIEW PROCESS. NO NEED TO SUBMIT
 COMPLETE REPORT SHOWING ALL STRAPS.
  
 7- PROFESSIONAL DESIGNEROF RECORD NEEDS TO PROVIDE
 ORIGINAL SIGNATURE (AND PROVIDE DATE)ON THE PRODUCT
 APPROVALSREVIEW STAMP.RUBBER SIGNATURE IS NOT
 ALLOWED BY CHAPTER 481 OF FLORIDA STATUTE.
  
 8- FLAT ROOF PRODUCT APPROVAL:SELECTED ASSEMBLY ON
 PAGE 18 OF 21 OF NOA 03-0501.05 SUBMITTED IS MISSING
 THE ENHANCED NAILING CALCULATIONS FOR PERIMETER AND
 CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7.
 THERE IS A NOTE SAYING "SEE ENHANCED NAILING", BUT THIS
 INFORMATION WAS NOT PROVIDED. PLEASE, PROVIDE THIS
 INFORMATION TO VERIFY COMPLIANCE WITH UPLIFT PRESSURES
 AS REQUIRED BY SEC. R301 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 9- OWES $0.74 FOR NEW ADDITIONS RADON FEES.
  
 10- UPDATE GENERAL SPECIFICATIONS NOTE #1 ON SHEET A-1.
 NEED TO REFERENCE2007 REVISIONS, NOT 2006. REVISE AS
 REQUIRED.
  
 11-SPECIFY ROOF PITCH TO VERIFY COMPLIANCE WITH SEC.
 R905.3.3.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 12-ROOF DRAINAGE ON FLAT ROOF NEEDS TO COMPLY WITH
 SEC. R903.4.1 OF 2004 FLORIDA RESIDENTIALCODE.
 PROVIDE COMPLETE SPECIFICATIONS AND DETAILS SHOWING
 COMPLIANCE.
  
 13- SHEET A-4:
 A) SECTION AT UTILITY ROOM. CLARIFY WHY USING (2)2X4
 HEADERS LAID FLAT ABOVE THE DOORINSTEAD OF BEING
 VERTICAL .THIS IS NOT AN STANDARD CONSTRUCTION
 TECHNIQUE.SPECIFY WHICH TABLE WAS USED TO USE HEADER
 IN THIS WAY. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 B) PROVIDE COMPLETE SPECIFICATIONS SHOWINGHOW ARE
 THE WALLS CONNECTED TO THE FOOTING TO TRANSMIT ALL THE
 LOADS TO THE FOOTING.SECTIONS SHOWN ON THIS DRAWINGS
 ARE MISSING THIS INFORMATION.ALSO, MISSINGCOMPLETE
 SPECIFICATION FOR NEW PARAPET WALL CONNECTIONS SEC.
 R601.2 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 C) REVISE TYPE OF NAIL TO BE USED ON ROOF SHEATHING.
 NEED TO SPECIFY MIN.8D RING SHANK NAILS AS REQUIRED
 BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712