Plan Review Notes
Plan Review Notes For Permit 07120063
Permit Number 07120063
Review Stop B
Sequence Number 1
Notes
Date Text
2007-12-11 08:57:11****CORRECTIONS****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE FBC*106.3.5, MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.NO PLANS WERE SUBMITTED.PROVIDE A FLOOR
 PLAN SHOWING LOCATION AND SCOPE OF WORK FOR ALL WORK
 REQUIRING A PERMIT (INSULATION, DRYWALL, STRUCTURAL
 REPAIR, DOORS, WINDOWS, SHUTTERS, CEILINGS, DEMOLITION
 OF PATIO, PATIO TRUSS REPAIR, ETC.), SITE PLAN.WORK
 WHICH IS NOT REQUIRED TO BE PERMITTED DOES NOT NEED TO
 BE INCLUDED IN THE PLANS (SUCH AS PAINT OF EXISTING
 ELEMENTS, BASEBOARD, ETC.).
  
 2.PROVIDE A STRUCTURAL DETAIL FOR THE FRONT DOOR
 SHELTER.THIS SHOULD INCLUDE ELEVATIONS, A SECTION,
 AND BE SHOWN ON THE FLOOR PLAN AND SITE PLAN.ZONING
 APPROVAL REQUIRED.
  
 3.PROVIDE A WALL SECTION SHOWING STRAPPING
 INFORMATION.THE FLOOR PLAN IS TO SHOW LOCATION OF
 STRAPPING.PROVIDE PRODUCT APPROVAL FOR THE
 CONNECTORS.
  
 4.FOR THE SHUTTERS, COMPLETE THE ATTACHED
 INSTALLATION SCHEDULE.PROVIDE A KEY PLAN SHOWING
 SHUTTER LOCATIONS WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE.
  
 5.DECLARE GOVERNING CODE INCLUDING 2007 AMENDMENTS
 AND WIND DESIGN CRITERIA FBC1603.1.4.