Plan Review Notes For Permit 07120041 |
Permit Number |
07120041 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-12-11 13:45:05 | ***DENIED*** | | | | 1) PERMIT APPLICATION INDICATES INSTALLATION OF (1) | | FLOW SWITCH AND (1) TAMPER SWITCH. THE DRAWINGS | | ILLUSTRATE (2) TAMPER SWITCHES. PLEASE CORRELATE | | INFORMATION. | | | | 2) PLEASE CLARIFY IF THE CONTROL PANEL IS EXISTING. | | MANUFACTURER SPEC SHEETS SHOULD INCLUDE THE EQUIPMENT | | THAT WILL BE INSTALLED. | | | | 3) PLEASE INDICATE THE TOTAL OCCUPANCY LOAD FOR THE | | BUILDING. | | | | 4) NEW SYSTEMS THAT SUPERVISE AN AUTOMATIC FIRE | | SPRINKLER SYSTEM ARE REQUIRED TO BE UL CERTIFIED FOR | | CENTRAL STATION SERVICE. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|