Date Text
2007-12-10 16:12:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE PERMIT APPLICATION STATES THE 5 TON UNITS ARE
 10.2 SEER. SEE 2004 FBC 13-407.1.ABC.3.2.1 THE MINIMUM
 SEER IS 13, PLEASE CORRECT.
  
 2) MODEL NUMBERS FOR EQUIPMENT COULD NOT BE FOUND ON
 THE ARI WEB SITE, PLEASE SUBMIT THE ARI CERTIFICATE,
 SEE 2004 FBC 13-407.1.ABC.3.1.1.
  
 3) THE ENGINEERING FOR THE WALL STANDS NEED TO BE
 SIGNED AND SEALED BY THE ENGINEER NOT COPIES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]