2008-02-04 09:23:14 | NOTE ADDED: |
| NEEDS ADDRESSING CLARIFICATION, PLANS SHOWS #205 YET |
| THE APPLIED LOCATION ON PERMIT APPLICATION IS #200 AND |
| 205 |
2008-02-04 09:20:38 | ** DENIED 2ND REVIEW ** |
| |
| ** PLEASE KNOW THIS IS THE FIRST REVIEW WITH METHOD *C* |
| SUBMITTED. |
| |
| 1) NOTE: PLEASE COORDINATE METHOD *C* WITH PLANS. FOR |
| EXAMPLE: PLEASE SEE CONFERENCE ROOM 101 WHICH SHOWS TWO |
| FIXTURES ON PLANS, YET THE INPUT DATA REPORT SHOWS ONLY |
| ONE. |
| PLEASE CONFIRM FIXTURE BALLAST VA RATING PER |
| 13-415.2.ABC.1.2 (2). FIXTURES ARE SHOWN AS 3-32W |
| BULBS, YET VA IS LESS.PLEASE CONFIRM EFFICACY OF |
| BALLAST. |
| 13-415.1.C, 13-415.2 |
| PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED BEFORE |
| RESUBMITTING. |
| |
| ** THE COMMENT IS MINOR AND ONLY NEEDS SOME ADJUSTMENTS |
| BEFORE REVIEW CAN BE PASSED. UNLESS THE FIXTURE TYPE |
| CHANGES, THE ELECTRICAL PLANS WERE STAMPED. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |