Plan Review Notes
Plan Review Notes For Permit 07120003
Permit Number 07120003
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-12 11:06:14*** DENIED**
  
 1) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS FOR NEW SPACES/AREAS/ROOMS.
 FBC 13-415.2
  
 2) NOTE: PLEASE CLARIFY THE AREA AND SCOPE OF WORK WIHT
 ARCHITECT AS THE COVER SHEET SEEMS TO INDICATE WORK IN
 A LARGER AREA?
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  