Date |
Text |
2007-12-10 11:12:09 | |
| BUILDING PLAN REVIEW |
| PERMIT: 07120002 |
| ADD: 2580- METRO CENTRE DR. #1 |
| CONT: FISHER CONTRACTING CORP |
| TEL: (561)691-4716 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| 12/10/07 |
| |
| 1A)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 1B) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION |
| DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 2) 106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS THAT |
| ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. PROVIDE THE |
| PRODUCT APPROVAL FOR THE NEW STOREFRONT IN OFFICE #1. |
| |
| 3) 11-4.24.2 THE BREAK ROOM SINK SHALL BE MOUNTED WITH |
| THE COUNTER RIM NO HIGHER THAN 34 INCHES ABOVE THE |
| FINISH FLOOR. THE DEPTH OF THE SINK SHALL BE 6 ? |
| INCHES. A CLEAR FLOOR SPACE SHALL BE PROVIDED IN FRONT |
| OF THE BREAK ROOM SINK TO ALLOW A FORWARD APPROACH. |
| SHEET A-6 DETAIL #2 SHOWS DOORS IN FRONT OF THE SINK, |
| THIS WILL NOT MEET THE REQUIREMENTS OF THE FORWARD |
| APPROACH PER 11-4.24.5. |
| |
| 4)EACH WALL SHALL BE LABELED ON SHEET A-1 TO REFLECT |
| THE WALL DETAILS ON SHEET A-4. ON SHEET A.1 TWO |
| DIFFERENT TYPES OF WALLS HAVE THE SAME LABELED P-2. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE. 106.1.1. |
| |
| 5)A LIFE SAFETY PLAN SHALL BE SUBMITTED SHOW THE |
| MEANS OF EGRESS FROM THE BUILDING IN CONFORMANCE WITH |
| FBC CHAPTER 10. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| [email protected] |