2008-04-01 07:17:36 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| |
| COMMENT FROM PREVIOUS AUDIT: |
| |
| 4.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE |
| REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5), |
| FS553.79 (2).HOW DOES THIS RENOVATION AFFECT THE FIRE |
| SPRINKLER LAYOUT? |
| |
| 2ND AUDIT, NOT ADDRESSED.PROVIDE, AT A MINIMUM, A |
| SPRINKLER HEAD LAYOUT AND SPECIFICATION.CALCULATIONS |
| AND SHOP DRAWINGS MAY BE SUBMITTED AT THE TIME OF FIRE |
| SPRINKLER PERMIT. |
| |
| 3RD AUDIT, ARCHITECT'S RESPONSE THAT THIS HAS BEEN |
| REQUESTED IS NOTED, THANK YOU.PLEASE NOTE THAT THIS |
| IS A STATUTORY REQUIREMENT AND CANNOT BE PROVISO'D. |
| THEREFORE, THIS PERMIT WILL REMAIN IN FAILED STATUS |
| UNTIL THE FIRE SPRINKLER PERMIT HAS BEEN REVIEWED AND |
| IS READY TO BE ISSUED.PLEASE ADVISE WHEN THIS IS |
| ISSUED AND THE STATUS WILL BE CHANGED TO "P". |
| |
| ***PLEASE NOTE THAT FIRE SPRINKLER PLANS REQUIRE |
| PRIVATE PROVIDER REVIEW AS IT IS A PART OF THE BUILDING |
| REVIEW*** |
| |
| NEW COMMENTS: |
| |
| 6.SHEET A7.1.2 HAS BEEN VOIDED PRIOR TO BUILDING |
| REVIEW AS IT IS LACKING THE COMPLETE ADDRESS AND IS NOT |
| INCLUDED IN THE INDEX SHEET.THIS SHEET IS REQUIRED AS |
| IT INCLUDES BUILDING DETAILS. |
| |
| 7.PLEASE CLARIFY; LEVEL 6 IS REFERENCED ON SHEET |
| A0.0.1 AND OTHER PLACES; SUITE NUMBER IS 700.ARE YOU |
| USING A BRITISH STORY NUMBERING CONVENTION? |
| |
| |
| |