2008-01-16 18:14:32 | REVIEW #: 2ND |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| |
| 1. BALANCED RETURN PROVISIONS HAVE BEEN PROVIDED FOR |
| ALL ROOMS LISTED IN THE PREVIOUS COMMENT EXCEPT FOR |
| ROOM 610. NO CHANGES OR TRANSFER DUCT COULD BE FOUND ON |
| PLANS. PLEASE CORRECT AND RESUBMIT. FBC, M 601.4. |
| |
| 2. IT IS UNCLEAR HOW THREE TRANSFER DUCTS IN ROOM 621 |
| COMMUNICATING WITH ROOM 624 IS TO PROVIDE BALANCED |
| RETURN FOR THE QUANTITIES OF AIR BEING SUPPLIED TO THAT |
| HALF OF THE FLOOR SPACE. PLEASE CLARIFY. BALANCED |
| RETURN IS REQUIRED IN ACCORDANCE WITH FBC, M 601.4. |
| |
| 3. OK |
| |
| 4. OK |
| |
| 5. THIS ITEM HAS NOT BEEN ADDRESSED. THE BUILDING |
| OFFICIAL HAS ESTABLISHED A POLICY BY WHICH TENANT |
| IMPROVEMENT PERMITS COULD BE ISSUED FOR SHELL BUILDINGS |
| PRIOR TO COMPLETION OF THE SHELL. THAT POLICY REQUIRES |
| A LETTER OF UNDERSTANDING (SEE PREVIOUS MECHANICAL |
| REVIEW COMMENT #5). THIS LETTER WAS NOT INCLUDED WITH |
| THIS SUBMITTAL. ALSO, A SHOP DRAWING REVIEW STAMP AND |
| ORIGINAL SIGNATURE OF THE BASE BUILDING DESIGNER OF |
| RECORD ON THE TENANT PLANS IS REQUIRED PRIOR TO PERMIT |
| ISSUANCE. THESE PLANS HAVE BEEN INITIALED BY SOMEONE |
| OTHER THAN DANIEL A. CAMPIA, THE MECHANICAL ENGINEER OF |
| RECORD. PLEASE INCLUDE THESE REQUIREMENTS WITH |
| RESUBMITTAL. |
| |