2007-12-03 16:59:29 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2005 AMENDMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| |
| 1. H2.6.1: ROOM 601, 606, 607, 610, 620, 638 |
| ARCHITECTURAL FLOOR PLAN SHOWS WALLS FOR THESE ROOMS |
| FROM FLOOR TO DECK. THERE ARE NO PROVISIONS FOR RETURN |
| AIR FROM THESE ROOMS. BALANCED RETURN AIR IS REQUIRED |
| PER FBC, M 601.4. SHOW HOW BALANCED RETURN IS TO BE |
| ACHIEVED IN THIS AREA. |
| |
| 2. H2.6.1: ROOM 620 HAS AN R/A TRANSFER SHOWN FROM ROOM |
| 621. HOWEVER, THERE IS NO MEANS SHOWN FRO RETURN AIR |
| FROM ROOM 620 BACK TO CENTRALIZED RETURN. ALSO, |
| CENTRALIZED RETURN INTAKE IS LOCATED ABOVE CLERICAL |
| ROOM 619. THIS INTAKE IS SEPARATED FROM THE EAST SIDE |
| OF THE SPACE BY TWO CONTINUOUS P25 WALLS, ONE ON EACH |
| SIDE OF RECEPTION 620 AND CONFERENCE 621. PLEASE SHOW |
| HOW BALANCED RETURN IN THESE AREAS IS TO BE ACHIEVED. |
| |
| 3. H7.6.1: VENTILATION AIR CALCULATIONS STATE THAT |
| THERE IS AN EXPECTED OCCUPANCY OF 35 AND THIS NUMBER IS |
| USED PER THE PROVISIONS OF FBC, M 403.3.1. THIS SECTION |
| ALLOWS FOR VENTILATION TO BE BASED ON ACTUAL OCCUPANTS, |
| NOT EXPECTED OCCUPANTS. THIS WOULD REQUIRE SOME MEANS |
| OF COUNTING THE NUMBER OF OCCUPANTS IN THE SPACE AT ANY |
| GIVEN TIME AND VARYING THE VENTILATION RATE BASED ON |
| THAT NUMBER. ABSENT THAT TYPE OF SYSTEM OR APPROVED |
| STATISTICAL DATA SHOWING AN OCCUPANT LOAD DIFFERENT |
| THAN THAT IN TABLE 403.3, AS ALLOWED BY THE EXCEPTION |
| TO THAT SECTION, THE VENTILATION RATE SHALL BE |
| DETERMINED IN ACCORDANCE WITH TABLE 403.3. |
| |
| -BASED ON THE SQUARE FOOTAGE SHOWN ON THE LIFE SAFETY |
| PLAN THERE IS APPROX. 6800S.F. OF OFFICE SPACE, |
| EXCLUDING CONFERENCE ROOMS, CORRIDORS, CLOSETS, ETC. |
| THE OCCUPANT LOAD AT 7/1000 IS 48. THE RATE FOR OFFICE |
| SPACE IS 20 CFM PER PERSON FOR A TOTAL OF 960CFM. |
| |
| - BASED ON THE SQUARE FOOTAGE SHOWN ON THE LIFE SAFETY |
| PLAN THERE IS APPROX. 1179S.F. IN CONFERENCE ROOMS 621, |
| 639 AND RNET ROOM 623. THE OCCUPANT LOAD AT 50/1000 IS |
| 59. THE RATE FOR CONFERENCE ROOMS IS 20 CFM PER PERSON |
| FOR A TOTAL OF 1180 CFM. |
| |
| - BASED ON THE SQUARE FOOTAGE SHOWN ON THE LIFE SAFETY |
| PLAN THERE IS APPROX. 685S.F. IN THE RECEPTION AREA |
| ROOM 620. THE OCCUPANT LOAD AT 60/1000 IS 41. THE RATE |
| FOR THE RECEPTION AREA IS 15 CFM PER PERSON FOR A TOTAL |
| OF 615 CFM. |
| |
| BASED ON THESE CALCULATIONS, THE OUTSIDE AIR |
| REQUIREMENTS FOR THIS SPACE EXCEEDS THE TOTAL SUPPLIED |
| BY BASE BUILDING SYSTEMS FOR THIS FLOOR. THE AMOUNT OF |
| OUTSIDE AIR FOR THIS SPACE CANNOT EXCEED THE PERCENTAGE |
| OF THE FLOOR SPACE USED BY THIS TENANT BUILD-OUT IN |
| ORDER TO ALLOW FOR ENOUGH FRESH AIR TO REMAIN FOR THE |
| REST OF THE FLOOR WHEN OCCUPIED. THE BASE BUILDING |
| VENTILATION SYSTEM WAS DESIGNED UNDER ASHRAE 62.1-2004 |
| AS ALLOWED BY FBC, M 403.4. DESIGNER SHOULD DETERMINE |
| IF THAT METHOD OF DESIGN WOULD BRING THE VENTILATION |
| REQUIREMENTS TO WITHIN THE QUANTITIES PROVIDED BY BASE |
| BUILDING SYSTEMS OR IF ADDITIONAL OUTSIDE AIR IS |
| REQUIRED BASED ON THE QUANTITIES REQUIRED BY TABLE |
| 403.3. |
| |
| 4. CEILING RETURN PLENUM CAVITIES DESIGNED FOR AIR |
| TRANSPORT SHALL BE LINED WITH AN AIR BARRIER AND SEALED |
| IN ACCORDANCE WITH SECTION 603.9 AND SHALL BE INSULATED |
| IN ACCORDANCE WITH TABLE 13-410.1.ABC.2.2. APPROVED AIR |
| BARRIERS SHALL BE AS DEFINED IN FBC, M 603.9.1 AND THE |
| R-VALUE OF INSULATION SHALL BE MIN. R-8 IN ACCORDANCE |
| WITH THE ABOVE TABLE. SHOW THESE COMPONENTS AS A |
| MINIMUM AS PART OF DETAIL 1 ON PG A7.6.3 |
| |
| 5. AS THIS TENANT BUILD OUT IS TO TAKE PLACE IN A |
| BUILDING WHICH HAS NOT BEEN COMPLETED, AS A CONDITION |
| OF PERMIT, THE CONSTRUCTION SERVICES DEPARTMENT IS |
| REQUIRING A LETTER OF UNDERSTANDING BETWEEN THE BASE |
| BUILDING CONTRACTOR, THE TENANT CONTRACTOR, AND THE |
| BASE BUILDING DEVELOPER. THIS LETTER SHALL STATE THAT |
| ALL INTERESTED PARTIES SHALL TAKE RESPONSIBILITY FOR |
| THEIR WORK AND ACKNOWLEDGE THAT THE WORK OF ONE |
| CONTRACTOR HAS THE POTENTIAL TO IMPACT THE OTHER?S |
| ABILITY TO OBTAIN FINAL INSPECTIONS. CODE DEFICIENCIES |
| WILL NOT BE OVERLOOKED REGARDLESS OF WHO IS RESPONSIBLE |
| FOR THE RELATED WORK. |
| |