2007-12-14 11:28:06 | ***DENIED*** | | | | 1) THE SUITE IDENTIFICATION TO BE ADDED TO TITLE BLOCK. | | THE CHARACTERS LOCATED NEAR THE FRONT ENTRANCE OF THE | | BUSINESS TO BE MINIMUM OF (3") AND CONTRASTING TO | | BACKGROUND PER CITY OF WEST PAKM BEACH REQUIREMENTS. | | | | 2) FIRE EXTINGUISHERS ARE REQUIRED TO BE MINIMUM | | 2A-10B,C RATED. | | | | 3) FIRE RATED DOORS TO BE ILLUSTRATED IN TERMS OF | | HOURS. | | | | 4) PLEASE CLARIFY OCCUPANT LOAD FOR SPACE PER NFPA 101, | | SEC. 7.3.1.2. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PALN REVIEW | | FIRE PREVENTIO (561) 804-4756 |
|