Plan Review Notes
Plan Review Notes For Permit 07110754
Permit Number 07110754
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-05 11:05:40** DENIED**
  
 1) NOTE: PLEASE SEE THE PERMIT APPLICATION AND
 SUPPORTING DOCUMENTS HAVE BEEN ROUTED TO THE ADDRESSING
 REVIEWER.
 THE PERMIT APPLICATION AS APPLIED INDICATES THE 6TH
 FLOOR HOWEVER THIS TENANT DOES NOT TAKE THE ENTIRE
 FLOOR AND WILL REQUIRE A SUITE/UNIT #.
 PLEASE KNOW ONCE THIS HAS BEEN DETERMINED THE TITLE
 BLOCKS ARE TO BE REVISED INDICATING THIS ADJUSTMENT.
 FBC 106.1.2, 106.3.5.1.2, 106.5.3 ETC
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE BE SURE ALL ROOM AND AREA DESIGNATIONS
 ARE LISTED ON PLANS FOR SCOPE OF WORK BEING DONE UNDER
 THIS PERMIT APPLICATION.
 PLEASE COMPLETE ALL CIRCUITING ON PLANS FOR ALL
 ELECTRICAL AS SHOWN.
 FOR EXAMPLE:
 PLEASE SEE E2.6.4 WHICH SHOWS NO CIRCUITING ETC. THIS
 ROOM BY THE LABEL ON THE ARCHITECTURAL PLANS SHEET
 A2.6.1 SHOWS THIS AS THE CATERING ROOM, YET THESE PLANS
 INDICATE NEW RECEPTACLES AND OUTLETS WITH NO
 CIRCUITING.?
 PLEASE COMPLETE.
 NEC 408.4, 310.16, 240.4
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 3) NOTE: PLEASE GO OVER ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE
 SEE FOR EXAMPLE:
 PLEASE SEE ROOM 622 AND 623 WHICH INDICATES CIRCUITS
 *P26-34,36 AND 38* YET THE PLANS FOR ROOM 623 DO NOT
 CONTAIN ANY 38?
 PLEASE SEE THIS SAME ROOM #623 WHICH SHOWS CIRCUIT 37,
 YET CIRCUIT 37 ON PANEL SCHEDULE SHOWS ROOM 673. COULD
 NOT LOCATE ANY ROOM 673.
 PLEASE SEE FOR EXAMPLE SAME AREA WHICH SHOWS CIRCUITS
 *P-26, 35, 37, AND 39* YET THE PANEL SCHEDULE SHOWS A
 *SPARE* FOR #39.
 ** THESE ARE A FEW EXAMPLES FOR COORDINATION.
 NEC 408.4
 FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION
  
 4) NOTE: PLEASE CORRELATE ALL LOADS ON PANEL SCHEDULES
 WITH THAT OF THE LOADS SET FORTH IN THE NEC FOR
 RECEPTACLES AT 180VA PER YOKE.
 PLEASE SEE NEC 220 .14/220.44.
 PLEASE SEE FOR EXAMPLE CIRCUIT #6 ON PLANS WHICH SHOW 7
 RECEPTACLES/YOKES YET THE VA SHOWN ON PANEL SCHEDULE IS
 LOWER.
 PLEASE SEE FOR EXAMPLE CIRCUIT #14 AND #29 ETC. PLEASE
 CORRELATE ALL LOADS WHICH ARE NOT KNOWN DEDICATED LOADS
 FOR EQUIPMENT ETC ON PANEL SCHEDULES.
  
 5) NOTE: PLEASE SEE THE ZONE DESIGNATIONS ON E6.6.2 AND
 2.6.2 ARE NOT LABELED THE SAME. PLEASE CLARIFY AND
 COORDINATE.
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE THE TOTALS SHOWN ON LCP6 AND LMC DO
 NOT APPEAR TO CORRELATE WITH THE LIGHTING WATTAGE LOADS
 ON LIGHTING PERFORMANCE CALCULATIONS.
 PLEASE ADJUST AND CORRELATE.
 13-415.2
 FBC 106.1.2
  
 7) NOTE: PLEASE CLARIFY OPEN OFFICE AREAS NOTED AS
 CLOSED OFFICE ON LP CALCULATIONS. THE ALLOWANCES ARE
 THE SAME AND THIS COULD BE REDLINED.
 SEE ROOM/AREA 619 FOR EXAMPLE.
  
 8) NOTE: PLEASE SEE THE OCTAGONAL NOTE #2 ON PLANS NEXT
 TO THE J-BOX SYMBOL AT DOORS WHICH BY THE NOTE MENTIONS
 THESEARE TABLE TOP MONUMENTS FOR PHONE ETC.
 THIS NOTE DOES NOT SEEM TO BE PART OF THE DOOR AREA
 J-BOX.
 PLEASE COORDINATE AND ADJUST. WHAT ARE THESE J-BOXES
 FOR? IF PART OF ACCESS CONTROL PLEASE BE SURE TO SEE
 NFPA-101 CHAPTER 7 FOR ACCESS/EGRESS CONTROLS. THIS IS
 NOT PART OF THIS PERMIT AT THIS TIME.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]