2007-12-05 11:05:40 | ** DENIED** |
| |
| 1) NOTE: PLEASE SEE THE PERMIT APPLICATION AND |
| SUPPORTING DOCUMENTS HAVE BEEN ROUTED TO THE ADDRESSING |
| REVIEWER. |
| THE PERMIT APPLICATION AS APPLIED INDICATES THE 6TH |
| FLOOR HOWEVER THIS TENANT DOES NOT TAKE THE ENTIRE |
| FLOOR AND WILL REQUIRE A SUITE/UNIT #. |
| PLEASE KNOW ONCE THIS HAS BEEN DETERMINED THE TITLE |
| BLOCKS ARE TO BE REVISED INDICATING THIS ADJUSTMENT. |
| FBC 106.1.2, 106.3.5.1.2, 106.5.3 ETC |
| FAC 61G1-16.004, 61G15-23.002 |
| |
| 2) NOTE: PLEASE BE SURE ALL ROOM AND AREA DESIGNATIONS |
| ARE LISTED ON PLANS FOR SCOPE OF WORK BEING DONE UNDER |
| THIS PERMIT APPLICATION. |
| PLEASE COMPLETE ALL CIRCUITING ON PLANS FOR ALL |
| ELECTRICAL AS SHOWN. |
| FOR EXAMPLE: |
| PLEASE SEE E2.6.4 WHICH SHOWS NO CIRCUITING ETC. THIS |
| ROOM BY THE LABEL ON THE ARCHITECTURAL PLANS SHEET |
| A2.6.1 SHOWS THIS AS THE CATERING ROOM, YET THESE PLANS |
| INDICATE NEW RECEPTACLES AND OUTLETS WITH NO |
| CIRCUITING.? |
| PLEASE COMPLETE. |
| NEC 408.4, 310.16, 240.4 |
| FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 3) NOTE: PLEASE GO OVER ALL CIRCUITING ON PLANS AND |
| CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE |
| SEE FOR EXAMPLE: |
| PLEASE SEE ROOM 622 AND 623 WHICH INDICATES CIRCUITS |
| *P26-34,36 AND 38* YET THE PLANS FOR ROOM 623 DO NOT |
| CONTAIN ANY 38? |
| PLEASE SEE THIS SAME ROOM #623 WHICH SHOWS CIRCUIT 37, |
| YET CIRCUIT 37 ON PANEL SCHEDULE SHOWS ROOM 673. COULD |
| NOT LOCATE ANY ROOM 673. |
| PLEASE SEE FOR EXAMPLE SAME AREA WHICH SHOWS CIRCUITS |
| *P-26, 35, 37, AND 39* YET THE PANEL SCHEDULE SHOWS A |
| *SPARE* FOR #39. |
| ** THESE ARE A FEW EXAMPLES FOR COORDINATION. |
| NEC 408.4 |
| FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION |
| |
| 4) NOTE: PLEASE CORRELATE ALL LOADS ON PANEL SCHEDULES |
| WITH THAT OF THE LOADS SET FORTH IN THE NEC FOR |
| RECEPTACLES AT 180VA PER YOKE. |
| PLEASE SEE NEC 220 .14/220.44. |
| PLEASE SEE FOR EXAMPLE CIRCUIT #6 ON PLANS WHICH SHOW 7 |
| RECEPTACLES/YOKES YET THE VA SHOWN ON PANEL SCHEDULE IS |
| LOWER. |
| PLEASE SEE FOR EXAMPLE CIRCUIT #14 AND #29 ETC. PLEASE |
| CORRELATE ALL LOADS WHICH ARE NOT KNOWN DEDICATED LOADS |
| FOR EQUIPMENT ETC ON PANEL SCHEDULES. |
| |
| 5) NOTE: PLEASE SEE THE ZONE DESIGNATIONS ON E6.6.2 AND |
| 2.6.2 ARE NOT LABELED THE SAME. PLEASE CLARIFY AND |
| COORDINATE. |
| FBC 106.1.2 |
| |
| 6) NOTE: PLEASE SEE THE TOTALS SHOWN ON LCP6 AND LMC DO |
| NOT APPEAR TO CORRELATE WITH THE LIGHTING WATTAGE LOADS |
| ON LIGHTING PERFORMANCE CALCULATIONS. |
| PLEASE ADJUST AND CORRELATE. |
| 13-415.2 |
| FBC 106.1.2 |
| |
| 7) NOTE: PLEASE CLARIFY OPEN OFFICE AREAS NOTED AS |
| CLOSED OFFICE ON LP CALCULATIONS. THE ALLOWANCES ARE |
| THE SAME AND THIS COULD BE REDLINED. |
| SEE ROOM/AREA 619 FOR EXAMPLE. |
| |
| 8) NOTE: PLEASE SEE THE OCTAGONAL NOTE #2 ON PLANS NEXT |
| TO THE J-BOX SYMBOL AT DOORS WHICH BY THE NOTE MENTIONS |
| THESEARE TABLE TOP MONUMENTS FOR PHONE ETC. |
| THIS NOTE DOES NOT SEEM TO BE PART OF THE DOOR AREA |
| J-BOX. |
| PLEASE COORDINATE AND ADJUST. WHAT ARE THESE J-BOXES |
| FOR? IF PART OF ACCESS CONTROL PLEASE BE SURE TO SEE |
| NFPA-101 CHAPTER 7 FOR ACCESS/EGRESS CONTROLS. THIS IS |
| NOT PART OF THIS PERMIT AT THIS TIME. |
| |
| |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |