Plan Review Notes For Permit 07110754 |
Permit Number |
07110754 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-12-07 11:03:43 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.SEE ELECTRIC COMMENTS REGARDING ADDRESSING.THIS | | ISSUE SHOULD BE RESOLVED PRIOR TO PERMIT ISSUANCE. | | | | 2.SEE MECHANICAL COMMENTS, ITEM 12, REGARDING TENANT | | BUILDOUT.THE DOR ON THIS JOB IS TO PROVIDE SHOP | | DRAWING REVIEW STAMP (MICHAEL O ROSSIN IS ARCHITECT OF | | RECORD, ROBERT J. MCNAMARE, PE IS STRUCTURAL ENGINEER | | OF RECORD). | | | | 3.APPLICABLE CODES SHOULD INCLUDE 2007 AMENDMENTS | | EFFECTIVE 7/1/07, SHEET A01.1. WWW.FLORIDABUILDING.ORG | | | | 4.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE | | REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5), | | FS553.79 (2).HOW DOES THIS RENOVATION AFFECT THE FIRE | | SPRINKLER LAYOUT? | | | | 5.SHOW MANEUVERING CLEARANCE, PULL SIDE, DOOR B619 AT | | RECEPTION, FBC FIGURE 11-25. | | |
|