Plan Review Notes
Plan Review Notes For Permit 07110752
Permit Number 07110752
Review Stop E
Sequence Number 3
Notes
Date Text
2008-03-31 19:30:44** DENIEDAUDIT **
  
  
 1) NOTE: PLEASE SEE REVISED SHEET A2.1.3 DOES NOT
 COORDINATE WITH SHEET E2.1.1. PLEASE SEE ROOM 122 AS
 SHOWN ON ELECTRICAL PLANS WHICH CONTAIN A WALL BETWEEN
 122 AND 121. PLEASE ALSO SEE FIXTURE LAYOUT HAS NOW
 BEEN REVISED.
 PLEASE COORDINATE SHEET E2.1.1 WITH OTHER PLANS AND
 SHEETS AS NO WALL IS SHOWN ON POWER PLANS NOR DOES THIS
 WALL APPEAR ON ARCHITECTURAL PLANS.
 PLEASE ADJUST ANY FIXTURE LAYOUTS.
  
 2) NOTE: PLEASE SEE SHEET E3.1.1 HAS NOW BEEN CHANGED
 FROM PREVIOUS REVIEW. PLEASE SEE THE TITLE BLOCKS
 INDICATES REVISIONS 1, 3 AND 6, HOWEVER PLANS ONLY
 INDICATE A REVISION #4. THIS REVISION #4 ON RISER IS
 NOT ON TITLE BLOCK AND REVISION #6 ON NOT ON PLANS.
 PLEASE COMPLETE PLANS WITH ALL REVISIONS AND COORDINATE
 ALL REVISIONS. IT IS UNCLEAR WHETHER OR NOT PLANS
 CONTAIN REVISIONS OR ARE MISSING REVISIONS NOT YET
 MADE.
  
 3) NOTE: PLEASE SEE NEW CHANGES MADE TO 2PUPS NOW HAS
 PANEL TO A 120/240V SINGLE PHASE PANEL WHICH IS OK,
 HOWEVER PLEASE SUBMIT THE MANUFACTURES SPEC/CUT SHEET
 FOR THIS PROPOSED UNIT IF THIS WILL BE UNDER THIS
 PERMIT.
 FBC 106.1.2, NE C90.7, 110.3
 ** PLEASE SEE THE LOAD WAS ADJUSTED ON PANEL P21 AND
 LM41, HOWEVER THE LOAD SUMMARY FOR LM41 WAS NOT
 CHANGED. PLEASE EXPLAIN THE KVA OF 16 SHOWN ON PANEL
 P21, WHEN THE LOAD IS NOT THAT OF THE LOAD ON UPS
 PANEL.
 NEC 220.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  