Date |
Text |
2008-03-31 19:30:44 | ** DENIEDAUDIT ** |
| |
| |
| 1) NOTE: PLEASE SEE REVISED SHEET A2.1.3 DOES NOT |
| COORDINATE WITH SHEET E2.1.1. PLEASE SEE ROOM 122 AS |
| SHOWN ON ELECTRICAL PLANS WHICH CONTAIN A WALL BETWEEN |
| 122 AND 121. PLEASE ALSO SEE FIXTURE LAYOUT HAS NOW |
| BEEN REVISED. |
| PLEASE COORDINATE SHEET E2.1.1 WITH OTHER PLANS AND |
| SHEETS AS NO WALL IS SHOWN ON POWER PLANS NOR DOES THIS |
| WALL APPEAR ON ARCHITECTURAL PLANS. |
| PLEASE ADJUST ANY FIXTURE LAYOUTS. |
| |
| 2) NOTE: PLEASE SEE SHEET E3.1.1 HAS NOW BEEN CHANGED |
| FROM PREVIOUS REVIEW. PLEASE SEE THE TITLE BLOCKS |
| INDICATES REVISIONS 1, 3 AND 6, HOWEVER PLANS ONLY |
| INDICATE A REVISION #4. THIS REVISION #4 ON RISER IS |
| NOT ON TITLE BLOCK AND REVISION #6 ON NOT ON PLANS. |
| PLEASE COMPLETE PLANS WITH ALL REVISIONS AND COORDINATE |
| ALL REVISIONS. IT IS UNCLEAR WHETHER OR NOT PLANS |
| CONTAIN REVISIONS OR ARE MISSING REVISIONS NOT YET |
| MADE. |
| |
| 3) NOTE: PLEASE SEE NEW CHANGES MADE TO 2PUPS NOW HAS |
| PANEL TO A 120/240V SINGLE PHASE PANEL WHICH IS OK, |
| HOWEVER PLEASE SUBMIT THE MANUFACTURES SPEC/CUT SHEET |
| FOR THIS PROPOSED UNIT IF THIS WILL BE UNDER THIS |
| PERMIT. |
| FBC 106.1.2, NE C90.7, 110.3 |
| ** PLEASE SEE THE LOAD WAS ADJUSTED ON PANEL P21 AND |
| LM41, HOWEVER THE LOAD SUMMARY FOR LM41 WAS NOT |
| CHANGED. PLEASE EXPLAIN THE KVA OF 16 SHOWN ON PANEL |
| P21, WHEN THE LOAD IS NOT THAT OF THE LOAD ON UPS |
| PANEL. |
| NEC 220. |
| |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |