2008-04-01 06:46:09 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| |
| COMMENT FROM FIRST AND SECOND AUDITS: |
| |
| 5.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE |
| REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5), |
| FS553.79 (2). |
| |
| 2ND REVIEW; SPRINKLER PLANS NOT PROVIDED.HAS THIS |
| BEEN APPLIED FOR SEPARATELY?A CLARIFICATION LETTER |
| FROM DCA STATES "PLEASE NOTE THAT DESIGN DOCUMENTS, |
| INCLUDING THE FIRE PROTECTION SPRINKLER SYSTEM (WHICH |
| IS TO BE REVIEWED BY THE APPROPRIATE FIRE SAFETY |
| INSPECTOR) ARE TO BE SUBMITTED TO YOU AT THE TIME OF |
| PERMITTING, AND THAT THOSE DESIGNS MUST BE REVIEWED FOR |
| COMPLIANCE AT THAT TIME BEFORE A PERMIT IS ISSUED." |
| |
| 3RD REVIEW, SPRINKLER PLANS NOT PROVIDED.ARCHITECT'S |
| RESPONSE THAT THIS WILL BE UNDER SEPARATE PERMIT IS |
| NOTED.AT A MINIMUM, A SPRINKLER HEAD LAYOUT PLAN IS |
| TO BE SUBMITTED WITH THIS PERMIT FOR PERMIT ISSUANCE OR |
| SUBMITTED SEPARATELY WITH COMPLETE INFORMATION FOR |
| SPRINKLER PERMIT ISSUANCE. |
| |
| PLANS ARE OTHERWISE CODE COMPLIANT; WILL REMAIN IN |
| FAILED STATUS UNTIL THE FIRE SPRINKLER PERMIT ISSUE IS |
| RESOLVED, EITHER BY SUBMISSION AND REVIEW OF A CODE |
| COMPLIANT SPRINKLER PERMIT (WHICH WOULD BE REQUIRED TO |
| REMAIN IN F STATUS UNTIL THE TENANT BUILDOUT IS ISSUED) |
| OR SUBMISSION AND REVIEW OF A SPRINKLER HEAD LAYOUT |
| WITH THE TENANT BUILDOUT PERMIT. |
| |
| ***PLEASE ADVISE IF THIS ITEM IS ADDRESSED PRIOR TO |
| RESUBMITTAL THROUGH SEPARATE PERMIT - STATUS WILL BE |
| CHANGED TO "P"*** |
| ***PLEASE NOTE THAT FIRE SPRINKLER PLANS REQUIRE |
| PRIVATE PROVIDER REVIEW AS THIS IS A BUILDING |
| REQUIREMENT*** |
| |