Plan Review Notes
Plan Review Notes For Permit 07110752
Permit Number 07110752
Review Stop E
Sequence Number 2
Notes
Date Text
2008-01-12 16:54:51*** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE PLANS HAVE NOW BEEN REVISED WITH ITEMS
 WHICH WERE NOT ON PREVIOUS PLANS FOR REVIEW.
 PLEASE SEE COMMENTS BELOW.
  
 1) NOTE: PLEASE SEE LIGHTING PLANS NOW SHOW NEW
 EXTERIOR FIXTURES XM WHICH ARE NOT LISTED ON FIXTURE
 LEGEND/SCHEDULE. THESE ARE CLOUDED AND APPEAR TO BE
 SEPARATED BY THE OTHER SINGLE XM FIXTURE AS WELL AS THE
 OTHER NEW FIXTURES EN.
 PLEASE SEE NO CIRCUITING, CONTROLS ETC HAVE BEEN
 SUBMITTED OR SHOWN FOR THESE SAME FIXTURES.
 PLEASE SEE NO EXTERIOR LIGHTING PERFORMANCE
 CALCULATIONS ARE SHOWN.
 13-415.2, 13-415.1.ABC.1.4, 13-415.2.ABC.1.3.
 NEC 240.4, 310.16, 408.4, 210, ETC.
  
  
 2) NOTE: PLEASE SEE PLANS ARE REQUIRED TO BE STAMPED
 AND SIGNED BY THE RESPONSIBLE ENGINEER ON BASE BUILDING
 AS THIS BUILDING IS STILL UNDER CONSTRUCTION AND HAS
 RECEIVED A CERTIFICATE OF OCCUPANCY.
 PLANS DO CONTAIN A (SHOP DRAWING REVIEW STAMP) HOWEVER
 NOT SIGNED BY THE ELECTRICAL DESIGNER OF RECORD.
  
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
  