2008-01-12 16:54:51 | *** DENIED 2ND REVIEW *** |
| |
| ** PLEASE SEE PLANS HAVE NOW BEEN REVISED WITH ITEMS |
| WHICH WERE NOT ON PREVIOUS PLANS FOR REVIEW. |
| PLEASE SEE COMMENTS BELOW. |
| |
| 1) NOTE: PLEASE SEE LIGHTING PLANS NOW SHOW NEW |
| EXTERIOR FIXTURES XM WHICH ARE NOT LISTED ON FIXTURE |
| LEGEND/SCHEDULE. THESE ARE CLOUDED AND APPEAR TO BE |
| SEPARATED BY THE OTHER SINGLE XM FIXTURE AS WELL AS THE |
| OTHER NEW FIXTURES EN. |
| PLEASE SEE NO CIRCUITING, CONTROLS ETC HAVE BEEN |
| SUBMITTED OR SHOWN FOR THESE SAME FIXTURES. |
| PLEASE SEE NO EXTERIOR LIGHTING PERFORMANCE |
| CALCULATIONS ARE SHOWN. |
| 13-415.2, 13-415.1.ABC.1.4, 13-415.2.ABC.1.3. |
| NEC 240.4, 310.16, 408.4, 210, ETC. |
| |
| |
| 2) NOTE: PLEASE SEE PLANS ARE REQUIRED TO BE STAMPED |
| AND SIGNED BY THE RESPONSIBLE ENGINEER ON BASE BUILDING |
| AS THIS BUILDING IS STILL UNDER CONSTRUCTION AND HAS |
| RECEIVED A CERTIFICATE OF OCCUPANCY. |
| PLANS DO CONTAIN A (SHOP DRAWING REVIEW STAMP) HOWEVER |
| NOT SIGNED BY THE ELECTRICAL DESIGNER OF RECORD. |
| |
| |
| ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| CONTACTING THIS REVIEWER. |
| |
| |