2008-01-11 16:03:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)ADDRESSED.
  
 2.)PLEASE SEE MECHANICAL COMMENT #12.THE RESPONSE
 LETTER STATES THAT THE CONSTRUCTION MANAGER AND BASE
 BUILDING DEVELOPER WILL ISSUE THIS LETTER.I WAS
 UNABLE TO LOCATE THE LETTER IN THE PACKAGE.
  
 3.)ADDRESSED.
  
 4.FROM FIRST REVIEW - ON EITHER THE FLOOR PLAN OR THE
 LIFE SAFETY PLAN, PLEASE NOTE ALL REQUIRED FIRE
 RESISTANCE RATED ELEMENTS AND WALLS.SEE MECHANICAL
 SHEET H2.1.1, AN EXHAUST FAN IS SHOWN THROUGH THE WALL
 TO THE GARAGE AREA.ISN'T THERE AN OCCUPANCY
 SEPARATION AT THIS WALL?SEE FBC712, PENETRATIONS.
  
 2ND REVIEW; 2 HOUR FIRE RATED WALLS SHOWN ON A2.1.5.
 PLEASE SEE SHEET A0.22, GROUND FLOOR PLAN (LIFE SAFETY)
 FOR THE BASE BUILDING, AND NOTE THE FOLLOWING:
  
 A.A 2 HOUR WALL IS SHOWN ON THE TENANT BUILDOUT PLAN
 BETWEEN THE BANK AND THE LOBBY.THIS IS NOT SHOWN ON
 THE BASE BUILDING.PLEASE NOTE THAT IT IS ACCEPTABLE
 TO EXCEED CODE COMPLIANCE, BUT IF NOTED ON THE PLAN AS
 HAVING A REQUIRED FIRE RESISTANCE RATING WILL BE
 TREATED AS SUCH.
  
 B.THE BASE BUILDING SHOWS A REQUIRED 2 HOUR OCCUPANCY
 SEPARATION BETWEEN THE PARKING GARAGE RAMP (NOTED ON
 THE PLAN AS "OPEN AIR RAMP AREA" AND "OUTSIDE WALL &
 CONC. RAMP") AND THE BANK.THE PLAN HAS BEEN REVISED
 TO SHOW OTHER FIRE RATED WALLS.PLEASE NOTE THE 2 HOUR
 REQUIREMENT AS REQUESTED OR CLARIFY HOW AND WHY THIS
 RATING REQUIREMENT HAS BEEN REMOVED.FIRE RESISTANCE
 RATINGS ARE REQUIRED ON PLANS TO EXPEDITE FIELD ISSUES
 WHICH MAY ARISE.
  
 5.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2).
  
 2ND REVIEW; SPRINKLER PLANS NOT PROVIDED.HAS THIS
 BEEN APPLIED FOR SEPARATELY?A CLARIFICATION LETTER
 FROM DCA STATES "PLEASE NOTE THAT DESIGN DOCUMENTS,
 INCLUDING THE FIRE PROTECTION SPRINKLER SYSTEM (WHICH
 IS TO BE REVIEWED BY THE APPROPRIATE FIRE SAFETY
 INSPECTOR) ARE TO BE SUBMITTED TO YOU AT THE TIME OF
 PERMITTING, AND THAT THOSE DESIGNS MUST BE REVIEWED FOR
 COMPLIANCE AT THAT TIME BEFORE A PERMIT IS ISSUED."
  
 6.SHOW MANEUVERING CLEARANCE, PULL SIDE, DOOR A119,
 FBC FIGURE 11-25.
  
 7.BATHROOMS 114, 113, A2.1.4 SHOWS VWC AS WALL
 FINISH.THIS WAS NOT INCLUDED IN THE SCHEDULE OF
 FINISHES; PLEASE SEE FBC1210.2 REGARDING WALL FINISHES
 (BATHROOM, NONABSORBENT SURFACE REQUIRED).ALSO NOTE
 THAT THE DETAIL ROOM NUMBERS DO NOT CORRELATE (SHOWN AS
 113/112), SHEET A3.1.1.
  
 8.THE FLOOR PLAN AND BREAK ROOM 112 PLAN SHOWS A
 SINK, BUT THE DETAILS 111 (NOTE THAT THE ROOM
 DESIGNATION NUMBER DOES NOT CORRELATE WITH FLOOR PLAN)
 DO NOT SHOW A SINK, A3.1.1, AND CABINET DOORS ARE
 SHOWN.SEE FBC11-4.24.3, 11-4.24.5, KNEE CLEARANCE.