2008-01-11 16:03:11 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| |
| 1.)ADDRESSED. |
| |
| 2.)PLEASE SEE MECHANICAL COMMENT #12.THE RESPONSE |
| LETTER STATES THAT THE CONSTRUCTION MANAGER AND BASE |
| BUILDING DEVELOPER WILL ISSUE THIS LETTER.I WAS |
| UNABLE TO LOCATE THE LETTER IN THE PACKAGE. |
| |
| 3.)ADDRESSED. |
| |
| 4.FROM FIRST REVIEW - ON EITHER THE FLOOR PLAN OR THE |
| LIFE SAFETY PLAN, PLEASE NOTE ALL REQUIRED FIRE |
| RESISTANCE RATED ELEMENTS AND WALLS.SEE MECHANICAL |
| SHEET H2.1.1, AN EXHAUST FAN IS SHOWN THROUGH THE WALL |
| TO THE GARAGE AREA.ISN'T THERE AN OCCUPANCY |
| SEPARATION AT THIS WALL?SEE FBC712, PENETRATIONS. |
| |
| 2ND REVIEW; 2 HOUR FIRE RATED WALLS SHOWN ON A2.1.5. |
| PLEASE SEE SHEET A0.22, GROUND FLOOR PLAN (LIFE SAFETY) |
| FOR THE BASE BUILDING, AND NOTE THE FOLLOWING: |
| |
| A.A 2 HOUR WALL IS SHOWN ON THE TENANT BUILDOUT PLAN |
| BETWEEN THE BANK AND THE LOBBY.THIS IS NOT SHOWN ON |
| THE BASE BUILDING.PLEASE NOTE THAT IT IS ACCEPTABLE |
| TO EXCEED CODE COMPLIANCE, BUT IF NOTED ON THE PLAN AS |
| HAVING A REQUIRED FIRE RESISTANCE RATING WILL BE |
| TREATED AS SUCH. |
| |
| B.THE BASE BUILDING SHOWS A REQUIRED 2 HOUR OCCUPANCY |
| SEPARATION BETWEEN THE PARKING GARAGE RAMP (NOTED ON |
| THE PLAN AS "OPEN AIR RAMP AREA" AND "OUTSIDE WALL & |
| CONC. RAMP") AND THE BANK.THE PLAN HAS BEEN REVISED |
| TO SHOW OTHER FIRE RATED WALLS.PLEASE NOTE THE 2 HOUR |
| REQUIREMENT AS REQUESTED OR CLARIFY HOW AND WHY THIS |
| RATING REQUIREMENT HAS BEEN REMOVED.FIRE RESISTANCE |
| RATINGS ARE REQUIRED ON PLANS TO EXPEDITE FIELD ISSUES |
| WHICH MAY ARISE. |
| |
| 5.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE |
| REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5), |
| FS553.79 (2). |
| |
| 2ND REVIEW; SPRINKLER PLANS NOT PROVIDED.HAS THIS |
| BEEN APPLIED FOR SEPARATELY?A CLARIFICATION LETTER |
| FROM DCA STATES "PLEASE NOTE THAT DESIGN DOCUMENTS, |
| INCLUDING THE FIRE PROTECTION SPRINKLER SYSTEM (WHICH |
| IS TO BE REVIEWED BY THE APPROPRIATE FIRE SAFETY |
| INSPECTOR) ARE TO BE SUBMITTED TO YOU AT THE TIME OF |
| PERMITTING, AND THAT THOSE DESIGNS MUST BE REVIEWED FOR |
| COMPLIANCE AT THAT TIME BEFORE A PERMIT IS ISSUED." |
| |
| 6.SHOW MANEUVERING CLEARANCE, PULL SIDE, DOOR A119, |
| FBC FIGURE 11-25. |
| |
| 7.BATHROOMS 114, 113, A2.1.4 SHOWS VWC AS WALL |
| FINISH.THIS WAS NOT INCLUDED IN THE SCHEDULE OF |
| FINISHES; PLEASE SEE FBC1210.2 REGARDING WALL FINISHES |
| (BATHROOM, NONABSORBENT SURFACE REQUIRED).ALSO NOTE |
| THAT THE DETAIL ROOM NUMBERS DO NOT CORRELATE (SHOWN AS |
| 113/112), SHEET A3.1.1. |
| |
| 8.THE FLOOR PLAN AND BREAK ROOM 112 PLAN SHOWS A |
| SINK, BUT THE DETAILS 111 (NOTE THAT THE ROOM |
| DESIGNATION NUMBER DOES NOT CORRELATE WITH FLOOR PLAN) |
| DO NOT SHOW A SINK, A3.1.1, AND CABINET DOORS ARE |
| SHOWN.SEE FBC11-4.24.3, 11-4.24.5, KNEE CLEARANCE. |