Plan Review Notes
Plan Review Notes For Permit 07110752
Permit Number 07110752
Review Stop P
Sequence Number 1
Notes
Date Text
2007-12-06 09:08:06DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. PLANS TO BE ROUTED TO ADDRESSING TO DETERMINE SUITE
 NUMBER. ONCE ESTABLISHED THE SUITE NUMBER SHALL BE
 INDICATED ON THE TITLE BLOCK OF EACH SHEET. SECTION
 106.1.1.
  
 2. A2.1.4 WALL FINISH LEGEND FOR THE MEN'S, (113), AND
 THE WOMEN'S, (114) TOILET ROOMS INDICATE P-1/CWT. CWT
 IS NOT SHOWN ON THE WALL FINISH LEGEND. PLEASE CLARIFY.
 ALSO P-1 PAINT DOES NOT COMPLY WITH SECTION 1210.2 OF
 THE BLDG CODE REQUIRING THE WALL TO HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE. PAINT IS NOT A HARD
 SURFACE. PLEASE INDICATE WHAT MATERIAL WILL BE
 PAINTED.
  
 3. SHT A3.1.1 ADA REQUIREMENTS. PLEASE SHOW COMPLIANCE
 WITH SECTION 11-4.19.4 EXPOSED PIPES & SURFACES, AND
 SHOW THE TURNING AREA REQUIRED IN THE TOILET ROOMS AS
 REQUIRED IN SECTION 11-4.22.3.
  
 4. SHOW THE CLEAR FLOOR SPACE FOR THE BREAK ROOM SINK
 AS REQUIRED IN SECTION 11-4.24.5.
  
 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 6.SHT P2.1.1 THE SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN IN THE TOILET ROOMS. THE RISER
 SHOWS LAV, W/C, W/C & LAV, BUT THE FLOOR PLAN SHOWS
 W/C, LAV, LAV & W/C. PLEASE SUBMIT A RISER DIAGRAM THAT
 REFLECTS THE FLOOR PLAN. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved