Plan Review Notes For Permit 07110752 |
Permit Number |
07110752 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-12-14 10:30:11 | ***DENIED*** | | | | 1) SUITE IDENTIFICATION TO BE ADDED TO TITLE BLOCK. THE | | SUITE CHARACTERS SHALL BE MINIMUM (3") IN WIDTH AND | | CONTRASTING TO THE BACKGROUND PER CITY OF WEST PALM | | BEACH REQUIREMENTS. | | | | 2) PLEASE PROVIDE MINIMUM INTERIOR FINISH | | CLASSIFICATION FOR WALLS AND CEILING IN TERMS OF CLASS | | A,B ORC. PLEASE BE SPECIFIC REGARDING THIS PROJECT. | | | | 3) FIRE RATED DOORS SHALL BE REFERERED TO IN TERMS OF | | HOURS. PLEASE CORRECT ON SHT A7.1.1 | | | | 4) DUCT SMOKE DETECTORS WHERE PROVIDED ARE TO INITIATE | | A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL | | REQUIREMENTS. | | | | 5) PLEASE CLARIFY THE OCCUPANT LOAD FOR THIS SPACE | | USING THE APPROPRIATE FACTOR PER NFPA 101, SEC.7.3.1.2. | | SEE BUILDING COMMENT #8 | | | | 6) MINIMUM RATING FOR FIRE EXTINGUISHERS SHALL BE | | 2A-10B,C. | | | | 7) HOW WILL EMERGENCY ACCESS INTO TENANT SPACE AFTER | | BUSINESS HOURS BE ACCOMPLISHED? | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|