2007-12-14 10:30:11***DENIED***
  
 1) SUITE IDENTIFICATION TO BE ADDED TO TITLE BLOCK. THE
 SUITE CHARACTERS SHALL BE MINIMUM (3") IN WIDTH AND
 CONTRASTING TO THE BACKGROUND PER CITY OF WEST PALM
 BEACH REQUIREMENTS.
  
 2) PLEASE PROVIDE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING IN TERMS OF CLASS
 A,B ORC. PLEASE BE SPECIFIC REGARDING THIS PROJECT.
  
 3) FIRE RATED DOORS SHALL BE REFERERED TO IN TERMS OF
 HOURS. PLEASE CORRECT ON SHT A7.1.1
  
 4) DUCT SMOKE DETECTORS WHERE PROVIDED ARE TO INITIATE
 A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
 5) PLEASE CLARIFY THE OCCUPANT LOAD FOR THIS SPACE
 USING THE APPROPRIATE FACTOR PER NFPA 101, SEC.7.3.1.2.
 SEE BUILDING COMMENT #8
  
 6) MINIMUM RATING FOR FIRE EXTINGUISHERS SHALL BE
 2A-10B,C.
  
 7) HOW WILL EMERGENCY ACCESS INTO TENANT SPACE AFTER
 BUSINESS HOURS BE ACCOMPLISHED?
  
  