Plan Review Notes
Plan Review Notes For Permit 07110752
Permit Number 07110752
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-05 17:00:07NOTE ADDED, SPECS AND CUT SHEETS FOR UPS EQUIPMENT IS
 TO BE SUBMITTED FOR REVIEW. PLEASE BE SURE EQUIPMENT
 CONTAINS ALISTING FROM A NRTL.
 90.7, 110.3
2007-12-05 12:57:33** DENIED**
  
 1) NOTE: PLEASE SEE THE PERMIT APPLICATION AND
 SUPPORTING DOCUMENTS HAVE BEEN ROUTED TO THE ADDRESSING
 REVIEWER.
 THE PERMIT APPLICATION AS APPLIED INDICATES THE 1ST
 FLOOR HOWEVER THIS TENANT DOES NOT TAKE THE ENTIRE
 FLOOR AND WILL REQUIRE SUITE/UNIT #.
 PLEASE KNOW ONCE THIS HAS BEEN DETERMINED THE TITLE
 BLOCKS ARE TO BE REVISED INDICATING THIS ADJUSTMENT.
 FBC 106.1.2, 106.3.5.1.2, 106.5.3 ETC
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE BE SURE ALL ROOM AND AREA DESIGNATIONS
 ARE LISTED ON PLANS FOR SCOPE OF WORK BEING DONE UNDER
 THIS PERMIT APPLICATION.
 PLEASE COMPLETE ALL CIRCUITING ON PLANS FOR ALL
 ELECTRICAL AS SHOWN AND CORRELATE WITH THE PANELS.
 FOR EXAMPLE:
 PANEL SCHEDULES INDICATE * OFFICE RECEPT* AND NOT THE
 ROOM OR AREA SPECIFIC. FOR EXAMPLE:PLEASE SEE
 2-PUPS-10, PANEL SCHEDULE WORK ROOM AND PLANS WORK ROOM
 IS A CIRCUIT IN BREAK-ROOM 112. PLEASE SEE WORK ROOM
 WHICH IS 121 DOES NOT CALL FOR ROOM OR ARE ON PLANS.
 PLEASE ADJUST
 NEC 408.4, 310.16, 240.4
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 3) NOTE: PLEASE GO OVER ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULES FOR
 LOADS.
 PLEASE CORRELATE ALL LOADS ON PANEL SCHEDULES WITH THAT
 OF THE LOADS SET FORTH IN THE NEC FOR RECEPTACLES AT
 180VA PER YOKE.
 PLEASE CLARIFY HOW SOME ARE HIGHER OR LOWER PER
 CIRCUIT. WHAT VALUE IS BEING USED.
 PLEASE SEE NEC 220 .14/220.44.
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 4) NOTE: PLEASE KNOW THAT ELECTRICAL CONDUITS ARE FEEDS
 MAY NOT BE IN A SEPARATE BUILDING ON A SEPARATE
 PROPERTY WHICH IS FED FROM A COMPLETELY DIFFERENT
 ELECTRICAL SERVICE AND SYSTEM.225.30, 230.3, 90.4.
 PLANS NOTE THE DRIVE THRU AND TELLER AREAS WILL BE
 UNDER SEPARATE PERMIT WHICH IS OK, HOWEVER ELECTRICAL
 SYSTEMS MAY NOT BE MIXED AND CROSSED.
 ** PLEASE SEE FLORIDA STATUTES 655.962 FOR MINIMUM
 LIGHTING LEVELS REQUIRED FOR ATM/TELLER LOCATIONS. **
 THIS IS ONLY NOTED FOR INFORMATION.
  
 5) NOTE: PLEASE SEE PLANS FOR AREA/ROOM 105 AS THE
 LIGHTING FIXTURES ON PLANS ARE A HIGHER AMOUNT THAN ON
 THE LIGHTING PERFORMANCE CALCULATIONS.
 EXAMPLE: PLEASE SEE PLANS WITH 18 FIXTURES AND
 CALCULATIONS SHOW 17. APPEARS PLAN CONTAINS AN EXTRA
 MISPRINTED FIXTURE.
  
 6) NOTE: PLEASE SEE COMMENTS FROM MECHANICAL REVIEW
 WITH RESPECT TO LOADS FOR AC AND FOR OTHER TRADES FOR
 ANY ITEMS WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  