2007-12-07 08:45:15 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| |
| 1.SEE ELECTRIC COMMENTS REGARDING ADDRESSING.THIS |
| ISSUE SHOULD BE RESOLVED PRIOR TO PERMIT ISSUANCE. |
| |
| 2.SEE MECHANICAL COMMENTS, ITEM 12, REGARDING TENANT |
| BUILDOUT.THE DOR ON THIS JOB IS TO PROVIDE SHOP |
| DRAWING REVIEW STAMP (MICHAEL O ROSSIN IS ARCHITECT OF |
| RECORD, ROBERT J. MCNAMARE, PE IS STRUCTURAL ENGINEER |
| OF RECORD). |
| |
| 3.APPLICABLE CODES SHOULD INCLUDE 2007 AMENDMENTS |
| EFFECTIVE 7/1/07, SHEET A01.1. WWW.FLORIDABUILDING.ORG |
| |
| 4.ON EITHER THE FLOOR PLAN OR THE LIFE SAFETY PLAN, |
| PLEASE NOTE ALL REQUIRED FIRE RESISTANCE RATED ELEMENTS |
| AND WALLS.SEE MECHANICAL SHEET H2.1.1, AN EXHAUST FAN |
| IS SHOWN THROUGH THE WALL TO THE GARAGE AREA.ISN'T |
| THERE AN OCCUPANCY SEPARATION AT THIS WALL?SEE |
| FBC712, PENETRATIONS. |
| |
| 5.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE |
| REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5), |
| FS553.79 (2). |
| |
| 6.SHOW MANEUVERING CLEARANCE, PULL SIDE, DOOR A119, |
| FBC FIGURE 11-25. |
| |
| 7.BATHROOMS 114, 113, A2.1.4 SHOWS VWC AS WALL |
| FINISH.THIS WAS NOT INCLUDED IN THE SCHEDULE OF |
| FINISHES; PLEASE SEE FBC1210.2 REGARDING WALL FINISHES |
| (BATHROOM, NONABSORBENT SURFACE REQUIRED).ALSO NOTE |
| THAT THE DETAIL ROOM NUMBERS DO NOT CORRELATE (SHOWN AS |
| 113/112), SHEET A3.1.1. |
| |
| 8.THE FLOOR PLAN AND BREAK ROOM 112 PLAN SHOWS A |
| SINK, BUT THE DETAILS 111 (NOTE THAT THE ROOM |
| DESIGNATION NUMBER DOES NOT CORRELATE WITH FLOOR PLAN) |
| DO NOT SHOW A SINK, A3.1.1, AND CABINET DOORS ARE |
| SHOWN.SEE FBC11-4.24.3, 11-4.24.5, KNEE CLEARANCE. |