Plan Review Notes
Plan Review Notes For Permit 07110750
Permit Number 07110750
Review Stop P
Sequence Number 3
Notes
Date Text
2008-01-07 15:03:22PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 3RD TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE STILL
 REQUIRED FOR THE PLUMBING PLAN REVIEW TO MEET CODE
 COMPLIANCE.
 NOTE: NO TRANSMITTAL LETTER WAS SUBMITTED FOR COMMENT
 RESPONSE AS ASKED FOR IN PREVIOUS PLAN REVIEWS.
  
 1. ***NO COMMENT RESPONSE, AND COMMENT NOT
 ADDRESSED***
 PLANS SUBMITTED IN PENCIL ARE UNACCEPTABLE. PER *106.
 CONSTRUCTION DOCUMENTS. *** BOTH SETS OF RESUBMITTED
 PLANS ARE IN PENCIL.
  
 2. ***NO COMMENT RESPONSE, AND COMMENT NOT
 ADDRESSED***
 NOTE: TWO SETS OF FLOOR PLANS REQUIRED, ONE SET OF
 FLOOR PLANS INDICATING THE EXISTING FLOOR PLAN LAYOUT
 AND THE OTHER SET INDICATING THE PROPOSED FLOOR PLAN
 LAYOUT. CLEARLY INDICATE ON THE PLANS EXISTING AND
 PROPOSED FIXTURES.
 PER FBC-2004, CHAPTER 1, SECTION *106.1.3, QUALITY OF
 BUILDING PLANS: BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR
 OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT.
 **NOTE: THIS IS A BUSSINESS, THE MINIMUM REQUIRED
 FIXTURES ARE AS FOLLOWS PER TABLE *403.1:
  
 **WATER CLOSETS = 1 PER 25 FOR THE FIRST 50 AND 1 PER
 50 FOR THE REMAINDER EXCEEDING 50.
  
 **LAVATORIES = 1 PER 40 FOR THE FIRST 50 AND 1 PER 80
 FOR THE REMAINDER EXCEEDING 50.
  
 **DRINKING FOUNTAIN = 1 PER 100.
  
 ***THERE WERE NO EXISTING OR PROPOSED FLOOR PLANS IN
 THE RESUBMITTAL AS ASKED FOR. THE REQUIRED DRINKING
 FOUNTAIN SHALL BE ACCESSIBLE. THE FOLLOWING IS REQUIRED
 FOR THE DRINKING FOUNTAIN AND NEEDS TO BE INDICATED ON
 AN ELEVATION DETAIL AS ASKED FOR IN PREVIOUS PLAN
 REVIEWS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 3. OK, COMMENT ADDRESSED, HOWEVER THE RESUBMITTED
 PLANS ARE IN PENCIL, REFERENCE COMMENT #1.
  
 4. ***NO COMMENT RESPONSE, AND COMMENT NOT
 ADDRESSED***
 SHAMPOO SINKS MUST DRAIN DOWNSTREAM OF THE WET VENTED
 BATHROOM. PER *909.1, WET VENT PERMITTED.
  
 5. OK, COMMENT ADDRESSED, HOWEVER THE RESUBMITTED
 PLANS ARE IN PENCIL, REFERENCE COMMENT #1.
  
 6. ***NO COMMENT RESPONSE, AND COMMENT PARTIALLY
 ADDRESSED, HOWEVER THE RESUBMITTED PLANS ARE IN PENCIL,
 REFERENCE COMMENT #1***
 PER FBC-2004 CHAPTER 1, SECTION *106.3.5.1.3, PLUMBING:
 AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS REQUIRED
 FOR THE PROPOSED WORK FOR BOTH THE HOT AND COLD WATER
 INDICATING THE PIPE SIZES, VALVE LOCATIONS, LOCATION OF
 THE WATER SUPPLY LINE WITH BACKFLOW PREVENTER **608,
 THERMAL EXPANSION CONTROL FOR THE WATER HEATER **607.3,
 AND LOCATION OF THE WATER-HAMMER ARRESTORS WHERE QUICK
 CLOSING VALVES ARE UTILIZED (EXAMPLES=WASHING MACHINES,
 DISHWASHERS, ICE MAKERS) **604.9.
 **NOTE: PLEASE INDICATE THE SIZE AND TYPE OF WATER
 HEATER (GAS OR ELECTRIC) PER *501.1 SCOPE. IF SHAMPOO
 SINKS HAVE SPRAY HOSES INDICATE PROTECTION PER SECTION
 *608, PROTECTION OF POTABLE WATER SUPPLY.
  
 ***THE FOLLOWING INFORMATION IS STILL REQUIRED:
  
 A} CLEARLY INDICATE THE TYPE OF WATER HEATER (GAS OR
 ELECTRIC) BEING USED,PER 501.1 SCOPE.
  
 B} CLEARLY INDICATE THAT THE POTABLE WATER SUPPLY TO
 THE SHAMPOO SINKS WITH SPRAY HOSES WILL BE PROTECTED
 PER *608, PROTECTION OF POTABLE WATER.
  
 C} THE BACKFLOW PREVENTER ON THE WATER RISER DIAGRAM
 IS BEING WRONGLY IDENTIFIED AS A "BACKWATER VALVE".
 PLEASE REFERENCE THE FOLLOWING DEFINITIONS TO CLARIFY
 THIS.
  
 BACKWATER VALVE. A DEVICE OR VALVE INSTALLED IN THE
 BUILDING DRAIN OR SEWER PIPE WHERE A SEWER IS SUBJECT
 TO BACKFLOW, AND WHICH PREVENTS DRAINAGE OR WASTE FROM
 BACKING UP INTO A LOW LEVEL OR FIXTURES AND CAUSING A
 FLOODING CONDITION.
  
 BACKFLOW PREVENTER. A DEVICE OR MEANS TO PREVENT
 BACKFLOW.
  
 BACKFLOW . PRESSURE CREATED BY ANY MEANS IN THE WATER
 DISTRIBUTION SYSTEM, WHICH BY BEING IN EXCESS OF THE
 PRESSURE IN THE WATER SUPPLY MAINS CAUSES A POTENTIAL
 BACKFLOW CONDITION.
  
 8. ***NO COMMENT RESPONSE, AND COMMENT PARTIALLY
 ADDRESSED***
 FBC-2004 CHAPTER 1,SECTION *106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 ***THE RESUBMITTED DRAWINGS ARE SIGNED AND DATED
 HOWEVER THE PRINTED NAME IS NOT IDICATED AND THE
 RESUBMITTED DRAWINGS AND SIGNATURES ARE IN PENCIL.
 REFERENCE COMMENT #1.
  
 9. ***NO COMMENT RESPONSE, AND COMMENT NOT
 ADDRESSED***
 CLEARLY INDICATE THE LOCATION OF THE PROPOSED WATER
 HEATER ON THE PROPOSED FLOOR PLAN. PER *501.1 SCOPE,
 AND 601.1 SCOPE.
 ***NOTE: THE RESUBMITTAL DOES NOT HAVE THE PROPOSED
 FLOOR PLAN AS ASKED FOR IN PREVIOUS PLAN REVIEWS.
  
 10. ***OK, HOWEVER THE RESUBMITTED PLANS ARE IN
 PENCIL, REFERENCE COMMENT #1***
  
 **THE FOLLOWING ARE NEW COMMENTS**
  
 11. THE VALUE OF THE PROPOSED WORK NEEDS TO BE
 INCREASED WITH THE ADDITION OF THE DRINKING FOUNTAIN.
 PER SECTION
 *108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
  
 **PROVIDE A SIGNED CONTRACT OF THE PROPOSED WORK
 INDICATING THE INCREASED VALUE.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER