2007-12-19 14:37:07PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE STILL
 REQUIRED FOR PLUMBING PLAN REVIEW TO MEET CODE
 COMPLIANCE.
 NOTE: NO TRANSMITTAL LETTER WAS SUBMITTED FOR COMMENT
 RESPONSE AS ASKED FOR.
  
 1. "OK"
  
 2.**NO COMMENT RESPONSE**
 NOTE: TWO SETS OF FLOOR PLANS REQUIRED, ONE SET OF
 FLOOR PLANS INDICATING THE EXISTING FLOOR PLAN LAYOUT
 AND THE OTHER SET INDICATING THE PROPOSED FLOOR PLAN
 LAYOUT. CLEARLY INDICATE ON THE PLANS EXISTING AND
 PROPOSED FIXTURES.
 PER FBC-2004, CHAPTER 1, SECTION *106.1.3, QUALITY OF
 BUILDING PLANS: BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR
 OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT.
 **NOTE: IF THIS IS A BUSSINESS MINIMUM REQUIRED
 FIXTURES ARE AS FOLLOWS PER TABLE *403.1:
  
 **WATER CLOSETS = 1 PER 25 FOR THE FIRST 50 AND 1 PER
 50 FOR THE REMAINDER EXCEEDING 50.
  
 **LAVATORIES = 1 PER 40 FOR THE FIRST 50 AND 1 PER 80
 FOR THE REMAINDER EXCEEDING 50.
  
 **DRINKING FOUNTAIN = 1 PER 100.
  
 **THE RESUBMITTED PLANS ARE NOT INDICATING A DRINKING
 FOUNTAIN ON THE EXISTING FLOOR PLAN AND A PROPOSED
 FLOOR PLAN WAS NOT SUBMITTED AS ASKED FOR. A DRINKING
 FOUNTAIN IS REQUIRED AND SHALL BE ACCESSIBLE PER THE
 FOLLOWING.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELAVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 3. OK
  
 4. **NO COMMENT RESPONSE**
 SHAMPOO SINKS MUST DRAIN DOWNSTREAM OF THE WET VENTED
 BATHROOM. PER *909.1, WET VENT PERMITTED.
  
 **NOTE: THE RESUBMITTED SANITARY ISOMETRIC RISER
 DIAGRAM IS STILL NOT COMPLIANT PER *909.1, WET VENT
 PERMITTED.
  
 5. OK
  
 6.**NO COMMENT RESPONSE**
 PER FBC-2004 CHAPTER 1, SECTION *106.3.5.1.3, PLUMBING:
 AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS REQUIRED
 FOR THE PROPOSED WORK FOR BOTH THE HOT AND COLD WATER
 INDICATING THE PIPE SIZES, VALVE LOCATIONS, LOCATION OF
 THE WATER SUPPLY LINE WITH BACKFLOW PREVENTER **608,
 THERMAL EXPANSION CONTROL FOR THE WATER HEATER **607.3,
 AND LOCATION OF THE WATER-HAMMER ARRESTORS WHERE QUICK
 CLOSING VALVES ARE UTILIZED (EXAMPLES=WASHING MACHINES,
 DISHWASHERS, ICE MAKERS) **604.9.
 **NOTE: PLEASE INDICATE THE SIZE AND TYPE OF WATER
 HEATER (GAS OR ELECTRIC) PER *501.1 SCOPE. IF SHAMPOO
 SINKS HAVE SPRAY HOSES INDICATE PROTECTION PER SECTION
 *608, PROTECTION OF POTABLE WATER SUPPLY.
  
 **NOTE: THE RESUBMITTED PLANS ARE NOT INDICATING THE
 WATER SUPPLY LINE WITH BACKFLOW PREVENTER **608,
 THERMAL EXPANSION CONTROL FOR THE WATER HEATER**607.3,
 AND THERE IS NO INDICATION ON THE RESUBMITTED PLANS IF
 SHAMPOO SINKS HAVE SPRAY HOSES AND AN INDICATION OF
 PROTECTION IF THEY DO, PER SECTION **608, PROTECTION OF
 POTABLE WATER SUPPLY.
  
 8.**NO COMMENT RESPONSE**
 FBC-2004 CHAPTER 1,SECTION *106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **NOTE: THE RESUBMITTED EXISTING FLOOR PLAN IS NOT
 SIGNED OR DATED AND ALL OF THE DRAWINGS DO NOT HAVE THE
 PRINTED NAME.
  
 **THE FOLLOWING ARE NEW COMMENTS**
  
 9. CLEARLY INDICATE THE LOCATION OF THE PROPOSED WATER
 HEATER ON THE PROPOSED FLOOR PLAN. PER *606.1, SCOPE
 AND 106.1.2, ADDITIONAL DATA.
  
 10. CLEARLY INDICATE THE WATER HEATER RELIEF VALVE
 DISCHARGE LOCATION PER THE FOLLOWING.
 504.6.1 DISCHARGE.
 THE RELIEF VALVE SHALL DISCHARGE FULL SIZE TO A SAFE
 PLACE OF DISPOSAL SUCH AS THE FLOOR, WATER HEATER PAN,
 OUTSIDE THE BUILDING OR AN INDIRECT WASTE RECEPTOR. THE
 DISCHARGE PIPE SHALL NOT HAVE ANY TRAPPED SECTIONS AND
 SHALL HAVE A VISIBLE AIR GAP OR AIR GAP FITTING LOCATED
 IN THE SAME ROOM AS THE WATER HEATER. THE DISCHARGE
 SHALL BE INSTALLED IN A MANNER THAT DOES NOT CAUSE
 PERSONAL INJURY TO OCCUPANTS IN THE IMMEDIATE AREA OR
 STRUCTURAL DAMAGE
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  