Date |
Text |
2007-12-19 14:37:07 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS |
| TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| DENIED 2ND TIME: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE STILL |
| REQUIRED FOR PLUMBING PLAN REVIEW TO MEET CODE |
| COMPLIANCE. |
| NOTE: NO TRANSMITTAL LETTER WAS SUBMITTED FOR COMMENT |
| RESPONSE AS ASKED FOR. |
| |
| 1. "OK" |
| |
| 2.**NO COMMENT RESPONSE** |
| NOTE: TWO SETS OF FLOOR PLANS REQUIRED, ONE SET OF |
| FLOOR PLANS INDICATING THE EXISTING FLOOR PLAN LAYOUT |
| AND THE OTHER SET INDICATING THE PROPOSED FLOOR PLAN |
| LAYOUT. CLEARLY INDICATE ON THE PLANS EXISTING AND |
| PROPOSED FIXTURES. |
| PER FBC-2004, CHAPTER 1, SECTION *106.1.3, QUALITY OF |
| BUILDING PLANS: BUILDING PLANS SHALL BE DRAWN TO A |
| MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR |
| OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY |
| ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR |
| PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY |
| MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS |
| MANAGEMENT. |
| **NOTE: IF THIS IS A BUSSINESS MINIMUM REQUIRED |
| FIXTURES ARE AS FOLLOWS PER TABLE *403.1: |
| |
| **WATER CLOSETS = 1 PER 25 FOR THE FIRST 50 AND 1 PER |
| 50 FOR THE REMAINDER EXCEEDING 50. |
| |
| **LAVATORIES = 1 PER 40 FOR THE FIRST 50 AND 1 PER 80 |
| FOR THE REMAINDER EXCEEDING 50. |
| |
| **DRINKING FOUNTAIN = 1 PER 100. |
| |
| **THE RESUBMITTED PLANS ARE NOT INDICATING A DRINKING |
| FOUNTAIN ON THE EXISTING FLOOR PLAN AND A PROPOSED |
| FLOOR PLAN WAS NOT SUBMITTED AS ASKED FOR. A DRINKING |
| FOUNTAIN IS REQUIRED AND SHALL BE ACCESSIBLE PER THE |
| FOLLOWING. |
| |
| **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS |
| (ELAVATION DETAIL REQUIRED WITH THE FOLLOWING |
| INFORMATION) |
| 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET |
| MAXIMUM. |
| 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN |
| TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT |
| OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN |
| ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3" |
| OF THE FRONT OF FOUNTAIN. |
| 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE |
| MOUNTED NEAR FRONT EDGE. |
| 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR |
| SPACE. |
| 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). |
| |
| 3. OK |
| |
| 4. **NO COMMENT RESPONSE** |
| SHAMPOO SINKS MUST DRAIN DOWNSTREAM OF THE WET VENTED |
| BATHROOM. PER *909.1, WET VENT PERMITTED. |
| |
| **NOTE: THE RESUBMITTED SANITARY ISOMETRIC RISER |
| DIAGRAM IS STILL NOT COMPLIANT PER *909.1, WET VENT |
| PERMITTED. |
| |
| 5. OK |
| |
| 6.**NO COMMENT RESPONSE** |
| PER FBC-2004 CHAPTER 1, SECTION *106.3.5.1.3, PLUMBING: |
| AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS REQUIRED |
| FOR THE PROPOSED WORK FOR BOTH THE HOT AND COLD WATER |
| INDICATING THE PIPE SIZES, VALVE LOCATIONS, LOCATION OF |
| THE WATER SUPPLY LINE WITH BACKFLOW PREVENTER **608, |
| THERMAL EXPANSION CONTROL FOR THE WATER HEATER **607.3, |
| AND LOCATION OF THE WATER-HAMMER ARRESTORS WHERE QUICK |
| CLOSING VALVES ARE UTILIZED (EXAMPLES=WASHING MACHINES, |
| DISHWASHERS, ICE MAKERS) **604.9. |
| **NOTE: PLEASE INDICATE THE SIZE AND TYPE OF WATER |
| HEATER (GAS OR ELECTRIC) PER *501.1 SCOPE. IF SHAMPOO |
| SINKS HAVE SPRAY HOSES INDICATE PROTECTION PER SECTION |
| *608, PROTECTION OF POTABLE WATER SUPPLY. |
| |
| **NOTE: THE RESUBMITTED PLANS ARE NOT INDICATING THE |
| WATER SUPPLY LINE WITH BACKFLOW PREVENTER **608, |
| THERMAL EXPANSION CONTROL FOR THE WATER HEATER**607.3, |
| AND THERE IS NO INDICATION ON THE RESUBMITTED PLANS IF |
| SHAMPOO SINKS HAVE SPRAY HOSES AND AN INDICATION OF |
| PROTECTION IF THEY DO, PER SECTION **608, PROTECTION OF |
| POTABLE WATER SUPPLY. |
| |
| 8.**NO COMMENT RESPONSE** |
| FBC-2004 CHAPTER 1,SECTION *106.3.4.3: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| **NOTE: THE RESUBMITTED EXISTING FLOOR PLAN IS NOT |
| SIGNED OR DATED AND ALL OF THE DRAWINGS DO NOT HAVE THE |
| PRINTED NAME. |
| |
| **THE FOLLOWING ARE NEW COMMENTS** |
| |
| 9. CLEARLY INDICATE THE LOCATION OF THE PROPOSED WATER |
| HEATER ON THE PROPOSED FLOOR PLAN. PER *606.1, SCOPE |
| AND 106.1.2, ADDITIONAL DATA. |
| |
| 10. CLEARLY INDICATE THE WATER HEATER RELIEF VALVE |
| DISCHARGE LOCATION PER THE FOLLOWING. |
| 504.6.1 DISCHARGE. |
| THE RELIEF VALVE SHALL DISCHARGE FULL SIZE TO A SAFE |
| PLACE OF DISPOSAL SUCH AS THE FLOOR, WATER HEATER PAN, |
| OUTSIDE THE BUILDING OR AN INDIRECT WASTE RECEPTOR. THE |
| DISCHARGE PIPE SHALL NOT HAVE ANY TRAPPED SECTIONS AND |
| SHALL HAVE A VISIBLE AIR GAP OR AIR GAP FITTING LOCATED |
| IN THE SAME ROOM AS THE WATER HEATER. THE DISCHARGE |
| SHALL BE INSTALLED IN A MANNER THAT DOES NOT CAUSE |
| PERSONAL INJURY TO OCCUPANTS IN THE IMMEDIATE AREA OR |
| STRUCTURAL DAMAGE |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| EXAMINER FOR REFERENCE FOR THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |