2007-12-10 13:07:23 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS |
| TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. PLANS SUBMITTED IN PENCIL ARE UNACCEPTABLE. PER |
| *106. CONSTRUCTION DOCUMENTS. **ONE SET OF PLANS IS IN |
| PENCIL. |
| |
| 2. NOTE: TWO SETS OF FLOOR PLANS REQUIRED, ONE SET OF |
| FLOOR PLANS INDICATING THE EXISTING FLOOR PLAN LAYOUT |
| AND THE OTHER SET INDICATING THE PROPOSED FLOOR PLAN |
| LAYOUT. CLEARLY INDICATE ON THE PLANS EXISTING AND |
| PROPOSED FIXTURES. |
| PER FBC-2004, CHAPTER 1, SECTION *106.1.3, QUALITY OF |
| BUILDING PLANS: BUILDING PLANS SHALL BE DRAWN TO A |
| MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR |
| OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY |
| ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR |
| PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY |
| MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS |
| MANAGEMENT. |
| **NOTE: IF THIS IS A BUSSINESS MINIMUM REQUIRED |
| FIXTURES ARE AS FOLLOWS PER TABLE *403.1: |
| |
| **WATER CLOSETS = 1 PER 25 FOR THE FIRST 50 AND 1 PER |
| 50 FOR THE REMAINDER EXCEEDING 50. |
| |
| **LAVATORIES = 1 PER 40 FOR THE FIRST 50 AND 1 PER 80 |
| FOR THE REMAINDER EXCEEDING 50. |
| |
| **DRINKING FOUNTAIN = 1 PER 100. |
| |
| 3. NOTE: PLEASE CORRELATE THE RESUBMITTED PLANS WITH |
| THE PERMIT APPLICATION. PERMIT APPLICATION STATES |
| INSTALLING THREE (3) SHAMPOO SINKS HOWEVER THE PLANS |
| ARE INDICATING LAVS. PER *106.1.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 4. SHAMPOO SINKS MUST DRAIN DOWNSTREAM OF THE WET |
| VENTED BATHROOM. PER *909.1, WET VENT PERMITTED. |
| |
| 5. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3, |
| COMMERCIAL BUILDINGS PLUMBING: PLEASE SUBMIT A PLUMBING |
| SANITARY ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE, |
| VENTS, TRAPS AND SIZES WITH CLEANOUT LOCATIONS. **THE |
| SUBMITTED SANITARY RISER DIAGRAM IS NOT SIZED, PLEASE |
| COMPLY ON THE RESUBMITTAL. |
| |
| 6. PER FBC-2004 CHAPTER 1, SECTION *106.3.5.1.3, |
| PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS |
| REQUIRED FOR THE PROPOSED WORK FOR BOTH THE HOT AND |
| COLD WATER INDICATING THE PIPE SIZES, VALVE LOCATIONS, |
| LOCATION OF THE WATER SUPPLY LINE WITH BACKFLOW |
| PREVENTER **608, THERMAL EXPANSION CONTROL FOR THE |
| WATER HEATER **607.3, AND LOCATION OF THE WATER-HAMMER |
| ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED |
| (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS) |
| **604.9. |
| **NOTE: PLEASE INDICATE THE SIZE AND TYPE OF WATER |
| HEATER (GAS OR ELECTRIC) PER *501.1 SCOPE. IF SHAMPOO |
| SINKS HAVE SPRAY HOSES INDICATE PROTECTION PER SECTION |
| *608, PROTECTION OF POTABLE WATER SUPPLY. |
| |
| 8. FBC-2004 CHAPTER 1,SECTION *106.3.4.3: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| EXAMINER FOR REFERENCE FOR THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |