Plan Review Notes
Plan Review Notes For Permit 07110750
Permit Number 07110750
Review Stop P
Sequence Number 1
Notes
Date Text
2007-12-10 13:07:23PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLANS SUBMITTED IN PENCIL ARE UNACCEPTABLE. PER
 *106. CONSTRUCTION DOCUMENTS. **ONE SET OF PLANS IS IN
 PENCIL.
  
 2. NOTE: TWO SETS OF FLOOR PLANS REQUIRED, ONE SET OF
 FLOOR PLANS INDICATING THE EXISTING FLOOR PLAN LAYOUT
 AND THE OTHER SET INDICATING THE PROPOSED FLOOR PLAN
 LAYOUT. CLEARLY INDICATE ON THE PLANS EXISTING AND
 PROPOSED FIXTURES.
 PER FBC-2004, CHAPTER 1, SECTION *106.1.3, QUALITY OF
 BUILDING PLANS: BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR
 OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT.
 **NOTE: IF THIS IS A BUSSINESS MINIMUM REQUIRED
 FIXTURES ARE AS FOLLOWS PER TABLE *403.1:
  
 **WATER CLOSETS = 1 PER 25 FOR THE FIRST 50 AND 1 PER
 50 FOR THE REMAINDER EXCEEDING 50.
  
 **LAVATORIES = 1 PER 40 FOR THE FIRST 50 AND 1 PER 80
 FOR THE REMAINDER EXCEEDING 50.
  
 **DRINKING FOUNTAIN = 1 PER 100.
  
 3. NOTE: PLEASE CORRELATE THE RESUBMITTED PLANS WITH
 THE PERMIT APPLICATION. PERMIT APPLICATION STATES
 INSTALLING THREE (3) SHAMPOO SINKS HOWEVER THE PLANS
 ARE INDICATING LAVS. PER *106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. SHAMPOO SINKS MUST DRAIN DOWNSTREAM OF THE WET
 VENTED BATHROOM. PER *909.1, WET VENT PERMITTED.
  
 5. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 COMMERCIAL BUILDINGS PLUMBING: PLEASE SUBMIT A PLUMBING
 SANITARY ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE,
 VENTS, TRAPS AND SIZES WITH CLEANOUT LOCATIONS. **THE
 SUBMITTED SANITARY RISER DIAGRAM IS NOT SIZED, PLEASE
 COMPLY ON THE RESUBMITTAL.
  
 6. PER FBC-2004 CHAPTER 1, SECTION *106.3.5.1.3,
 PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED WORK FOR BOTH THE HOT AND
 COLD WATER INDICATING THE PIPE SIZES, VALVE LOCATIONS,
 LOCATION OF THE WATER SUPPLY LINE WITH BACKFLOW
 PREVENTER **608, THERMAL EXPANSION CONTROL FOR THE
 WATER HEATER **607.3, AND LOCATION OF THE WATER-HAMMER
 ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED
 (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS)
 **604.9.
 **NOTE: PLEASE INDICATE THE SIZE AND TYPE OF WATER
 HEATER (GAS OR ELECTRIC) PER *501.1 SCOPE. IF SHAMPOO
 SINKS HAVE SPRAY HOSES INDICATE PROTECTION PER SECTION
 *608, PROTECTION OF POTABLE WATER SUPPLY.
  
 8. FBC-2004 CHAPTER 1,SECTION *106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731