Plan Review Notes
Plan Review Notes For Permit 07110731
Permit Number 07110731
Review Stop B
Sequence Number 3
Notes
Date Text
2008-11-13 16:12:56900 BRANDYWINE RD
 UNITED METHODIST CHURCH
 NOV.13,2008
  
  
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07110731
 ADD: 900 BRANDYWINE RD
 CONT: HEDRICK BROTHERS
 TEL: (561)281-7530
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION:
  
 ENERGY CALCULATIONS:
  
 1) IN THE INPUT DATA REPORT, FLOORS, HAVE TAKEN A VALUE
 OF 5.73 FOR THE TOTAL AREA OF THE BUILDING. FOR
 CONCRETE FLOOR, IN ELECTRIC ROOMS, MECHANICAL, JANITORS
 COLOSETS. THE SAME VALUE FOR CARPET AND PADDING ALSO
 WAS TAKEN FOR CERAMIC TILE FLOORS, THE ENERGY CODE
 APPENDIX-B 2.5.2 FOR MASS FLOORS. PLEASE REVIEW U-
 FACTORS IF THE INSULATION IS NOT CONTINUOUS.
  
 THIS ITEM PLUS THE MECHANICAL REVIEW COMMENT RELATED TO
 THE ENRGY CODE WILL HAVE AN EFFECT ON THE OUTCOME OF
 THE BUILDING END USE SCORE OF 99.44.
  
 BOTH THE MECHANICAL AND BUILDING REVIEWERS WILL ACCEPT
 NEW ENERGY CALCULATION FOR THIS REVIEW.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.