Plan Review Notes For Permit 07110731 |
Permit Number |
07110731 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-06-12 11:13:37 | ***DENIED*** | | | | MOST OF THE COMMENTS HAVE BEEN ADDRESSED. PLEASE SEE | | THE FOLLOWING COMMENT NUMBERS TO CORRESPOND WITH THE | | FIRST FIRE REVIEW: | | | | 05. NOTE TO READ: ELECTRONIC SWITCHES SHALL BE REQUIRED | | ON CONTROL VALVES. ADD NOTE REFERENCING CHAIN AND LOCK | | PER LOCAL REQUIREMENTS IN ADDITION TO ELECTRONIC | | SUPERVISION. | | | | 08. OCCUPANT LOAD SIGNS REQUIRED FOR ASSEMBLY AREAS NOT | | HAVING FIXED SEATING. SIGNS MAY BE OBTAINED FROM BUREAU | | OF FIRE PREVENTION, (561) 804-4756. | | | | 13. NFPA 101, 2003 EDITION SEC. 12.3.3.4 REQUIRES | | INTERIOR FINISH OF CLASS A OR CLASS B FOR SCREENS ON | | WHICH PICTURES ARE PROJECTED. | | | | 15. OK FOUND ON DOOR SCHEDULE. | | | | 17. PLEASE INDICATE THE SHEET NUMBER THAT REFERENCES | | INFORMATION REGARDING KNOX LOCKING CAPS FOR FIRE | | DEPARTMENT CONNECTION. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|