Plan Review Notes
Plan Review Notes For Permit 07110731
Permit Number 07110731
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2008-06-12 11:13:37***DENIED***
  
 MOST OF THE COMMENTS HAVE BEEN ADDRESSED. PLEASE SEE
 THE FOLLOWING COMMENT NUMBERS TO CORRESPOND WITH THE
 FIRST FIRE REVIEW:
  
 05. NOTE TO READ: ELECTRONIC SWITCHES SHALL BE REQUIRED
 ON CONTROL VALVES. ADD NOTE REFERENCING CHAIN AND LOCK
 PER LOCAL REQUIREMENTS IN ADDITION TO ELECTRONIC
 SUPERVISION.
  
 08. OCCUPANT LOAD SIGNS REQUIRED FOR ASSEMBLY AREAS NOT
 HAVING FIXED SEATING. SIGNS MAY BE OBTAINED FROM BUREAU
 OF FIRE PREVENTION, (561) 804-4756.
  
 13. NFPA 101, 2003 EDITION SEC. 12.3.3.4 REQUIRES
 INTERIOR FINISH OF CLASS A OR CLASS B FOR SCREENS ON
 WHICH PICTURES ARE PROJECTED.
  
 15. OK FOUND ON DOOR SCHEDULE.
  
 17. PLEASE INDICATE THE SHEET NUMBER THAT REFERENCES
 INFORMATION REGARDING KNOX LOCKING CAPS FOR FIRE
 DEPARTMENT CONNECTION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756