Plan Review Notes
Plan Review Notes For Permit 07110731
Permit Number 07110731
Review Stop B
Sequence Number 2
Notes
Date Text
2008-06-05 07:34:39900 BRANDYWINE RD
 UNITED METHODIST CHURCH
 DEC.28, 2007
  
  
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07110731
 ADD: 900 BRANDYWINE RD
 CONT: HEDRICK BROTHERS
 TEL: (561)281-7530
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1-8 COMPLIED
  
 9) 2ND REQUEST, PLEASE SEE A-2.1.1 & A2.1.3 BOTH PLANS
 INDICATE THE USE OF RAMPS 3/4" /12". SEE DEFINITION OF
 RAMP 11-3 A WALKING SURFACE WHICH HAS A RUNNING SLOPE
 GREATER THAN 1:20. SEE 11-4.8.5 WHERE HANDRAILS WILL BE
 REQUIRED, HORIZONTAL PROJECTIONS GRATER THAN 72". THE
 RESPONCE INDICATED THAT THE CITY IS IN RECEIPT OF A
 LETTER THAT WAS WRITTEN BY THE BOARD OF THE UNITED
 METHODIST OF THE PALM BEACHES, IN A MEETING BETWEEN
 ARCHITECT PAUL TWITTY AND ROBERT BROWN THIS WAS AGREED
 UPON BUT TO THIS DATE THIS REQUIREMENT HAS NOT BEEN
 MET.
  
 10) 2ND REQUEST, A-211 & A-2.1.3 BOTH INDICATE THE USE
 OF AN ELECTRIC LIFT, PLEASE PROVIDE CODE COMPLIANCE
 INFORMATION ON THE LIFT, 11-4.1.3 EXCEPTION# 4. THE
 MANUFACTURERS MUST MEET THE REQUIREMENTS OF ASME A17.1
 AS OF 11-4.11.
  
 11-15) COMPLIED.
  
 16) 2ND REQUEST, ROOF HATCHES TO DATE THERE IS ONLY ONE
 ROOF HATCH THAT HAS SAUGHT AN APPROVAL WITHIN THE CITY
 A COPY OF THAT APPROVAL WAS PROVIDED TO YOUR OFFICE
 EARLIER. THIS IS A REQUIREMENT THAT WILL NEED TO BE MET
 BEFORE ISSUANCE OF THE PLAN. RULE 9B-72.
  
 17-23) COMPLIED.
  
 24) SEMI-COMPLIED, 3-HOUR FUSIBLE LINK DOOR APPROVALS
 FOR FIRE RATING HAVE BEEN SUBMITTED TO THIS OFFICE,
 DOOR D-173 IS OPEN TO AN EXTERIOR CORRIDOR WHICH WILL
 ALSO BE EXPOSED TO WIND AND WILL NEED A TEST REPORT
 ALSO FOR WIND PRESSURES. SINCE THERE IS NO GLAZING IN
 THIS DOOR IT WILL ONLY NEED TO BE TESTED FOR WIND
 RESISTANCE AND NEED TO MEET THE REQUIREMENTS OF
 1714.5.3.1.
  
 25) SEMI COMPLIED IMPACT RATED GLASS AND FRAMES A-7.3.3
 THE DALLE DE VERRE GLASS ALUMINUM WINDOWS PLEASE
 CLARIFY IF THE DALLE DE VERRE IS THE MANUFACTURER OF
 THE WHOLE WINDOW UNIT INCLUSIVE OF WINDOW FRAME OR IF
 THEY ARE RESPONSIBLE FOR A STAIN GLASS INSET PANEL
 WHICH WILL BE SANDWICHED WITHIN A WINDOW AND FRAME UNIT
 THAT HAS BEEN TESTED FOR LARGE MISSILE IMPACT TESTING
 AND RECEIVED A ACCEPTANCE REPORT. ON BOTH THE FLORIDA
 WEBSITE AND THE MIAMI-DADE WEBSITE DALLE DE VERRE GLASS
 DOE NOT INDICATE THAT ANY OF THEIR PRODUCTS HAVE BEEN
 TESTED TO COMPLY WITH 1609.1.4.
  
 26 ) 2ND REQUEST, FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
  
 A) GLAZED OPENINGS, FIXED
 YKKAP YHS 50 TU NOA 05-0317.03 IS MISSING THE FLORIDA
 APPROVAL, THERE ARE (3) APRROVALS THIS WINDOW CAN FALL
 UNDER, 2ND NO SHOP DRAWING STAMP OF APPROVAL FROM THE
 DESIGN TEAMPLEASE
 AFFIX THIS STAMP TO THE FRONT OF THE DOCUMENT, PLACED
 ON THE BACK DOES NOT TIE IT TO THE DOCUMENT WHEN
 STAMPED.SHEETS 3-5 THE TOP OF THE COLUMN HEADINGS ARE
 CUT OFF AND NO IDENTIFICATION OF
 THESE HEADINGS ARE NOT KNOWN.
  
 SHEET A-7.3.1 WINDOW TYPE J A SEMI CIRCULAR WINDOW IS
 MISSING THERE APPROVA NO SUBMITTED.
  
 YKK YHC-300 O/G CURTAIN WALL NOA 06-0306.02 IS MISSING
 THE FLORIDA APPROVAL, AND NO SHOP DRAWING STAMP OF
 APPROVAL FROM THE DESIGN TEAM, PLEASE AFFIX ON THE
 FRONT OF THE DOCUMENT.
 PLEASE IDENTIFY GLASS TYPE TO BE USED , THIS WILL
 EFFECT PRESSURE RATINGS OF GLASS.
  
 B) GLAZED OPENINGS, OPERABLE YKK YOW 225H NON-THERMAL
 ALUMINUM CASEMENT WINDOWSPLEASE NOTE THE WINDOW
 LIMITATION IN HEIGTH OF 62'" NOT THE 75.5" AS INDICATED
 ON THE PLANS. PLEASE APPLY THE DESIGN TEAMS APPROVAL ON
 THE FRONT OF THE DOCUMENT NOT THE BACK AS ON THIS
 DOCUMENTSHOWING APPROVAL.
  
 C) MULLIONS- MAY OR MAYNOT BE INCLUDED IN THE WINDOW
 PRODUCT APPROVAL WITH THE CASEMENT WINDOWS BEING A
 ISSUE THIS MAY STILL BE A CONCERN. SHEET A-7.3.1 DETAIL
 B2 INDICATES THE USE OF 2 MULLIONS FOR DOUBLE UNITS.
  
 D) EXTERIOR GLAZED DOORS
 YKK 35H SERIES ALUMINUM OUTSWING ENTRANCE DOOR, MISSING
 THE FLORIDA COVER SHEET,
  
 E) EXTERIOR HOLLOW METAL DOORS
 DOORS 127 & 128 ARE EXTERIOR DOORS TO RESTROOMS A-7.2.1
 DOOR SCHEDULE INDICATES THESE DOORS ARE HOLLOW METAL
 DOORS BUT THE DOOR TYPE# 2 INDICATES THESE ARE WOOD
 INTERIOR DOORS.
 PAIR OF DOORS A147 EXTERIOR METAL DOORS WITH LOUVER
 PAIR OF DOORS A108 EXTERIR HOLLOW METAL DOORS
 NO PRODUCT APPROVALS WERE SUBMITTED FOR HOLLOW METAL
 DOORS
  
 NEW DOOR HEADING:
 EXTERIOR WOOD DOOR
 EXTERIOR WOOD DOORS WITH GLAZING
 IN BOTH CASES OF THE EXTERIOR WOOD DOORS SITE SPECIFIC
 REPORT WILL NEED TO BE SUPPLIED SEE ATTACHEMENT FOR
 LOCAL AND SITE SPECIFIC PRODUCT APPROVAL REPORTS
 MEERTING THE REQUIREMENTS OF
 RULE 9B-72.040PRODUCT EVALUATION AND QUALITY ASSURANCE
 FOR LOCAL APPROVAL.
 METHOD 2 (B) AN EVALUATION REPORT FROM A FLORIDA
 PROFESSIONAL ENGINEER DEVELOPED AND SIGNED AND SEALED,
 BASED UPON TESTING, OR COMPARARATIVE OR RATIONAL
 ANALYSIS, OR COMBINATION THEREOF WHICH PROVIDES
 VERIFIBLE DOCUMENTATIONINDICATING THE PRODUCT WAS
 EVALUATED TO BE IN COMPLIANCE WITH THE CODE AND THAT
 THE PRODUCT IS, FOR THE PURPOSE INTENDED, AT LEAST
 EQUIVALENT TO THAT REQUIRED BY THE CODE.
 NOTE: THE CUSTOM WOOD ENTRY DOORS WITH GLAZED OPENINGS
 WILL NOT NEED TO MEET LARGE MISSILE IMPACT RESISTANCE
 AS PER THE BUILDING OFFICIALS INTERPRETATION PHAMPHLET
 QUESTION# 15.
  
 F) EXTERIOR ROLL UP DOORS- COVERED UNDER COMMENT# 24
 REQUIRES PRODUCT APPROVAL FOR WIND
  
 G) ROOF ACCESS HATCHES- NO APPROVAL SUBMITTED
  
 H) PANEL WALL SYSTEMS : LOUVERS NO APPROVALS SUBMITTED
  
 I) PANEL WALL SYSTEMS: EFIS WALL SYSTEMS - REMOVED FROM
 PROJECT NOT REQUIRED
  
 J) ROOFING SYSTEMS BOTH FOR FLAT ROOF AND TILED SLOPED
 SYSTEMS
  
 JOHN MANSVILLE MODIFIED NOA 07-0228.04 NO FLORIDA
 APPROVAL SUBMITTED. PAGES 7-41 OF THE PRODUCT APPROVAL
 THAT WAS SUBMITTED ARE SUB-SYSTEMS, EACH OF THESE
 SUB-SYSTEMS HAVE ASSOCIATED
 WIND PRESSURES THAT MAY OR MAY NO REQUIRE ENHANCED
 FASTENING. PLEASE CIRCLE THE SUB-SYSTEM TO BE
 INSTALLED, NOTE THE ASSOCIATED PRESSURES WITH THAT
 SUB-SYSTEM IF THE PRESSURES ARE LESS THAN 89PSF FOR
 ZONES 2 AND 3 , ENHANCED FASTENING WILL BE REQUIRED.
 PLEASE LOOK AT THE HIGH LIGHTED SUB-SYSTEM PICKED TO
 SEE IF LIMITATION 7 OR 9 EXIST. LIMITATION# 7 WILL
 ALLOW ENHANCED FASTENING IN ZONES 2& 3 LIMITATION# 9
 WILL NOT ALLOW ENHANCEDFASTENING. THIS REPORT DOES
 REQUIRE A DESIGN PROFESSIONAL TO COMPLETE THE RAS 117
 CALCULATION FOR ENHANCED FASTENING.
  
 POLYFOAM - NO PRODUCT APPROVALS WERE SUBMITTED NOR
 FLORIDA COVER SHEET. THEERE ARE 4 SEPERATE FLORIDA
 APPROVALS ON THE WEBSITE. RULE 9B-72. NOT KNOWN AS TO
 WHAT PATTY SIZE WIL BE USED WITH ASSOCIATED PRESSURES.
  
 SANTAFE TILE , NO FLORIDA APPROVLA WAS SUBMITTED
  
 CENTRIA- RIB METAL WALL PANEL -NO FL APPROVAL
 SUBMITTED
  
 CLAYLITE- NO PRODUCT APPROVAL SUBMITTED, CLAY TILE
 VENTURES DOES HAVE A FL COVERSHEET.
  
 27) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 28-31) PART OF THE PRODUCT APPROVALSSEMI COMPLIED.
  
 32) NEW COMMENT:
 SHEET A-7.2.1/ DOOR SCHEDULE:
 DOOR# 113B& C REVISION INDICATES THESE DOORS ARE TO BE
 A FIRE RATED 45 MINUTE DOOR, IF THESE DOORS ARE TO BE
 CUSTOM MADE WHO WILL PROVIDE THE FIRE RATING FOR THESE
 DOORS?
 715.3 HSA TEST REQUIREMENTS PLUS THE DOOR ALSO HAS
 GLAZED OPENINGS THAT WILL NEED TO MEET THE REQUIREMENTS
 OF 715.4 FIRE-PROTECTION RATED GLAZING.
  
 DOOR 114A IS INDICATED AS A 90 MINUTE DOOR, TYPE 12 A
 SINGLE DOOR WITH LITE SEE TABLE 715.4 AND 715.4.3
  
 DOOR 126A & C BOTH ARE INDICATED AS A DOOR TYPE 9 A
 HOLLOW METAL DOOR BUT THE DEPICTION INDICATES THIS DOOR
 TO BE A WOOD ENTRY DOOR WITH WOOD PANELS, 90 MINUTE
 DOOR?
  
 DOOR 135A & 140A BOTH INDICATE THE DOOR TYPE TO BE A 12
 SINGLE DOOR WITH LITE, SEE TABLE 715.4 AND 715.4.3
  
 DOOR 145B IS LISTED AS A DOOR TYPE 2 HOLLOW METAL 90
 MINUTE DOOR BUT DEPICTED AS A WOOD DOOR.
  
 .DOOR 143A&C BOTH ARE INDICATED AS A DOOR TYPE 9 A
 HOLLOW METAL DOOR BUT THE DEPICTION INDICATES THIS DOOR
 TO BE A WOOD ENTRY DOOR WITH WOOD PANELS, 90 MINUTE
 DOOR?
  
 33) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG