Plan Review Notes
Plan Review Notes For Permit 07110731
Permit Number 07110731
Review Stop P
Sequence Number 1
Notes
Date Text
2007-12-22 06:57:04DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT P-0.1.1 ELECTRIC WATER HEATER - 2 DETAIL
 INDICATES THE EMERGENCY PAN DRAIN DRAINING TO A FLOOR
 DRAIN OR MOP SINK. FLOOR DRAINS ARE NOT APPROVED
 INDIRECT WASTE RECEPTORS. EITHER A FLOOR SINK OR HUB
 DRAIN IS REQUIRED. SECTIONS 802.3 & 802.3.2. PLEASE
 CORRECT DETAIL.
  
 2.SHTSLP-1 THRU LP-4 NOT SEALED AS REQUIRED BY FAC
 61G1-16.003, FS 481.2055 & SECTION 106.1. AN EMBOSSED
 SEAL IS REQUIRED. ALSO THE FIRM LICENSE NUMBER SHALL BE
 INDICATED ON EACH SHEET. FAC 61G1-16.001,
 61G1-16.004(2) & FS 481.306.
  
 3. SHTSP-2.2.0 NO SECONDARY ROOF DRAIN OR EMERGENCY
 OVERFLOW SCUPPER IS INDICATED ON THE SMALL ROOF, RD-1
 (260SF), AS REQUIRED IN SECTION 1107. PLEASE INDICATE
 THE LOCATION OF THE SECONDARY ROOF DRAIN OR EMERGENCY
 OVERFLOW SCUPPER AND INDICATE THE SIZE OF THE DRAIN OR
 SCUPPER. (LENGTH, WIDTH, HEIGHT). SECTION 106.1.2.
  
 4. SHT P-3.1.0 DETAILS 1, 2 & 6NO WASTE ARMS FOR THE
 DRINKING FOUNTAINS ARE SHOWN. PLEASE CLARIFY. SECTION
 106.1.1.
  
 5. SHT P-3.1.0 DETAIL 4 THE FLOOR DRAINS SHALL CONNECT
 TO THE VENTED BRANCH LINE, NOT THE SHOWER DRAIN LINE.
 SECTION 901.2.1.
  
 6. SHT P-4.1.0 DETAIL 4 THE FLOOR DRAINS SHALL CONNECT
 TO THE VENTED BRANCH LINE, NOT THE SHOWER DRAIN LINE.
 SECTION 901.2.1.
  
 7. SHT P-4.1.0 DETAIL 6 DOES NOT REFLECT THE FLOOR
 PLAN. THE FLOOR CLEANOUT SHOWN ON THE FLOOR PLAN NEAR
 THE WATER CLOSET IS NOT SHOWN ON THE RISER DIAGRAM.
 ALSO SHOW THE WASTE ARMS FOR THE DRINKING FOUNTAINS.
 SECTION 106.1.1.
  
 8. SHT P-4.2.0 DETAILS 1 THRU 7. PLEASE IDENTIFY THE
 FITTINGS/DEVICES AT THE TOP OF THE DROPS. THEY ARE NOT
 SHOWN ON THE PLUMBING LEGEND ON SHT P-0.1.1. IF THEY
 ARE AIR CHAMBERS, PLEASE DELETE AS THEY ARE NOT
 APPROVED. SECTION 604.9. IF THEY ARE WATER HAMMER
 ARRESTORS, THEY SHALL BE LOCATED NEAR THE FIXTURES IN
 AN "EFFECTIVE RANGE", NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 9. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO
 THE BUILDING. SECTION 608.13.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  