2007-12-22 06:57:04 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHT P-0.1.1 ELECTRIC WATER HEATER - 2 DETAIL |
| INDICATES THE EMERGENCY PAN DRAIN DRAINING TO A FLOOR |
| DRAIN OR MOP SINK. FLOOR DRAINS ARE NOT APPROVED |
| INDIRECT WASTE RECEPTORS. EITHER A FLOOR SINK OR HUB |
| DRAIN IS REQUIRED. SECTIONS 802.3 & 802.3.2. PLEASE |
| CORRECT DETAIL. |
| |
| 2.SHTSLP-1 THRU LP-4 NOT SEALED AS REQUIRED BY FAC |
| 61G1-16.003, FS 481.2055 & SECTION 106.1. AN EMBOSSED |
| SEAL IS REQUIRED. ALSO THE FIRM LICENSE NUMBER SHALL BE |
| INDICATED ON EACH SHEET. FAC 61G1-16.001, |
| 61G1-16.004(2) & FS 481.306. |
| |
| 3. SHTSP-2.2.0 NO SECONDARY ROOF DRAIN OR EMERGENCY |
| OVERFLOW SCUPPER IS INDICATED ON THE SMALL ROOF, RD-1 |
| (260SF), AS REQUIRED IN SECTION 1107. PLEASE INDICATE |
| THE LOCATION OF THE SECONDARY ROOF DRAIN OR EMERGENCY |
| OVERFLOW SCUPPER AND INDICATE THE SIZE OF THE DRAIN OR |
| SCUPPER. (LENGTH, WIDTH, HEIGHT). SECTION 106.1.2. |
| |
| 4. SHT P-3.1.0 DETAILS 1, 2 & 6NO WASTE ARMS FOR THE |
| DRINKING FOUNTAINS ARE SHOWN. PLEASE CLARIFY. SECTION |
| 106.1.1. |
| |
| 5. SHT P-3.1.0 DETAIL 4 THE FLOOR DRAINS SHALL CONNECT |
| TO THE VENTED BRANCH LINE, NOT THE SHOWER DRAIN LINE. |
| SECTION 901.2.1. |
| |
| 6. SHT P-4.1.0 DETAIL 4 THE FLOOR DRAINS SHALL CONNECT |
| TO THE VENTED BRANCH LINE, NOT THE SHOWER DRAIN LINE. |
| SECTION 901.2.1. |
| |
| 7. SHT P-4.1.0 DETAIL 6 DOES NOT REFLECT THE FLOOR |
| PLAN. THE FLOOR CLEANOUT SHOWN ON THE FLOOR PLAN NEAR |
| THE WATER CLOSET IS NOT SHOWN ON THE RISER DIAGRAM. |
| ALSO SHOW THE WASTE ARMS FOR THE DRINKING FOUNTAINS. |
| SECTION 106.1.1. |
| |
| 8. SHT P-4.2.0 DETAILS 1 THRU 7. PLEASE IDENTIFY THE |
| FITTINGS/DEVICES AT THE TOP OF THE DROPS. THEY ARE NOT |
| SHOWN ON THE PLUMBING LEGEND ON SHT P-0.1.1. IF THEY |
| ARE AIR CHAMBERS, PLEASE DELETE AS THEY ARE NOT |
| APPROVED. SECTION 604.9. IF THEY ARE WATER HAMMER |
| ARRESTORS, THEY SHALL BE LOCATED NEAR THE FIXTURES IN |
| AN "EFFECTIVE RANGE", NOT IN THE CEILING AS SHOWN. |
| PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS. |
| |
| 9. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO |
| THE BUILDING. SECTION 608.13.2. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |