Plan Review Notes
Plan Review Notes For Permit 07110731
Permit Number 07110731
Review Stop M
Sequence Number 1
Notes
Date Text
2007-12-11 10:15:47REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 STATE AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M-0.1.1: VENTILATION DESIGN CRITERIA NOTE #1 STATES
 THE VENTILATION RATE PROCEDURE IS PER ASHRAE 62
 ADDENDUM N. THIS ADDENDUM IS PART OF ASHRAE 62-2001.
 ALL MECHANICAL SYSTEMS SUBMITTED FOR PERMIT AFTER DEC.
 8, 2006 SHALL BE DESIGNED TO EITHER FBC, M SEC.403 OR
 ASHRAE 62.1-2004 W/ APPROVED ADDENDA IN ACCORDANCE WITH
 FBC, M 403.4. DECLARE THE METHOD USED AND SHOW THE
 VENTILATION SYSTEM TO BE DESIGNED IN ACCORDANCE WITH
 THE SPECIFIED METHOD. VENTILATION AND EXHAUST SYSTEMS
 CAN NOT BE REVIEWED AT THIS TIME.
  
 2. M-2.1.0: BASED ON LOCATIONS OF RATED WALLS AS SHOWN
 ON PG A-2.1.3, THERE ARE SEVERAL DUCTS PENETRATING
 RATED WALL ASSEMBLIES WITHOUT OPENING PROTECTIVES (SUCH
 AS FIRE DAMPERS) AS REQUIRED BY FBC, M 607.5. EXAMPLES:
 THERE IS AN 8 INCH ROUND SUPPLY AND AN 8X6 RETURN
 PENETRATING THE CORRIDOR WALL AT STORAGE ROOM 142
 WITHOUT ANY OPENING PROTECTIVES SHOWN AT THESE
 LOCATIONS. THIS OCCURS IN SEVERAL LOCATIONS THROUGHOUT
 CORRIDOR 173. PLEASE CHECK ALL AREAS AND SHOW HOW THESE
 OPENINGS ARE TO BE PROTECTED.
  
 3. M-2.1.0: CORRIDORS 173 AND 167 ARE SHOWN TO BE 1
 HOUR FIRE RESISTANCE RATED ON PG A-2.1.3. A LISTED
 SMOKE DAMPER DESIGNED TO RESIST THE PASSAGE OF SMOKE
 SHALL BE PROVIDED AT EACH POINT A DUCT OR AIR TRANSFER
 OPENING PENETRATES A CORRIDOR ENCLOSURE REQUIRED TO
 HAVE SMOKE AND DRAFT CONTROL DOORS IN ACCORDANCE WITH
 SECTION 715.3.3. SEE FBC 716.5.4.1.
 NOTE: FBC 715.3.3 REQUIRES DOORS IN A 1 HOUR FIRE
 RESISTANCE RATED CORRIDOR TO MEET THE REQUIREMENTS FOR
 A SMOKE-AND DRAFT-CONTROL DOOR ASSEMBLY TESTED IN
 ACCORDANCE WITH UL 1784, WHICH TRIGGERS THE REQUIREMENT
 FOR SMOKE DAMPERS IN FBC 716.5.4.1.
  
 4. M-2.1.0: CORRIDORS 111, 118 AND 120 ARE NOT SHOWN ON
 PLANS TO BE FIRE RESISTANCE RATED. HOWEVER, BASED ON
 THE REQUIREMENTS OF FBC TABLE 1016.1, THESE CORRIDORS
 MAY BE REQUIRED TO BE RATED. PLEASE SEE BUILDING PLAN
 REVIEW FOR REQUIREMENTS RELATED TO THIS ISSUE.
 NOTE: IF THESE CORRIDORS ARE REQUIRED TO BE RATED, THEY
 ARE SUBJECT TO THE SAME REQUIREMENTS AS STATED IN
 COMMENTS 2 AND 3 ABOVE. PLEASE COORDINATE WITH
 ARCHITECT TO ASSURE LOCATIONS OF RATED ASSEMBLIES AND
 OPENING PROTECTIVES CORRESPOND ON ALL PLANS.
  
 5. M-2.1.0: ROOM 127 BOYS RESTROOM SHOWS 8 INCH ROUND
 DUCT TURNING DOWN WITH A FIRE DAMPER. THIS FIRE DAMPER
 APPEARS TO BE IN MID-AIR AND SERVING NO PURPOSE. IS
 THIS DAMPER INTENDED TO BE LOCATED AT THE WALL
 PENETRATION RATHER THAN IN THE VERTICAL DUCT? PLEASE
 CLARIFY. FIRE DAMPERS SHALL BE INSTALLED IN ACCORDANCE
 WITH THE REQUIREMENTS OF THIS SECTION, AND THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS AND LISTING IN
 ACCORDANCE WITH FBC, M 607.2.
  
 6. M-2.1.0: EXHAUST DISCHARGE FOR RESTROOMS 127 AND 128
 APPEARS TO BE DISCHARGING ONTO A WALKWAY. OUTDOOR
 EXHAUST OPENINGS SHALL BE LOCATED SO AS NOT TO CREATE A
 NUISANCE. EXHAUST AIR SHALL NOT BE DIRECTED ONTO
 WALKWAYS IN ACCORDANCE WITH FBC, M 401.5.2.
  
 7. M-2.1.0 AND M-2.2.0: THREE DUCTS FROM AHU-7 ON 2ND
 FLOOR ARE SHOWN PENETRATING BLOCK WALL WHEN LEAVING
 ROOM 214 AND RUNNING IN TRUSSES ABOVE CORRIDOR 167.
 THIS CORRIDOR IS SHOWN AS FIRE RESISTANCE RATED.
 OPENING PROTECTIVES ARE REQUIRED TO MAINTAIN FIRE
 RATING AT THIS LOCATION IN ACCORDANCE WITH FBC, M 607.5
 AND FBC, M 607.5.4.
  
 8. M-2.2.0: DUCT PENETRATIONS AT BLOWER ROOM 208 DO NOT
 SHOW OPENING PROTECTIVES. SHOW HOW THESE OPENINGS ARE
 TO BE PROTECTED IN ACCORDANCE WITH FBC, M 607.5.
  
 9. M-2.2.0: FIRE DAMPERS ARE SHOWN AT DUCT PENETRATIONS
 OF NON-RATED WALLS AT ROOMS 212 AND 214. FIRE DAMPERS
 CAN NOT BE INSTALLED IN ACCORDANCE WITH THEIR LISTING
 IF THEY ARE NOT INSTALLED IN RATED ASSEMBLIES. SHOW
 COMPLIANCE WITH FBC, M 607.2. IF RATED WALLS ARE
 REQUIRED AT THESE LOCATIONS, PLEASE COORDINATE WITH
 ARCHITECTURAL PLANS. IF RATED WALLS ARE NOT REQUIRED AT
 THESE LOCATIONS, PLEASE REMOVE FIRE DAMPERS FROM THESE
 WALLS IN ORDER TO COORDINATE WITH ARCHITECTURAL PLANS.
  
 10. M-2.2.0: CATWALKS ARE SHOWN ABOVE THE SANCTUARY TO
 PROVIDE ACCESS TO ROOF HATCH AND MOTORIZED DAMPERS AT
 RELIEF VENTS. DETAIL 7 ON PG S-7 HAS NO DIMENSIONS
 RELATED TO SPACING AND HEIGHTS OF GUARDS FOR THE
 CATWALKS. PLEASE PROVIDE ALL DIMENSIONAL INFORMATION TO
 SHOW COMPLIANCE WITH FBC, M 304.10.
  
 11. M-4.1.0: DETAIL 4, FCU-1 IS SHOWN APPROX. 2 FEET
 FROM THE WALL OF THE STAIRWELL. SHOW HOW MINIMUM
 SERVICE ACCESS CLEARANCE IS TO BE ACHIEVED IN
 ACCORDANCE WITH FBC, M 306.1 AND MANUFACTURER?S
 INSTRUCTIONS.
  
 12. M-4.1.0: OUTSIDE AIR INTAKES, WALL LOUVERS ARE
 DEFINED AS PANEL WALLS PER FAC RULE 9B-72. AS SUCH, A
 PRODUCT APPROVAL IS REQUIRED. PROVIDE A COMPLETE
 PRODUCT APPROVAL FOR THE TYPE OF LOUVERS TO BE USED TO
 SHOW COMPLIANCE WITH FBC, M 401.5.1. FOR MORE
 INFORMATION ON THE FLORIDA PRODUCT APPROVAL SYSTEM,
 PLEASE VISIT: WWW.FLORIDABUILDING.ORG
  
 13. M-6.0.2: DETAIL 1, FIRE DAMPERS, SMOKE DAMPERS,
 COMBINATION FIRE/SMOKE DAMPERS AND CEILING DAMPERS
 LOCATED WITHIN AIR DISTRIBUTION AND SMOKE CONTROL
 SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 REQUIREMENTS OF THIS SECTION, AND THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS AND LISTING IN ACCORDANCE
 WITH FBC, M 607.2. PLEASE VERIFY THAT THE DETAIL ON
 PLANS IS IN CONFORMANCE WITH THE DAMPER MANUFACTURER?S
 INSTALLATION INSTRUCTIONS OR THE PLANS MAY DEFER TO THE
 MANUFACTURER?S INSTRUCTIONS.
  
 14. M-6.0.2: DETAIL 2, THE THROUGH-PENETRATION FIRESTOP
 SYSTEM SHOWN SAYS AT BOTTOM ?PIPE/INSULATED.? HOWEVER,
 THIS DETAIL DOES NOT ACCOMMODATE INSULATED PIPE, RATHER
 IT CALLS FOR PACKING MATERIAL TO BE USED AS A FORM.
 ALSO PLEASE NOTE THAT THIS DETAIL IS FOR IRON/STEEL
 PIPE PENETRATING CONCRETE ASSEMBLIES ONLY, NOT FOR
 COPPER OR FOR PENETRATING FRAMED/GYPSUM ASSEMBLIES.
 PLEASE VERIFY THAT THIS SYSTEM MEETS ALL THE NEEDS FOR
 THIS PROJECT OR PROVIDE ADDITIONAL THROUGH-PENETRATION
 SYSTEMS FOR OTHER CONDITIONS NOT COVERED BY THIS
 ASSEMBLY. FBC 712.3 AND 712.4.
  
 15. M-7.0.1: SEQUENCE OF OPERATION: EXHAUST FANS ARE
 SHOWN TO BE CONTROLLED BY THE EMS. HOWEVER, FAN
 SCHEDULE ON M-5.0.1 CALLS FOR FANS TO BE CONTROLLED BY
 EITHER INTERLOCK WITH AHU OR LIGHT SWITCH. PLEASE
 CLARIFY HOW THE FANS ARE TO BE CONTROLLED AND MEET THE
 REQUIREMENTS OF FBC, M 401.3.
  
 16. M-7.0.1: SYSTEMS WITH DESIGN OUTSIDE AIR CAPACITIES
 GREATER THAN 3,000 CFM (1.4 M3/S) SERVING AREAS HAVING
 AN AVERAGE DESIGN OCCUPANCY DENSITY EXCEEDING 100
 PEOPLE PER 1,000 FEET (93 M3) SHALL INCLUDE MEANS TO
 AUTOMATICALLY REDUCE OUTSIDE AIR INTAKE BELOW DESIGN
 RATES WHEN SPACES ARE PARTIALLY OCCUPIED. SHOW
 VENTILATION CONTROLS FOR HIGH-OCCUPANCY AREAS IN
 COMPLIANCE WITH FBC 13-409.1.ABC.3.5.
  
 17. M-7.0.1: SHOW OPTIMUM START CONTROLS IN ACCORDANCE
 WITH FBC 13-407.1.ABC.2.4.2.
  
 18. ENERGY CALCULATIONS: THE SIGNATURE OF MR. WAMSLEY
 ON THE FRONT PAGE, WITH THE SEAL AFFIXED, AS WELL AS
 THE SIGNATURE ON THE CERTIFICATIONS PAGE ARE
 PHOTOCOPIES ON ALL 3 SETS OF CALCULATIONS SUBMITTED. A
 PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND AFFIX HIS
 SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS, FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE OWNER?S
 REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED OR ISSUED
 BY SAID REGISTRANT AND BEING FILED FOR PUBLIC RECORD IN
 ACCORDANCE WITH FAC RULE 61G15-23.002(1). ONLY ORIGINAL
 SIGNATURES SHALL BE PROVIDED AND SEALED IN ACCORDANCE
 WITH THIS RULE. PROVIDE ENERGY CALCULATIONS WITH
 ORIGINAL SEAL AND SIGNATURE OF THE DESIGNER RESPONSIBLE
 FOR THEIR PREPARATION IN ACCORDANCE WITH FBC
 13-103.1.1.1.
  
 19. ENERGY CALCULATIONS: THE COMPLIANCE FORM WAS NOT
 SIGNED BY THE OWNER OR THE OWNER?S AGENT. THE
 BUILDING?S OWNER, THE OWNER?S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE IN ACCORDANCE WITH FBC 13-103.1.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]