Plan Review Notes
Plan Review Notes For Permit 07110731
Permit Number 07110731
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-01-03 23:20:56*****DENIED*****
  
  
 05. ON SHEET FP 4 IN THE DOUBLE CHECK DETECTOR ASSEMBLY
 DETAIL, INDICATE IN THE NOTES AND/OR ILLUSTRATE THAT
 THE DEVICE IS TO BE CHAINED AND LOCKED (AS PER WEST
 PALM BEACH FIRE PREVENTION BUREAU) .
  
 08. ON SHEET A-0.1.1, PROVIDE THE OCCUPANT LOAD LOAD
 FOR THIS NEW ASSEMBLY STRUCTURE, AS IN THE NUMBER OF
 PERSONS WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE
 REQUIRED.
  
 17. PLEASE NOTE AND (OR) ILLUSTRATE ON AN APPROPIATE
 PLAN SHEET THAT KNOX LOCKING CAPS WILL BE REQUIRED ON
 FIRE DEPARTMENT CONNECTION (FDC). FOR APPLICATIONS,
 CONTACT WEST PALM BEACH FIRE PREVENTION BUREAU AT
 561-804-4724.
  
  
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE IN THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722