2007-12-12 10:08:45 | FAILED FOR FOLLOWING REASONS: |
| |
| 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). |
| PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR |
| NOI. |
| YOU CAN GET NOI INFO FROM |
| WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ |
| NOTICE OF INTENT DEP FORM 62-621.300(4)(B), |
| EFFECTIVE MAY 1, 2003 |
| |
| 2. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR |
| SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP |
| PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL |
| CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING |
| SERVICES, PHONE# 494-1040 |
| |
| 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE |
| DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION |
| MUST BE ACCESSIBLE FOR PICKUP TRUCK. |
| |
| 4. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED |
| FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA |
| AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST |
| FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE |
| ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD. |
| |
| 5. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA, |
| GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU |
| ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE |
| THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH |
| AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE |
| PROVIDE A COPY OF THESE WATER QUALITYCALCULATIONS. |
| |
| 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE |
| SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM |
| ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE |
| CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING |
| ELEVATION, ETC ON DRAWINGS, CALCULATION FOR |
| EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET |
| DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL |
| THESE. |
| |
| 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND |
| YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET |
| FLOODED AND HAVE ENOUGH DRAINS. |
| |
| 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,,GEO-TECH |
| REPORT &STORM WATER QUALITY CALCULATIONS. STORM WATER |
| CALS MUST BE APPROVED FROM 100045TH STREET |
| ENGINEERING SERVICES. |
| |
| 9. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION |
| DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT |
| FENCE AROUND THE SITE & CATCH BASINS DURING |
| CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT OF FENCE |
| SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST PARTICLES. |
| |
| 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH |
| STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED. |
| |
| PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR |
| PERMITTING PROCESS |
| |
| RASIK CHOKSHI805-6723 |
| |